Plan Review Stops For Permit 22081426 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-06-01 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-06-01 |
Time |
11:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-03-16 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-03-16 |
Time |
16:50 |
Sent To |
|
|
Notes |
2023-03-16 16:56:12 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE DETAILS FOR THE GENERATOR PAD AND SPECIFY | | HOW THE GENERATOR WILL BE ANCHORED TO THE PAD TO RESIST | | WIND LOADS. FBC 107.2.1 AND CHAPTER 16 | | | | 2) SPECIFY THE WIND LOAD DESIGN DATA ON THE DRAWINGS. | | FBC CHAPTER 16 | | | | 3) DRAWINGS AND DETAILS ARE REQUIRED TO BE SIGNED AND | | SEALED BY THE DESIGN PROFESSIONAL. FS471 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2023-06-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-06-12 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-06-12 |
Time |
15:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-03-13 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-03-13 |
Time |
08:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-01-10 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-01-10 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-29 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-09-29 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2023-06-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-06-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-06-06 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2023-05-23 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-23 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-23 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2023-04-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-04-04 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-04-04 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-12-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-12-30 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-12-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-12-21 |
Time |
09:43 |
Sent To |
|
|
Notes |
2022-12-21 10:10:15 | THE PREVIOUS COMMENTS BY FIRE HAVE NOT BEEN ADDRESSED. | | | | THE NEW SUBMITTED DOCUMENTS DATED 12/19/22 WITHIN THE | | TITLE BLOCK INDICATE AN ADDRESS OF 7640 OKEECHOBEE | | BLVD. | | | | WHEREAS THE ORIGINAL SUBMITTED DOCUMENTS AND | | APPLICATION INDICATED 477 S ROSEMARY AVE # 187. | | | | PLEASE REIVEW AND CORRECT WITH THE PROPER ADDRESS AND | | APPLICABLE DOCUMENTS TO ADDRESS FIRE'S PREVIOUS | | COMMENTS WHICH ARE NOTED BELOW. | | | | ******************************************************* | | ******************************************************* | | **************************************************** | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO INDICATION OF THE GENERATOR TYPE, | | MANUFACTURES SPEC SHEET, FUEL SUPPLY, NOR EXHAUST | | LOCATION FOR THE PROPOSED GENERATOR REPLACEMENT. | | | | PER NFPA 1 | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | APPLICABLE CODES AND STANDARDS | | | | PER NFPA 110 | | | | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY | | SYSTEMS (EPSSS) | | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF | | ELECTRICAL | | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO | | LOADS FOR | | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND | | WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF | | THE NORMAL POWER SUPPLY | | AS SPECIFIED IN TABLE 4.1(B). | | | | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN | | HOURS, FOR | | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD | | WITHOUT | | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] | | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN | | SECONDS, | | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE | | TRANSFER | | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE | | 4.1(B) | | PROVIDES THE TYPES DEFINED BY THIS STANDARD. | | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF | | EQUIPMENT | | INSTALLATION, PERFORMANCE, AND MAINTENANCE. | | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | OF THE | | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE | | OR | | SERIOUS INJURIES. | | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | OF TH | | | | PLEASE PROVIDE | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-09-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-09-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-09-07 |
Time |
15:23 |
Sent To |
|
|
Notes |
