Plan Review Details - Permit 22090260
Plan Review Stops For Permit 22090260
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 16:03 Rev Time 0.00
Received By cthroop Date 2022-11-04 Time 15:13 Sent To  
Notes
2022-11-04 16:07:181ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA
 FOR THE PROPOSED WINDOWS AND EXT. DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOAS DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-14 Cont ID  
Sent By mpeterso Date 2022-10-14 Time 09:57 Rev Time 0.00
Received By mpeterso Date 2022-10-14 Time 09:30 Sent To  
Notes
2022-10-14 15:17:21ELECTRIC REVIEW FAILED
 1) SHEET E-200 IS MIS LABELED IN SUBMITTAL AS M-200
 PLEASE CORRECT NAME IN SUBMITTAL, OTHERWISE, ELECTRICAL
 WOULD PASS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 16:07 Rev Time 0.00
Received By cthroop Date 2022-10-03 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By medwards Date 2022-10-05 Time 06:16 Rev Time 0.00
Received By medwards Date 2022-10-05 Time 06:16 Sent To  
Notes
2022-10-05 06:16:591ST REVIEW FMC
 PERMIT: 22090260
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) OUR RECORDS INDICATE THERE HAS BEEN NO PERMITTED
 MECHANICAL SYSTEM INSTALLED AT THIS ADDRESS. PLEASE
 SUBMIT THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR
 THIS PROJECT.
  
 2) PROVIDE THE ENERGY CALCULATIONS. FBC 107.3.5
  
 3) THE DRYER DUCT MUST MEET THE MATERIAL REQUIREMENTS
 OF FMC M1502.4.1
  
 M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A
 SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL
 HAVING A MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE).
 THE DUCT SHALL BE 4 INCHES (102 MM) NOMINAL IN
 DIAMETER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-10-05 Cont ID  
Sent By rwbrown Date 2022-10-05 Time 15:47 Rev Time 0.00
Received By rwbrown Date 2022-10-05 Time 15:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By medwards Date 2022-10-05 Time 06:40 Rev Time 0.00
Received By medwards Date 2022-10-05 Time 06:40 Sent To  
Notes
2022-10-05 06:42:56THE DESIGNER NADER GOUBRAN'S IGC CA 1 CERTIFICATE HAS
 EXPIRED MAKING HIS DIGITAL SIGNATURE INVALID. PLEASE
 UPDATE THE CERTIFICATE AND DIGITALLY SIGN THE DOCUMENTS
 BEFORE RESUBMITTAL. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By asangele Date 2022-10-13 Time 14:35 Rev Time 0.00
Received By asangele Date 2022-10-13 Time 14:35 Sent To  
Notes
2022-10-13 14:38:2610/13/2022
 FAIL
  
 PLEASE PROVIDE A SURVEY WITH APPLICATION WITH LABELED
 SETBACKS OF THE HOME
  
 A LANDSCAPE PERMIT IS REQUIRED
 THE VALUE OF THE CONSTRUCTION ($70,000) EXCEEDS 50% OF
 THE STRUCTURE'S IMPROVEMENT VALUE ($56,322) ACCORDING
 TO THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]