Plan Review Details - Permit 22081426
Plan Review Stops For Permit 22081426
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-01 Cont ID  
Sent By rmcdouga Date 2023-06-01 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2023-06-01 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-16 Cont ID  
Sent By rmcdouga Date 2023-03-16 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2023-03-16 Time 16:50 Sent To  
Notes
2023-03-16 16:56:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE DETAILS FOR THE GENERATOR PAD AND SPECIFY
 HOW THE GENERATOR WILL BE ANCHORED TO THE PAD TO RESIST
 WIND LOADS. FBC 107.2.1 AND CHAPTER 16
  
 2) SPECIFY THE WIND LOAD DESIGN DATA ON THE DRAWINGS.
 FBC CHAPTER 16
  
 3) DRAWINGS AND DETAILS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. FS471

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-06-12 Cont ID  
Sent By jleahy Date 2023-06-12 Time 16:09 Rev Time 0.00
Received By jleahy Date 2023-06-12 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-13 Cont ID  
Sent By jleahy Date 2023-03-13 Time 09:46 Rev Time 0.00
Received By jleahy Date 2023-03-13 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-10 Cont ID  
Sent By jleahy Date 2023-01-10 Time 15:34 Rev Time 0.00
Received By jleahy Date 2023-01-10 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 16:43 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 16:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2023-06-06 Cont ID  
Sent By pleduc Date 2023-06-06 Time   Rev Time 0.00
Received By pleduc Date 2023-06-06 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-04-04 Cont ID  
Sent By pleduc Date 2023-04-04 Time   Rev Time 0.00
Received By pleduc Date 2023-04-04 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-12-30 Cont ID  
Sent By pleduc Date 2022-12-30 Time   Rev Time 0.00
Received By pleduc Date 2022-12-30 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By pleduc Date 2022-12-21 Time   Rev Time 0.00
Received By pleduc Date 2022-12-21 Time 09:43 Sent To  
Notes
2022-12-21 10:10:15THE PREVIOUS COMMENTS BY FIRE HAVE NOT BEEN ADDRESSED.
  
 THE NEW SUBMITTED DOCUMENTS DATED 12/19/22 WITHIN THE
 TITLE BLOCK INDICATE AN ADDRESS OF 7640 OKEECHOBEE
 BLVD.
  
 WHEREAS THE ORIGINAL SUBMITTED DOCUMENTS AND
 APPLICATION INDICATED 477 S ROSEMARY AVE # 187.
  
 PLEASE REIVEW AND CORRECT WITH THE PROPER ADDRESS AND
 APPLICABLE DOCUMENTS TO ADDRESS FIRE'S PREVIOUS
 COMMENTS WHICH ARE NOTED BELOW.
  
 *******************************************************
 *******************************************************
 ****************************************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF THE GENERATOR TYPE,
 MANUFACTURES SPEC SHEET, FUEL SUPPLY, NOR EXHAUST
 LOCATION FOR THE PROPOSED GENERATOR REPLACEMENT.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF
 THE NORMAL POWER SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF TH
  
 PLEASE PROVIDE
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-09-07 Cont ID  
Sent By pleduc Date 2022-09-07 Time   Rev Time 0.00
Received By pleduc Date 2022-09-07 Time 15:23 Sent To  
Notes
2022-09-07 15:27:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF THE GENERATOR TYPE,
 MANUFACTURES SPEC SHEET, FUEL SUPPLY, NOR EXHAUST
 LOCATION FOR THE PROPOSED GENERATOR REPLACEMENT.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF
 THE NORMAL POWER SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF TH
  
 PLEASE PROVIDE
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-02-24 Cont ID  
Sent By ccole Date 2023-02-24 Time 16:41 Rev Time 0.00
Received By ccole Date 2023-02-24 Time 15:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-12 Cont ID  
Sent By ccole Date 2023-01-12 Time 09:43 Rev Time 0.00
Received By ccole Date 2023-01-12 Time 08:41 Sent To  
Notes
2023-01-12 09:45:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22081426
 1/12/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING IN COMPLIANCE WITH SEC.
 107.3.5.1.3 WPB. THE RISER SHALL INCLUDE THE FOLLOWING
 INFORMATION AS REQUIRED BY SEC. 402 FBC FG.
  
 A) TYPE OF GAS- NATURAL OR LP. (PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED FOR LP TANKS).
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD OF THE GENERATOR AND ALL EXISTING
 APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SHOW THE TYPE AND SIZE OF CONNECTOR FROM THE
 SHUTOFF/REGULATOR ASSEMBLY TO THE GENERATOR. PLEASE
 NOTE THE GENERATOR SHALL NOT BE RIGIDLY CONNECTED TO
 THE GAS SUPPLY- SECS. 411.1.5 & 616.2 FBC FG.
 A) PLEASE NOTE THE SUBMITTED MANUFACTURER' S
 SPECIFICATIONS FOR THE GENERATOR RECOMMENDS THE
 REGULATOR TO BE LOCATED A MINIMUM 10 FT. FROM THE
 GENERATOR SET CONNECTION POINT- SEE PAGE 2 OF THE
 GENERAC DESIGN GUIDE WHICH ALSO PROVIDES REGULATOR
 SELECTION SPECIFICATIONS- SEC. 410.2 FBC FG.
  
