Plan Review Details - Permit 22091292
Plan Review Stops For Permit 22091292
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By rmcphers Date 2023-03-16 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2023-03-16 Time 14:33 Sent To  
Notes
2023-03-16 14:33:50PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 08:48 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 16:48 Sent To  
Notes
2022-11-14 08:50:36PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By rmcphers Date 2023-03-16 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2023-03-16 Time 13:59 Sent To  
Notes
2023-03-16 14:15:48ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE PRODUCT APPROVALS PROVIDED DO NOT HAVE THE SAME
 PRODUCT APPROVAL NUMBERS AS SHOWN ON DRAWING A3
 "FENESTRATION SCHEDULE" PLEASE UP DATE THE PRODUCT
 APPROVALS NUMBERS ON THE "FENESTRATION SCHEDULE"
  
 2) A PRODUCT APPROVAL FOR SLIDING GLASS DOORS HAS BEEN
 PROVIDED - PLEASE SHOW THE LOCATION OF THE SLIDING
 GLASS DOORS ON THE DRAWING.
  
 3) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING SPACE TO THE ENTRY - FBC 206.2.1
  
 4) PLEASE PROVIDE A SURVEY - EXTERIOR SWINGING DOORS
 CANNOT ENCROACH INTO THE RIGHT-OF-WAY - FBC 3202.2
  
 5) JOB COST SHOWN ON THE PERMIT APPLICATION APPEARS TO
 BE LOW - PLEASE PROVIDE A COST BREAK DOWN ( ALL
 MATERIALS AND LABOR NEEDS TO BE INCLUDED IN THE JOB
 COST) - FBC WPB 109.3
  
 6) SIGNED AND SEALED DRAWINGS C-1, S-1, A-1, BOTH A-3,
 (YES - THERE A 2 SEPARATE A-3 DRAWINGS) E1.1, E2.1,
 E4.1, FA1.1, E0.1, FA0.1 AND THE RESPONSE LETTER FROM
 DANIEL J. MOSS P.E. WHICH INCLUDES ACCESSIBILITY
 DETAILS - DO NOT SHOW IN ADOBE READER AS DIGITALLY
 SIGNED - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 16:48 Sent To  
Notes
2022-11-14 09:01:18ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING C-1 SHOWS BUILDING CONSTRUCTION TYPE II -
 DRAWING A3 SHOWS WOOD FRAMING - PLEASE SHOW WOOD
 FRAMING TO BE FIRE RETARDANT WOOD PER FBC 603.1
 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 2) PLEASE PROVIDE COPIES OF THE PRODUCT APPROVALS SHOWN
 ON DRAWING A-3 FOR THE WINDOWS AND DOORS.
  
 3) PLEASE SHOW THE ACCESSIBLE BAR SEATING - SHOW THE
 FLOOR SPACE, COUNTER HEIGHT, TOE AND KNEE CLEARANCE PER
 FBC ACCESSIBILITY 226
  
 4) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING SPACE TO THE ENTRY - FBC 206.2.1
  
 5) SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By jleahy Date 2023-03-24 Time 11:01 Rev Time 0.00
Received By jleahy Date 2023-03-24 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-26 Cont ID  
Sent By jleahy Date 2022-10-26 Time 11:29 Rev Time 0.00
Received By jleahy Date 2022-10-26 Time 10:45 Sent To  
Notes
2022-10-26 11:31:23FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS 600A MAIN WITH 400A WIRE, PLEASE CORRECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-17 Cont ID  
Sent By cwalker Date 2023-03-17 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-17 09:34:28FIRE PROVISO COMMENTS:
  
 (1) INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS
 A, CLASS B, OR CLASS C. NFPA 101, 12.3.3.3
  
 (2) EXTERIOR EXIT DOOR HARDWARE LATCHING DEVICES SHALL
 BE PANIC HARDWARE. NFPA 101, 12.2.2.2.4 (2)
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-11 Cont ID  
Sent By cwalker Date 2022-10-11 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-11 11:30:28FIRE REVIEW COMMENTS:
  
