Plan Review Details - Permit 22090839
Plan Review Stops For Permit 22090839
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-04 Cont ID  
Sent By medwards Date 2022-11-04 Time 09:00 Rev Time 0.00
Received By medwards Date 2022-10-27 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-05 Cont ID  
Sent By medwards Date 2022-10-05 Time 09:51 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 06:09 Rev Time 0.00
Received By medwards Date 2022-09-30 Time 10:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 06:25 Rev Time 0.00
Received By medwards Date 2022-09-27 Time 05:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-11-04 Cont ID  
Sent By medwards Date 2022-11-04 Time 09:00 Rev Time 0.00
Received By medwards Date 2022-11-04 Time 09:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-10-05 Cont ID  
Sent By medwards Date 2022-10-05 Time 09:47 Rev Time 0.00
Received By medwards Date 2022-10-05 Time 09:47 Sent To  
Notes
2022-10-05 09:51:34PLEASE ADDRESS COMMENT NUMBER 1 OF PREVIOUS REVIEWS...
 YOU ARE CONDITIONING A SPACE THAT WAS NEVER CONDITIONED
 BEFORE, THE GARAGE. YOU MUST PROVIDE THE ENERGY
 CALCULATIONS FOR THIS SPACE. YOU HAVE PROVIDED THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS, NOW PROVIDE
 THE ENERGY CALCULATIONS.
  
 FEC R101.5.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE CODE OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
 ALTERNATIVELY, A FLORIDA RESCHECK COMPUTER PRINTOUT MAY
 BE SUBMITTED TO DEMONSTRATE COMPLIANCE BY SECTIONS
 R402, R403 AND R404.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 06:05 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 06:05 Sent To  
Notes
2022-10-03 06:08:47PLEASE ADDRESS PREVIOUS REVIEW COMMENTS BELOW:
  
 THE DOCUMENT SUBMITTED AS GRASS HEAT LOAD IS THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE SHOW
 THE INSULATION VALUES FOR THE GARAGE AND THAT THEY MEET
 THE FEC IN THE ENERGY CALCULATIONS I HAVE ASKED FOR
 BELOW.
  
  
 1ST REVIEW FMC
 PERMIT: 22090839
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS GARAGE. FEC
 R402
  
 2) PROVIDE A MECHANICAL DRAWING IDENTIFYING THE
 LOCATION OF THE MINI SPLIT HEAD AND THE CONDENSING UNIT
 LOCATION. PLEASE ALSO SHOW THE CONDENSATE DRAIN PIPE
 MATERIAL AND TERMINATION LOCATION. FBC 107.3.5
  
 3) SHOW THE TIE DOWN METHOD USED FOR ANCHORING THE
 CONDENSING UNIT. M1307.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 06:24 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 06:24 Sent To  
Notes
2022-09-29 06:24:551ST REVIEW FMC
 PERMIT: 22090839
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS GARAGE. FEC
 R402
  
 2) PROVIDE A MECHANICAL DRAWING IDENTIFYING THE
 LOCATION OF THE MINI SPLIT HEAD AND THE CONDENSING UNIT
 LOCATION. PLEASE ALSO SHOW THE CONDENSATE DRAIN PIPE
 MATERIAL AND TERMINATION LOCATION. FBC 107.3.5
  
 3) SHOW THE TIE DOWN METHOD USED FOR ANCHORING THE
 CONDENSING UNIT. M1307.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 06:25 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 06:25 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved