Plan Review Details - Permit 22081471
Plan Review Stops For Permit 22081471
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-02-10 Cont ID  
Sent By dbattles Date 2023-02-10 Time 08:10 Rev Time 0.00
Received By dbattles Date 2023-02-10 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-02-01 Cont ID  
Sent By dbattles Date 2023-02-01 Time 14:27 Rev Time 0.00
Received By dbattles Date 2023-02-01 Time 14:23 Sent To  
Notes
2023-02-01 14:39:10W.P.B. PERMIT: 22081471
 REVIEWED: FEBRUARY 1, 2023
  
 THERE WILL NOT BE A SUB PERMIT FOR THE GAGARGE DOORS,
 THEY GET APPROVED IN THIS PERMIT.
 PLEASE PROVIDE THE PROCUCT APPROVAL FOR THE GARAGE DOOR
 SINCE IT IS INTEGRAL TO THIS PERMIT.
 OR, PROVIDE PERMIT APPLICATION FOR THE GARAGE DOORS
 SEPARATE IF YOU NEED TO HAVE THAT CONTRACTOR ON A
 PERMIT.
  
 ALSO, PROVIDE A RESPONSE TO ZONING THAT YOU ARE PUTTING
 THIS UNIT BACK TO A GARAGE.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
  
 PLEASE FEEL FREE TO CONTACT ME AT
 561-805-6718 (M-F 8-5) TO DISCUSS COMMENTS, OR E-MAIL
 ANYTIME
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-19 Cont ID  
Sent By cthroop Date 2022-11-19 Time 08:15 Rev Time 0.00
Received By cthroop Date 2022-11-19 Time 07:49 Sent To  
Notes
2022-11-19 08:16:582ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED. SEE BELOW:
  
 W.P.B. PERMIT: 22081471
 REVIEWED: SEPTEMBER 16, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
  
 THESE COMMENTS ARE PRELIMINARY PENDING ZONING APPROVAL
  
 1. 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW
 R806.5 FOR UNVENTED.
 *THE ENERGY CALCS CALL FOR VENTED
  
 2. 109.3 FBC[AMENDED] PROVIDE A COST BREAKDOWN FOR ALL
 WORK, INCLUDING DEMO, IN-FILL INSULATION, DRYWALL,
 KITCHENETTE, BATHROOM, WINDOWS AND OTHER RELATED WORK,
 BECAUSE THE VALUE OF $6000.00 SEEMS LOW FOR THIS MUCH
 WORK.
  
 3. 807 FBC[R] BUILDINGS WITH COMBUSTIBLE CEILING OR
 ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  
 4. 107.3.4.1 FBC[AMENDED]THE PRODUCT APPROVAL PROVIDED
 IS FOR FIXED WINDOWS. THE PLANS SHOW SINGLE HUNG
 WINDOWS AND THAT IS CONSISTENT WITH WHAT IS NEEDED FOR
 EMERGENCY EGRESS.
 PLEASE PROVIDE PRODUCT APPROVALS FOR SINGLE HUNG
 WINDOWS
 IF WINDOW PRODUCT NOT KNOWN AT THIS TIME, PLEASE STATE
 ON PLANS THAT WINDOWS ARE TO BE A DEFERRED SUBMITTAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-16 Cont ID  
Sent By dbattles Date 2022-09-16 Time 12:09 Rev Time 0.00
Received By dbattles Date 2022-09-16 Time 12:09 Sent To  
Notes
2022-09-16 13:31:09BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 22081471
 REVIEWED: SEPTEMBER 16, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 THESE COMMENTS ARE PRELIMINARY PENDING ZONING APPROVAL
  
 1. 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW
 R806.5 FOR UNVENTED.
 *THE ENERGY CALCS CALL FOR VENTED
  
 2. 109.3 FBC[AMENDED] PROVIDE A COST BREAKDOWN FOR ALL
 WORK, INCLUDING DEMO, IN-FILL INSULATION, DRYWALL,
 KITCHENETTE, BATHROOM, WINDOWS AND OTHER RELATED WORK,
 BECAUSE THE VALUE OF $6000.00 SEEMS LOW FOR THIS MUCH
 WORK.
  