 (1) PROVIDE AN INTERIOR FINISH SCHEDULE TO COMPLY WITH
 NFPA 101, CHAPTER 10
  
 (2) PROVIDE A DOOR HARDWARE SCHEDULE FOR ALL REQUIRED
 EXIT DOORS TO COMPLY WITH NFPA 101 12.2.2.2
  
 (3) PROVIDE THE TOTAL OCCUPANT LOAD FOR THE SPACE. NFPA
 101, 12.1.7
  
 (4) PROVIDE THE TRAVEL DISTANCE TO ALL REQUIRED EXITS.
 NFPA 101, 12.2.6
  
 (5) PROVIDE DETAIL ON THE EXIT DISCHARGE TO COMPLY WITH
 NFPA 101 12.2.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-24 Cont ID  
Sent By jleahy Date 2023-03-24 Time 11:01 Rev Time 0.00
Received By jleahy Date 2023-03-15 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2022-10-07 Time 11:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 09:10 Sent To  
Notes
2022-11-14 09:11:00PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-17 Cont ID  
Sent By medwards Date 2023-03-17 Time 06:02 Rev Time 0.00
Received By medwards Date 2023-03-17 Time 06:02 Sent To  
Notes
2023-03-17 06:03:39PLEASE RESPOND TO THE COMMENTS BELOW FROM THE PREVIOUS
 REVIEW CYCLE. I CANNOT FIND PERMITS FOR AN EXISTING
 RESTAURANTAT THIS ADDRESS.
  
 1) IS THIS A CHANGE OF OCCUPANCY? IF SO, PROVIDE THE
 CURRENT OCCUPANCY.
 2) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS TENANT
 SPACE INCLUDING MECHANICAL DRAWINGS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-19 Cont ID  
Sent By medwards Date 2022-10-19 Time 17:09 Rev Time 0.00
Received By medwards Date 2022-10-19 Time 17:09 Sent To  
Notes
2022-10-19 17:19:231) IS THIS A CHANGE OF OCCUPANCY? IF SO, PROVIDE THE
 CURRENT OCCUPANCY.
 2) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS TENANT
 SPACE INCLUDING MECHANICAL DRAWINGS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By rwbrown Date 2023-03-20 Time 12:21 Rev Time 0.00
Received By rwbrown Date 2023-03-20 Time 12:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By rwbrown Date 2022-10-17 Time 08:26 Rev Time 0.00
Received By rwbrown Date 2022-10-17 Time 08:24 Sent To  
Notes
2022-10-17 08:29:321ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - IT APPEARS THAT THE FIXTURES
 PROVIDED DO NOT MEET THE OCCUPANT LOAD SHOWN ON PAGE
 C-1 AT 120 PEOPLE.
  
 2. 2017 WPB AMENDS 107.2.1 - THERE IS A TABLE OF
 CONTENTS PROVIDE ON PAGE C-1 THAT DOES NOT MATCH THE
 PAGES PROVIDED. I DO NOT SEE THE EXISTING FLOOR PLAN.
  
 3. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL MEET THE ASSE 1017
 STANDARD AND BE INSTALLED AT THE HOT WATER SOURCE PER
 613.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By rmcphers Date 2023-03-16 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2023-03-16 Time 14:20 Sent To  
Notes
2023-03-16 14:21:37SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS C-1, S-1, A-1, BOTH A-3,
 E1.1, E2.1, E4.1, FA1.1, E0.1, FA0.1 AND THE RESPONSE
 LETTER FROM DANIEL J. MOSS P.E. WHICH INCLUDES
 ACCESSIBILITY DETAILS - DO NOT SHOW IN ADOBE READER AS
 DIGITALLY SIGNED - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 09:12 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 09:12 Sent To  
Notes
2022-11-14 09:13:29SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-10-26 11:32:58SIGNATURES DON'T SEEM TO BE VERIFIABLE.

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-20 Cont ID  
Sent By asangele Date 2023-03-20 Time 11:39 Rev Time 0.00
Received By asangele Date 2023-03-20 Time 11:39 Sent To  
Notes
2023-03-20 11:39:503/20/2023
 FAILED
 REPEAT COMMENT
  
 PLEASE REACH OUT TO ANGELLA VANN OR ERIC SCHNEIDER TO
 DISCUSS AND SEE IF WHAT YOU ARE PROPOSING WOULD MEET
 THE CRITERIA TO OBTAIN A LIQUOR LICENSE.
  
 ANGELLA: 561-822-1441
 ERIC: 561-822-1446
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By asangele Date 2022-10-20 Time 12:04 Rev Time 0.00
Received By asangele Date 2022-10-20 Time 12:04 Sent To  
Notes
2022-10-20 12:10:1410/20/2022
 FAILED
  
  
 PLEASE REACH OUT TO ANGELLA VANN OR ERIC SCHNEIDER TO
 DISCUSS AND SEE IF WHAT YOU ARE PROPOSING WOULD MEET
 THE CRITERIA TO OBTAIN A LIQUOR LICENSE.
  
 ANGELLA: 561-822-1441
 ERIC: 561-822-1446
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]