Plan Review Details - Permit 22090841
Plan Review Stops For Permit 22090841 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-10-11 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-10-11 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-10-07 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-10-05 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-10-05 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-10-02 |
Time |
08:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-09-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-27 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-22 |
Time |
09:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2022-10-10 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-10-10 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2022-10-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-10-03 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-10-03 |
Time |
07:42 |
Sent To |
|
|
Notes |
2022-10-03 07:54:59 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 22090841 | | 10/3/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW FROM THE | | 1ST REVIEW WERE NOT ADDRESSED. PLEASE CONTACT ME BY | | PHONE IF YOU NEED FURTHER ASSISTANCE. | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WATTS SERIES 919 | | DOES NOT SHOW THAT THE DEVICE IS LEAD FREE PER THE | | NSF/ANSI 61 STANDARD (0.25% MAX WEIGHTED AVERAGE LEAD | | CONTENT.) | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-09-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-09-23 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-09-23 |
Time |
16:08 |
Sent To |
|
|
Notes |
2022-09-23 16:23:38 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22090841 | | 9/23/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WATTS SERIES 919 | | DOES NOT SHOW THAT THE DEVICE IS LEAD FREE PER THE | | NSF/ANSI 61 STANDARD (0.25% MAX WEIGHTED AVERAGE LEAD | | CONTENT.) | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
3 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
2 |
Status |
F |
Date |
2022-10-11 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-10-11 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-10-11 |
Time |
12:11 |
Sent To |
|
|
Notes |
2022-10-11 12:11:26 | PER MHURLEY - BACKFLOW ASSEMBLY IS NOT LEAD FREE. | | SUBMIT NEW SPEC SHEET FOR LEAD-FREE RP BACKFLOW | | ASSEMBLY. |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-10-05 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-10-05 |
Time |
07:50 |
Sent To |
|
|
Notes |
2022-10-05 07:51:24 | PER MHURLEY - BACKFLOW ASSEMBLY IS NOT LEAD FREE. | | SUBMIT NEW SPEC SHEET FOR LEAD-FREE RP BACKFLOW | | ASSEMBLY. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |