Plan Review Details - Permit 22090368
Plan Review Stops For Permit 22090368
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By rmcphers Date 2023-01-26 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2023-01-26 Time 13:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcphers Date 2022-10-27 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2022-10-27 Time 12:53 Sent To  
Notes
2022-10-27 12:53:33PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 08:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By rmcphers Date 2023-01-26 Time 14:01 Rev Time 0.00
Received By rmcphers Date 2023-01-26 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcphers Date 2022-10-27 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2022-10-27 Time 12:53 Sent To  
Notes
2022-10-27 13:04:28ADD WALLS AND GARAGE DOOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS - DOOR
 WIDTH, TOILET GRAB BAR LOCATION DIMENSIONS, TOILET
 PAPER HOLDER LOCATION DIMENSIONS, MIRROR LOCATION
 DIMENSIONS, CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES
 ETC. PER FBC ACCESSIBILITY 213.1
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR OVERHEAD GARAGE
 DOOR.
  
 3) DRAWINGS NEED ARCHITECTS LICENSE NUMBER IN THE TITLE
 BLOCK - SEE FAC 61G1-16.004
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-27 Cont ID  
Sent By jleahy Date 2023-03-27 Time 10:38 Rev Time 0.00
Received By jleahy Date 2023-03-27 Time 10:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 13:59 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By mpeterso Date 2022-10-17 Time 09:15 Rev Time 0.00
Received By mpeterso Date 2022-10-17 Time 09:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-03-21 Cont ID  
Sent By pleduc Date 2023-03-21 Time   Rev Time 0.00
Received By pleduc Date 2023-03-21 Time 14:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By pleduc Date 2023-01-26 Time   Rev Time 0.00
Received By pleduc Date 2023-01-26 Time 15:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By pleduc Date 2022-10-17 Time   Rev Time 0.00
Received By pleduc Date 2022-10-17 Time 12:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-04-05 Time   Rev Time 0.00
Received By lmarchan Date 2023-03-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 13:59 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-28 Time   Rev Time 0.00
Received By lmarchan Date 2022-09-09 Time 14:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 11:18 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 11:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-30 Cont ID  
Sent By ccole Date 2023-01-30 Time 14:19 Rev Time 0.00
Received By ccole Date 2023-01-30 Time 12:26 Sent To  
Notes
2023-01-30 14:20:372ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22090368
 1/30/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-2: THE SANITARY ISOMETRIC DRAWING WAS
 REMOVED FROM THE RESUBMITTED PLAN. PLEASE SUBMIT A
 REVISED DRAWING - SEC. 107.2.1 & 107.3.5.1.3 WPB.
 PLEASE NOTE THE FOLLOWING 1ST REVIEW COMMENTS
 CONCERNING THE ISO:
 A) THE KITCHENETTE SINK DRAIN SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROOM HORIZONTAL WET VENT, AND
 SHALL BE SEPARATELY VENTED PER SECS. 912.1 & 912.1.1
 FBC P.
 B) THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL
 HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS- SEC. 904.1 FBC P.
 C) THE PREVIOUS ISOMETRIC DID NOT INCLUDE THE DRAINAGE
 AND VENTING FOR THE DRINKING FOUNTAINS.
  
 2) A-2 & A-3: THE LAVATORY AND TOILET CONFIGURATION IN
 THE DETAIL ON A-3 DOES NOT MATCH THE CONFIGURATION
 SHOWN ON THE FLOOR PLAN ??? SEC. 107.2.1 WPB AND SECS.
 603.3 & 606.2 FBC ACC.
  
 3) A-3, DETAIL D-2: PLEASE SHOW THE KNEE AND TOE
 CLEARANCES FOR THE LAVATORY AS SHOWN IN FIGURES 306.2 &
 306.3 FBC ACC. MISSING FROM THE DETAIL ARE THE MINIMUM
 AND MAXIMUM 17-25 INCHES TOE CLEARANCES UNDER THE LAV,
 AND THE 8-INCH MINIMUM KNEE CLEARANCE.
  
 4) A-3: SHOW THE HEIGHT OF THE MIRROR FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACE- SEC. 603.3.
  
 5) A-3: PLEASE SHOW THE HEIGHTS OF THE GRAB BARS
 MEASURED TO THE TOPS OF THE GRIPPING SURFACES- SEC.
 609.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-28 Cont ID  
Sent By ccole Date 2022-10-28 Time 07:47 Rev Time 0.00
Received By ccole Date 2022-10-28 Time 06:59 Sent To  
Notes
2022-10-28 07:48:561ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22090368
 10/28/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: THE KITCHENETTE SINK DRAIN SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM HORIZONTAL OR
 VERTICAL WET VENT, AND SHALL BE SEPARATELY VENTED PER
 SECS. 912.1 & 912.1.1 FBC P.
  
 2) E-1: THE VENT SYSTEM SERVING EACH BUILDING DRAIN
 SHALL HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO
 THE OUTDOORS- SEC. 904.1 FBC P.
  
 3) A-2 & E-1: SHOW THE LOCATIONS OF THE REQUIRED
 SERVICE SINK AND DRINKING FOUNTAINS FOR THE OCCUPANCY-
 SEE TABLE 403.1 & SEC. 410.3 FBC P- A MINIMUM OF TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED- ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
  
 4) E-1: REVISE THE SANITARY ISOMETRIC TO THE SHOW THE
 DRAINAGE AND VENT SYSTEMS FOR THE ADDITIONAL REQUIRED
 FIXTURES, AND PROVIDE A WATER RISER THAT AND THE HOT
 AND COLD WATER SUPPLY PIPES TO THE FIXTURES AND THE
 SOURCE OF THE HOT WATER- SEC. 107.3.5.1.3 WPB AND SEC.
 607.1 FBC P. CLARIFY IF THERE IS AN EXISTING WATER
 HEATER IN THE SPACE OR IF A NEW UNIT WILL BE INSTALLED.
  
 A) TEMPERATURE LIMITING MEANS ??? PLEASE NOTE THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY- SEC. 607.1.1 FBC P.
  
 B) PLEASE NOTE THAT IF HOT WATER IS SUPPLIED TO THE
 LAVATORY THE WATER SHALL BE TEMPERED PER SEC. 419.5 FBC
 P. A TEMPERATURE LIMITING DEVICE CONFORMING TO ASSE
 1070 SHALL BE PROVIDED- SEC. 607.1.2 FBC P.
  
 C) PROVIDE HOT WATER PIPING INSULATION DETAILS- TABLE
 C403.
  
 5) A-2 & E-1: PROVIDE THE FOLLOWING DETAILS FOR THE
 BATHROOM AND KITCHEN FIXTURES ON THE PLAN IN COMPLIANCE
 WITH THE FBC ACC.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORY AND KITCHEN SINKS- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY AND KITCHEN SINK RIMS OR
 COUNTER SURFACE FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY AND KITCHEN
 SINK- SECTION 606.2. PLEASE NOTE A PARALLEL APPROACH IS
 ACCEPTABLE FOR THE KITCHEN SINK.
 L) DRINKING FOUNTAINS- REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 6) A-2: PROVIDE A SLAB REPAIR AND SOIL TREATMENT
 DETAIL- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-27 Cont ID  
Sent By jleahy Date 2023-03-27 Time 10:35 Rev Time 0.00
Received By jleahy Date 2023-03-27 Time 10:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 08:43 Sent To  
Notes
2023-03-24 08:48:16SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A-1 AND E-1 DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By rmcphers Date 2023-01-26 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2023-01-26 Time 13:48 Sent To  
Notes
2023-01-25 16:32:38SIGNED FILES IN SIGNATURES FOLDER. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By mpeterso Date 2022-10-17 Time 09:15 Rev Time 0.00
Received By mpeterso Date 2022-10-17 Time 09:15 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved