Plan Review Details - Permit 22090273
Plan Review Stops For Permit 22090273
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 10:04 Rev Time 0.00
Received By medwards Date 2022-10-02 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-30 Cont ID  
Sent By medwards Date 2022-09-30 Time 09:44 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-26 Cont ID  
Sent By medwards Date 2022-09-26 Time 09:49 Rev Time 0.00
Received By medwards Date 2022-09-23 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-22 Cont ID  
Sent By medwards Date 2022-09-22 Time 08:01 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 10:04 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-09-30 Cont ID  
Sent By medwards Date 2022-09-30 Time 09:38 Rev Time 0.00
Received By medwards Date 2022-09-30 Time 09:38 Sent To  
Notes
2022-09-30 09:43:38THE DRYER DUCT TERMINATION MUST MEET FRC M1502.3.1. IT
 CANNOT HAVE ANYTHING AFTER THE DAMPER, NO SCREEN.
  
 FRC M1502.3.1: EXHAUST DUCT TERMINATIONS SHALL BE
 EQUIPPED WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE
 INSTALLED AT THE DUCT TERMINATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-26 Cont ID  
Sent By medwards Date 2022-09-26 Time 09:45 Rev Time 0.00
Received By medwards Date 2022-09-26 Time 09:45 Sent To  
Notes
2022-09-26 09:46:52PLEASE ADDRESS THE ORIGINAL REVIEW COMMENTS BELOW:
  
 1) PROVIDE THE DUCT SIZES AND THE MATERIAL FOR THE
 EXHAUST FANS AND THE DRYER EXHAUST. FBC 107.3.5
 2) THE DESIGNER OF THE DRAWINGS MUST INCLUDE THEIR
 PRINTED NAME AND SIGNATURE ON EACH DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By medwards Date 2022-09-22 Time 07:56 Rev Time 0.00
Received By medwards Date 2022-09-22 Time 07:56 Sent To  
Notes
2022-09-22 08:00:271) PROVIDE THE DUCT SIZES AND THE MATERIAL FOR THE
 EXHAUST FANS AND THE DRYER EXHAUST. FBC 107.3.5
 2) THE DESIGNER OF THE DRAWINGS MUST INCLUDE THEIR
 PRINTED NAME AND SIGNATURE ON EACH DRAWING. FBC 107.2.1
 3) ALL DRAWINGS MUST ALSO HAVE THE JOB ADDRESS INCLUDED
 ON THE DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2022-09-30 Cont ID  
Sent By medwards Date 2022-09-30 Time 09:43 Rev Time 0.00
Received By medwards Date 2022-09-30 Time 09:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-09-26 Cont ID  
Sent By medwards Date 2022-09-26 Time 09:47 Rev Time 0.00
Received By medwards Date 2022-09-26 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-22 Cont ID  
Sent By medwards Date 2022-09-22 Time 08:00 Rev Time 0.00
Received By medwards Date 2022-09-22 Time 08:00 Sent To  
Notes
2022-09-22 08:01:06DIGITAL SIGNATURE NOT REQUIRED.ME