 3) PROVIDE A DIMENSIONED SITE PLAN WITH ENLARGED
 DRAWING OF THE GENERATOR SHOWING THE FOLLOWING
 INFORMATION.
 A) GAS PIPING RUNS ON THE EXTERIOR AND INTERIOR THE
 BUILDING AND MEANS OF PROTECTING PIPING FROM PHYSICAL
 DAMAGE AND CORROSION- SEC. 404.
 B) PROTECTION FROM VEHICLE IMPACT FOR THE GENERATOR AND
 APPURTENANCES- SEC. 303.4.
  
 4) PROVIDE A VENTING PLAN FOR THE GENERATOR EXHAUST
 LISTING THE CATEGORY OF THE VENT SYSTEM- 1,2,3, OR 4,
 AND VENT SPECIFICARTIONS- TYPES ANSD SIZE, VENT RUN AND
 TERNINATION LOCATION WITH CLEARANCE DISTANCES TO
 MECHANICAL AND GRAVITY AIR INTALES INTO THE BUILDING-
 SEC. 503.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-06-12 Cont ID  
Sent By jleahy Date 2023-06-12 Time 16:11 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-01 Cont ID  
Sent By rmcdouga Date 2023-06-01 Time 11:08 Rev Time 0.00
Received By rmcdouga Date 2023-05-22 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-04 Cont ID  
Sent By lmarchan Date 2023-04-04 Time 15:48 Rev Time 0.00
Received By lmarchan Date 2023-02-23 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-21 Cont ID  
Sent By aoliver Date 2023-02-21 Time 22:06 Rev Time 0.00
Received By aoliver Date 2022-12-29 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-28 Cont ID  
Sent By lmarchan Date 2022-12-28 Time 12:12 Rev Time 0.00
Received By lmarchan Date 2022-12-20 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-19 Cont ID  
Sent By aoliver Date 2022-10-19 Time 08:48 Rev Time 0.00
Received By aoliver Date 2022-09-02 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 15:05 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 09:23 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 09:23 Sent To  
Notes
2023-01-11 09:24:021ST REVIEW FMC
 PERMIT: 22081426
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION LISTS UNIT 187. THE MASTER
 PERMIT REFERENCED AND THE DRAWINGS SUBMITTED LIST UNIT
 200. PLEASE PROVIDE THE CORRECT UNIT NUMBER.
  
 2) PROVIDE A SITE PLAN THAT INDICATES THE PROPERTY
 LINES. THIS SHOULD SHOW THAT THE GENERATOR EXHAUST
 MEETS ALL OF THE REQUIREMENTS IN FMC 501.3.1 NUMBER 2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-02-24 Cont ID  
Sent By ccole Date 2023-02-24 Time 16:42 Rev Time 0.00
Received By ccole Date 2023-02-24 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-01-12 Cont ID  
Sent By ccole Date 2023-01-12 Time 09:54 Rev Time 0.00
Received By ccole Date 2023-01-12 Time 08:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-06-12 Cont ID  
Sent By jleahy Date 2023-06-12 Time 16:11 Rev Time 0.00
Received By jleahy Date 2023-06-12 Time 16:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-01 Cont ID  
Sent By rmcdouga Date 2023-06-01 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2023-06-01 Time 11:07 Sent To  
Notes
2023-06-01 11:06:44SIGNATURE REVIEW:
  
 1- 3RD TIME REPEAT COMMENT. SAME COMMENT FROM PREVIOUS
 REVIEW APPLY. SHEET E-000 IS NOT DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER OF RECORD. SEC. 61G15-23.001 FAC
 AND CHAPTER 471 F.S.
  
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-04-03 Cont ID  
Sent By jgomez Date 2023-04-03 Time 14:37 Rev Time 0.00
Received By jgomez Date 2023-04-03 Time 14:36 Sent To  
Notes
2023-04-03 14:43:57SIGNATURE REVIEW:
  
 1- REPEAT COMMENT. SAME COMMENT FROM PREVIOUS REVIEW
 APPLY. SHEET E-000 IS NOT DIGITALLY SIGNED AND SEALED
 BY THE ENGINEER OF RECORD. SEC. 61G15-23.001 FAC AND
 CHAPTER 471 F.S.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
2023-03-13 09:47:39ELECTRICAL SIGNATURE PAGES APPROVED JLEAHY
2023-02-24 16:43:21FUEL GAS (FG) PLAN SIGS APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-12 Cont ID  
Sent By ccole Date 2023-01-12 Time 10:06 Rev Time 0.00
Received By ccole Date 2023-01-12 Time 10:06 Sent To  
Notes
2023-01-12 10:07:01SIGNATURE REVIEW FBC- 2020
 PERMIT- 22081426
 1/12/23
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-000 IS NOT DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND
 SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 16:45 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 16:45 Sent To  
Notes
2022-09-29 16:46:01SEE MASTER PERMIT FOR SIGNATURES ON FILE.

Review Stop Z ZONING
Rev No 4 Status P Date 2023-05-30 Cont ID  
Sent By eschneid Date 2023-05-30 Time 17:44 Rev Time 0.25
Received By eschneid Date 2023-05-30 Time 17:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-03-29 Cont ID  
Sent By eschneid Date 2023-03-29 Time 14:45 Rev Time 0.50
Received By eschneid Date 2023-03-29 Time 14:08 Sent To  
Notes
2023-03-29 14:46:00FAILED
  
 THE GENERATOR IS REQUIRED TO BE SCREENED. ZONING WILL
 NOT APPROVE THIS PERMIT UNTIL FENCING PERMIT 22081416
 IS APPROVED.
  
 THE GENERATOR AND LOCATION COMPLY WITH ZONING.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-02-21 Cont ID  
Sent By eschneid Date 2023-02-21 Time 15:09 Rev Time 0.50
Received By eschneid Date 2023-02-21 Time 10:17 Sent To  
Notes
2023-02-21 15:10:02FAILED
  
 1) REPEAT COMMENT: THE CITYPLACE RETAIL MANAGEMENT
 APPROVAL STAMP IS REQUIRED ON THE PLANS. ALTERNATIVELY,
 YOU MAY PROVIDE A LETTER FROM CITYPLACE RETAIL
 MANAGEMENT WHICH APPROVES THE SPECIFIC PLANS SUBMITTED
 AS PART OF THE PERMIT.
  
 2) REPEAT COMMENT: PROVIDE A RECENT COPY OF A SURVEY
 FOR THE AREA. THE SURVEY SHALL INCLUDE ALL FEATURES AND
 EASEMENTS. THE SITE PLAN IS TO BE BASED OFF OF THE
 SURVEY AND SHOW SETBACKS TO THE BUILDING, ROADWAY,
 PARKING AND ABOVE GROUND FEATURES AND INCLUDE THE
 DIMENSIONS OF THE GENERATOR.
  
 3) THE SITE PLAN MUST SHOW THE GENERATOR, THE ENCLOSURE
 AND THE SETBACKS FOR THE FEATURES. THE DIMENSION
 SHOWING THAT THE LOADING ZONE REMAINS AT A MINIMUM OF
 50 FEET DEEP MUST BE CLEARLY SHOWN ON THE PLANS.
  
 4) UPDATED COMMENT: THE GENERATOR IS REQUIRED TO BE
 SCREENED. ZONING WILL NOT APPROVE THIS PERMIT UNTIL
 FENCING PERMIT 22081416 IS APPROVED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By eschneid Date 2022-10-18 Time 16:58 Rev Time 0.25
Received By eschneid Date 2022-10-18 Time 16:58 Sent To  
Notes
2022-10-18 16:58:21FAILED
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 2) PROVIDE A RECENT COPY OF A SURVEY FOR THE AREA. THE
 SURVEY SHALL INCLUDE ALL FEATURES AND EASEMENTS. THE
 SITE PLAN IS TO BE BASED OFF OF THE SURVEY AND SHOW
 SETBACKS TO THE BUILDING, ROADWAY, PARKING AND ABOVE
 GROUND FEATURES AND INCLUDE THE DIMENSIONS OF THE
 GENERATOR.
  
 3) THE GENERATOR IS REQUIRED TO BE SCREENED. ZONING
 WILL NOT APPROVE THIS PERMIT WITHOUT SHOWING COMPLIANCE
 WITH THE SCREENING REQUIREMENTS. THE OVERALL HEIGHT OF
 THE GENERATOR (INCLUDING ITS MOUNT) MUST BE SCREENED.
  
 4) ZONING MET WITH CITYPLACE RETAIL STAFF AND THEY
 INDICATED THAT THE GENERATOR WOULD BE LOCATED TO THE
 SOUTH OF WHERE IT IS BEING SHOWN ON THE SITE PLAN.
 PLEASE VERIFY THE EXACT LOCATION OF THE GENERATOR.
  
 5) PROVIDE SPECIFICATION SHEETS FOR THE GENERATOR,
 INCLUDING THE HEIGHT AND THE MOUNT HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  