Plan Review Details - Permit 22090764
Plan Review Stops For Permit 22090764
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By rmcphers Date 2023-02-17 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2023-02-17 Time 10:49 Sent To  
Notes
2023-02-17 11:02:37REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE SMOKE DETECTOR LOCATIONS - FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By fgiaquin Date 2023-04-17 Time 18:31 Rev Time 0.00
Received By fgiaquin Date 2023-04-13 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-21 Cont ID  
Sent By fgiaquin Date 2023-03-21 Time 20:15 Rev Time 0.00
Received By fgiaquin Date 2023-03-21 Time 19:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By fgiaquin Date 2023-02-01 Time 23:29 Rev Time 0.00
Received By fgiaquin Date 2023-02-01 Time 22:37 Sent To  
Notes
2023-02-01 23:29:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS NOT READABLE. PROVIDE LEGIBLE PLAN FOR
 REVIEW.
  
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2. PROVIDE PANEL SCHEDULE, FBC 107.2.1 NEC 215 NEC 220
  
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
  
 4. SEVERAL RECEPTACLE SPACING VIOLATIONS. PROVIDE
 CORRECTIONS. NEC 210.52
  
 5. SMOKE/CO ALARMS REQUIRED PER FBC 314 AND 315.
 PROVIDE CORRECTIONS.
  
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
  
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
  
 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
  
 9. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12
  
 10. AT LEAST ONE LIGHTING OUTLET CONTROLLED BY A LISTED
 WALL MOUNTED CONTROL DEVICE SHALL BE INSTALLED IN EVERY
 HABITABLE ROOM, KITCHEN, AND BATHROOM. THE WALL MOUNTED
 CONTROL DEVICE SHALL BE LOCATED NEAR AN ENTRANCE TO THE
 ROOM ON A WALL. (A SWITCHED RECEPTACLE OR HIGH HATS IN
 EACH ROOM WILL SUFFICE, A FAN WILL NOT). NEC 210.70A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-17 Cont ID  
Sent By fgiaquin Date 2023-04-17 Time 18:31 Rev Time 0.00
Received By fgiaquin Date 2023-04-11 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-21 Cont ID  
Sent By fgiaquin Date 2023-03-21 Time 20:16 Rev Time 0.00
Received By fgiaquin Date 2023-03-17 Time 06:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-17 Cont ID  
Sent By rmcphers Date 2023-02-17 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2023-01-27 Time 06:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 11:09 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 11:09 Sent To  
Notes
2023-01-30 11:10:27LIKE FOR LIKE CHANGE OUT ONLY. NO NEW DUCTWORK. ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By ccole Date 2023-01-30 Time 09:05 Rev Time 0.00
Received By ccole Date 2023-01-30 Time 08:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-12 Cont ID  
Sent By jleahy Date 2023-04-12 Time 16:50 Rev Time 0.00
Received By jleahy Date 2023-04-12 Time 16:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-20 Cont ID  
Sent By jgomez Date 2023-03-20 Time 11:10 Rev Time 0.00
Received By jgomez Date 2023-03-20 Time 11:09 Sent To  
Notes
2023-03-20 11:12:08SIGNATURE REVIEW:
  
 1- HARD COPY OF DRAWING E-1 NEEDS ENGINEER'S WET
 SIGNATURE. PLANS/DOCUMENTS NEED TO HAVE THE ORIGINAL
 SEAL/SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY
 SEC. 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN
 SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-27 Cont ID  
Sent By mpeterso Date 2023-01-27 Time 08:47 Rev Time 0.00
Received By mpeterso Date 2023-01-27 Time 08:47 Sent To  
Notes
2023-01-27 09:04:321/27/23 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP