Plan Review Details - Permit 22090133
Plan Review Stops For Permit 22090133
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-21 Cont ID  
Sent By rmcdouga Date 2022-12-21 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2022-12-21 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By rmcdouga Date 2022-11-15 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2022-11-15 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By rmcdouga Date 2022-10-24 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2022-10-24 Time 14:07 Sent To  
Notes
2022-10-24 15:29:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE DIAMETER OF THE TAPCON ANCHORS FOR THE
 POOL EQUIPMENT ANCHORING ON SHEET 6. FBC 107.2.1
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE POOL BARRIER
 FENCE. FBC-R 4501.17
  
 3) THE POOL EQUIPMENT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA AND IS REQUIRED TO BE LOCATED AT OR ABOVE
 THE FINISH FLOOR ELEVATION OF THE DWELLING. FBC-R322
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By ppetty Date 2022-10-31 Time 11:36 Rev Time 0.00
Received By ppetty Date 2022-10-31 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-22 Cont ID  
Sent By ppetty Date 2022-09-22 Time 09:30 Rev Time 0.00
Received By ppetty Date 2022-09-22 Time 09:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 11:02 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 09:54 Sent To  
Notes
2022-09-16 11:04:12A SEPARATE PLAN SUBMITTAL AND PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GAS PIPING FOR THE POOL HEATER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-21 Cont ID  
Sent By rmcdouga Date 2022-12-21 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2022-12-02 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-15 Cont ID  
Sent By rmcdouga Date 2022-11-15 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2022-10-27 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-24 Cont ID  
Sent By rmcdouga Date 2022-10-24 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2022-09-06 Time 05:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By ccole Date 2022-11-03 Time 12:56 Rev Time 0.00
Received By ccole Date 2022-11-03 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 11:04 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 09:54 Sent To  
Notes
2022-09-16 11:19:431ST PLUMBING REVIEW
 22090133
 9/16/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3 & 6: PLEASE PROVIDE TDH CALCULATIONS- SEC.
 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7.
  
 2) SHEET 3 & 6: PROVIDE THE JANDY 2.7 HP PUMP CURVE ON
 THE SHEET MARKED UP TO SHOW THE TDH AND FLOW RATES OF
 THE SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES. PLEASE CORRECT THE PLAN
 NOTES INDICATING A 3HP PUMP PER THE SUBMITTED PUMP
 SPECS.
  
 3) SHEET 3: PROVIDE POOL EQUIPMENT MOUNTING PAD AND
 EQUIPMENT ANCHORING DETAILS- SEC. R4501.22 FBC RES.
  
 4) SHEET 1: PLEASE NOTE THE POOL IS BEING CONSTRUCTED
 IN AN AE FLOOD HAZARD ZONE. PLEASE PROVIDE EQUIPMENT
 PAD ELEVATION SHEET 3 & 6: PLEASE PROVIDE TDH
 CALCULATIONS- SEC. 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7.
  
 5) SHEET 3: PLEASE NOTE THAT THE GAS HEATER SHALL BE
 INSTALLED UNDER A SEPARATE PERMIT- SECS. 105.1,
 107.2.1, 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPER L. COLE
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-21 Cont ID  
Sent By rmcdouga Date 2022-12-21 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2022-12-21 Time 09:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By rmcdouga Date 2022-11-15 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2022-11-15 Time 10:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By rmcdouga Date 2022-10-24 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2022-10-24 Time 14:00 Sent To  
Notes
2022-10-24 14:05:14PLANS ARE NOT DIGITALLY SIGNED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15

Review Stop Z ZONING
Rev No 3 Status P Date 2022-12-13 Cont ID  
Sent By asangele Date 2022-12-13 Time 16:27 Rev Time 0.00
Received By asangele Date 2022-12-13 Time 16:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-08 Cont ID  
Sent By asangele Date 2022-11-08 Time 16:22 Rev Time 0.00
Received By asangele Date 2022-11-08 Time 16:22 Sent To  
Notes
2022-11-08 16:24:33FAILED
 11/8/2022
  
  
 PLEASE LABEL THE SETBACK OF THE POOL EQUIPMENT ON
 SURVEY
  
 ARTICLE X SECTION 94-305
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2022-09-13 Cont ID  
Sent By asangele Date 2022-09-13 Time 14:23 Rev Time 0.00
Received By asangele Date 2022-09-13 Time 14:23 Sent To  
Notes
***NONE***