 3. 807 FBC[R] BUILDINGS WITH COMBUSTIBLE CEILING OR
 ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  
 4. 107.3.4.1 FBC[AMENDED]THE PRODUCT APPROVAL PROVIDED
 IS FOR FIXED WINDOWS. THE PLANS SHOW SINGLE HUNG
 WINDOWS AND THAT IS CONSISTENT WITH WHAT IS NEEDED FOR
 EMERGENCY EGRESS.
 PLEASE PROVIDE PRODUCT APPROVALS FOR SINGLE HUNG
 WINDOWS
 IF WINDOW PRODUCT NOT KNOWN AT THIS TIME, PLEASE STATE
 ON PLANS THAT WINDOWS ARE TO BE A DEFERRED SUBMITTAL.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  
2022-09-16 12:13:15CUSTOMER SPOKE WITH ZONING REVIEWER AND WOULD LIKE TO
 RE SUBMIT.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-02-17 Cont ID  
Sent By mpeterso Date 2023-02-17 Time 13:27 Rev Time 0.00
Received By mpeterso Date 2023-02-17 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-01-31 Cont ID  
Sent By jleahy Date 2023-01-31 Time 11:07 Rev Time 0.00
Received By jleahy Date 2023-01-31 Time 10:47 Sent To  
Notes
2023-01-31 11:11:20NO ELECTRICAL WORK SHOWN ON PLAN JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-25 Cont ID  
Sent By jleahy Date 2022-10-25 Time 07:14 Rev Time 0.00
Received By jleahy Date 2022-10-25 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-09-15 Cont ID  
Sent By jleahy Date 2022-09-15 Time 11:37 Rev Time 0.00
Received By jleahy Date 2022-09-15 Time 11:33 Sent To  
Notes
2022-09-15 11:39:35FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BATHROOM REQUIRES A LIGHT AND OUTLET PET 210.52, AND
 210.70
  
 PANEL AT SEPARATE STRUCTURE REQUIRES A GROUNDING
 ELECTRODE PER 250.32.
  
 OUTLETS ARE REQUIRED AT THE FRONT AND REAR OF THE UNIT.
 210.52

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-02-17 Cont ID  
Sent By mpeterso Date 2023-02-17 Time 13:41 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-10 Cont ID  
Sent By vbroglia Date 2023-02-10 Time 12:15 Rev Time 0.00
Received By vbroglia Date 2023-02-10 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-01 Cont ID  
Sent By dbattles Date 2023-02-01 Time 14:39 Rev Time 0.00
Received By dbattles Date 2023-01-25 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-19 Cont ID  
Sent By cthroop Date 2022-11-19 Time 09:11 Rev Time 0.00
Received By cthroop Date 2022-10-14 Time 09:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By dbattles Date 2022-09-16 Time 13:31 Rev Time 0.00
Received By dbattles Date 2022-09-02 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2023-01-26 Cont ID  
Sent By medwards Date 2023-01-26 Time 10:15 Rev Time 0.00
Received By medwards Date 2023-01-26 Time 10:15 Sent To  
Notes
2023-01-26 10:16:39N- IS BASED ON THE NEW REVISED PERMIT APPLICATION AND
 DRAWING SHOWING THE UNPERMITTED WORK IS TO BE REMOVED
 AND THIS GARAGE WILL BECOME A 2 CAR GARAGE AGAIN. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 05:17 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 05:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By rwbrown Date 2023-01-26 Time 08:06 Rev Time 0.00
Received By rwbrown Date 2023-01-26 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By rwbrown Date 2022-09-06 Time 13:06 Rev Time 0.00
Received By rwbrown Date 2022-09-06 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2023-02-01 Cont ID  
Sent By dbattles Date 2023-02-01 Time 14:24 Rev Time 0.00
Received By dbattles Date 2023-02-01 Time 14:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-25 Cont ID  
Sent By jleahy Date 2022-10-25 Time 07:16 Rev Time 0.00
Received By jleahy Date 2022-10-25 Time 07:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 05:17 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 05:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2023-02-10 Cont ID  
Sent By vbroglia Date 2023-02-10 Time 12:15 Rev Time 0.00
Received By vbroglia Date 2023-02-10 Time 12:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-31 Cont ID  
Sent By vbroglia Date 2023-01-31 Time 15:51 Rev Time 0.00
Received By vbroglia Date 2023-01-31 Time 15:51 Sent To  
Notes
2023-01-31 15:55:331/31/2023
  
 STOVE NOT REMOVED FROM PERVIOUS PLANS UPLOADED, PLEASE
 ASK PERMIT LIBRARIAN TO HELP DELETE FROM THE PROTAL
 SEE PREVIOUS COMMENT FOR MORE DETAIL
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-10-21 Cont ID  
Sent By vbroglia Date 2022-10-21 Time 11:47 Rev Time 0.00
Received By vbroglia Date 2022-10-21 Time 11:47 Sent To  
Notes
2022-10-21 11:50:19PLEASE REMOVE STOVE FROM ALL PLANS (SEETS A-2 AND M-1)
 AS THIS IS NOT PERMITTED PER THE ZONING DISTRICT
  
 PLEASE REMOVE THE V240 FROM ELECTRICAL
  
 VALENTINA BROGLIA
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-13 Cont ID  
Sent By vbroglia Date 2022-09-13 Time 13:16 Rev Time 0.00
Received By vbroglia Date 2022-09-13 Time 13:16 Sent To  
Notes
2022-09-13 13:20:079/13/2022 FAILED
  
 PER THE ZONING DISTRICT THE PROPERTY IS LOCATED: SF7
  
 ACCESSORY APARTMENTS ARE NOT PERMITTED IN SF7 AND
 ACCESSORY STRUCTURE WILL NOT BE PERMITTED TO BE RENTED
 TO PUBLIC PER THE ZONING DISTRICT
  
 PLEASE REMOVE KITCHEN FORM PLANS
  
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  