2022-09-07 15:27:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO INDICATION OF THE GENERATOR TYPE, | | MANUFACTURES SPEC SHEET, FUEL SUPPLY, NOR EXHAUST | | LOCATION FOR THE PROPOSED GENERATOR REPLACEMENT. | | | | PER NFPA 1 | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | APPLICABLE CODES AND STANDARDS | | | | PER NFPA 110 | | | | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY | | SYSTEMS (EPSSS) | | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF | | ELECTRICAL | | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO | | LOADS FOR | | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND | | WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF | | THE NORMAL POWER SUPPLY | | AS SPECIFIED IN TABLE 4.1(B). | | | | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN | | HOURS, FOR | | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD | | WITHOUT | | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] | | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN | | SECONDS, | | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE | | TRANSFER | | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE | | 4.1(B) | | PROVIDES THE TYPES DEFINED BY THIS STANDARD. | | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF | | EQUIPMENT | | INSTALLATION, PERFORMANCE, AND MAINTENANCE. | | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | OF THE | | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE | | OR | | SERIOUS INJURIES. | | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | OF TH | | | | PLEASE PROVIDE | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-24 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-24 |
Time |
15:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-12 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-12 |
Time |
08:41 |
Sent To |
|
|
Notes |
2023-01-12 09:45:15 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 22081426 | | 1/12/23 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A GAS RISER DRAWING IN COMPLIANCE WITH SEC. | | 107.3.5.1.3 WPB. THE RISER SHALL INCLUDE THE FOLLOWING | | INFORMATION AS REQUIRED BY SEC. 402 FBC FG. | | | | A) TYPE OF GAS- NATURAL OR LP. (PLEASE NOTE SEPARATE | | PERMITS ARE REQUIRED FOR LP TANKS). | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD OF THE GENERATOR AND ALL EXISTING | | APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | 2) SHOW THE TYPE AND SIZE OF CONNECTOR FROM THE | | SHUTOFF/REGULATOR ASSEMBLY TO THE GENERATOR. PLEASE | | NOTE THE GENERATOR SHALL NOT BE RIGIDLY CONNECTED TO | | THE GAS SUPPLY- SECS. 411.1.5 & 616.2 FBC FG. | | A) PLEASE NOTE THE SUBMITTED MANUFACTURER' S | | SPECIFICATIONS FOR THE GENERATOR RECOMMENDS THE | | REGULATOR TO BE LOCATED A MINIMUM 10 FT. FROM THE | | GENERATOR SET CONNECTION POINT- SEE PAGE 2 OF THE | | GENERAC DESIGN GUIDE WHICH ALSO PROVIDES REGULATOR | | SELECTION SPECIFICATIONS- SEC. 410.2 FBC FG. | | | | 3) PROVIDE A DIMENSIONED SITE PLAN WITH ENLARGED | | DRAWING OF THE GENERATOR SHOWING THE FOLLOWING | | INFORMATION. | | A) GAS PIPING RUNS ON THE EXTERIOR AND INTERIOR THE | | BUILDING AND MEANS OF PROTECTING PIPING FROM PHYSICAL | | DAMAGE AND CORROSION- SEC. 404. | | B) PROTECTION FROM VEHICLE IMPACT FOR THE GENERATOR AND | | APPURTENANCES- SEC. 303.4. | | | | 4) PROVIDE A VENTING PLAN FOR THE GENERATOR EXHAUST | | LISTING THE CATEGORY OF THE VENT SYSTEM- 1,2,3, OR 4, | | AND VENT SPECIFICARTIONS- TYPES ANSD SIZE, VENT RUN AND | | TERNINATION LOCATION WITH CLEARANCE DISTANCES TO | | MECHANICAL AND GRAVITY AIR INTALES INTO THE BUILDING- | | SEC. 503.1 FBC FG. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2023-06-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-06-12 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-06-05 |
Time |
08:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-06-01 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-05-22 |
Time |
16:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-04-04 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-04-04 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-02-23 |
Time |
08:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-02-21 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-02-21 |
Time |
22:06 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-12-29 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-28 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-12-28 |
Time |
12:12 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-12-20 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-10-19 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-10-19 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-09-02 |
Time |
07:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-27 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-27 |
Time |
15:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-01-11 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-11 |
Time |
09:23 |
Sent To |
|
|
Notes |
2023-01-11 09:24:02 | 1ST REVIEW FMC | | PERMIT: 22081426 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PERMIT APPLICATION LISTS UNIT 187. THE MASTER | | PERMIT REFERENCED AND THE DRAWINGS SUBMITTED LIST UNIT | | 200. PLEASE PROVIDE THE CORRECT UNIT NUMBER. | | | | 2) PROVIDE A SITE PLAN THAT INDICATES THE PROPERTY | | LINES. THIS SHOULD SHOW THAT THE GENERATOR EXHAUST | | MEETS ALL OF THE REQUIREMENTS IN FMC 501.3.1 NUMBER 2. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-24 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-24 |
Time |
15:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-12 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-12 |
Time |
08:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2023-06-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-06-12 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-06-12 |
Time |
16:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-06-01 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-06-01 |
Time |
11:07 |
Sent To |
|
|
Notes |
2023-06-01 11:06:44 | SIGNATURE REVIEW: | | | | 1- 3RD TIME REPEAT COMMENT. SAME COMMENT FROM PREVIOUS | | REVIEW APPLY. SHEET E-000 IS NOT DIGITALLY SIGNED AND | | SEALED BY THE ENGINEER OF RECORD. SEC. 61G15-23.001 FAC | | AND CHAPTER 471 F.S. | | | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | | | | | | | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-03 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-03 |
Time |
14:36 |
Sent To |
|
|
Notes |
2023-04-03 14:43:57 | SIGNATURE REVIEW: | | | | 1- REPEAT COMMENT. SAME COMMENT FROM PREVIOUS REVIEW | | APPLY. SHEET E-000 IS NOT DIGITALLY SIGNED AND SEALED | | BY THE ENGINEER OF RECORD. SEC. 61G15-23.001 FAC AND | | CHAPTER 471 F.S. | | | | ENGINEERS | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | 2023-03-13 09:47:39 | ELECTRICAL SIGNATURE PAGES APPROVED JLEAHY | 2023-02-24 16:43:21 | FUEL GAS (FG) PLAN SIGS APPROVED. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-12 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-12 |
Time |
10:06 |
Sent To |
|
|
Notes |
2023-01-12 10:07:01 | SIGNATURE REVIEW FBC- 2020 | | PERMIT- 22081426 | | 1/12/23 | | | | CODES IN EFFECT: | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET E-000 IS NOT DIGITALLY SIGNED AND SEALED BY | | THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND | | SECTION 61G15-23.005 FAC. | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | DOCUMENTS. | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | USE A THIRD PARTY. | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | AND DOCUMENT. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-29 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-09-29 |
Time |
16:45 |
Sent To |
|
|
Notes |
2022-09-29 16:46:01 | SEE MASTER PERMIT FOR SIGNATURES ON FILE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2023-05-30 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-05-30 |
Time |
17:44 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2023-05-30 |
Time |
17:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2023-03-29 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-03-29 |
Time |
14:45 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2023-03-29 |
Time |
14:08 |
Sent To |
|
|
Notes |
2023-03-29 14:46:00 | FAILED | | | | THE GENERATOR IS REQUIRED TO BE SCREENED. ZONING WILL | | NOT APPROVE THIS PERMIT UNTIL FENCING PERMIT 22081416 | | IS APPROVED. | | | | THE GENERATOR AND LOCATION COMPLY WITH ZONING. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-02-21 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-02-21 |
Time |
15:09 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2023-02-21 |
Time |
10:17 |
Sent To |
|
|
Notes |
2023-02-21 15:10:02 | FAILED | | | | 1) REPEAT COMMENT: THE CITYPLACE RETAIL MANAGEMENT | | APPROVAL STAMP IS REQUIRED ON THE PLANS. ALTERNATIVELY, | | YOU MAY PROVIDE A LETTER FROM CITYPLACE RETAIL | | MANAGEMENT WHICH APPROVES THE SPECIFIC PLANS SUBMITTED | | AS PART OF THE PERMIT. | | | | 2) REPEAT COMMENT: PROVIDE A RECENT COPY OF A SURVEY | | FOR THE AREA. THE SURVEY SHALL INCLUDE ALL FEATURES AND | | EASEMENTS. THE SITE PLAN IS TO BE BASED OFF OF THE | | SURVEY AND SHOW SETBACKS TO THE BUILDING, ROADWAY, | | PARKING AND ABOVE GROUND FEATURES AND INCLUDE THE | | DIMENSIONS OF THE GENERATOR. | | | | 3) THE SITE PLAN MUST SHOW THE GENERATOR, THE ENCLOSURE | | AND THE SETBACKS FOR THE FEATURES. THE DIMENSION | | SHOWING THAT THE LOADING ZONE REMAINS AT A MINIMUM OF | | 50 FEET DEEP MUST BE CLEARLY SHOWN ON THE PLANS. | | | | 4) UPDATED COMMENT: THE GENERATOR IS REQUIRED TO BE | | SCREENED. ZONING WILL NOT APPROVE THIS PERMIT UNTIL | | FENCING PERMIT 22081416 IS APPROVED. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-10-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2022-10-18 |
Time |
16:58 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2022-10-18 |
Time |
16:58 |
Sent To |
|
|
Notes |
2022-10-18 16:58:21 | FAILED | | | | 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS | | REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A | | LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES | | THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT. | | | | 2) PROVIDE A RECENT COPY OF A SURVEY FOR THE AREA. THE | | SURVEY SHALL INCLUDE ALL FEATURES AND EASEMENTS. THE | | SITE PLAN IS TO BE BASED OFF OF THE SURVEY AND SHOW | | SETBACKS TO THE BUILDING, ROADWAY, PARKING AND ABOVE | | GROUND FEATURES AND INCLUDE THE DIMENSIONS OF THE | | GENERATOR. | | | | 3) THE GENERATOR IS REQUIRED TO BE SCREENED. ZONING | | WILL NOT APPROVE THIS PERMIT WITHOUT SHOWING COMPLIANCE | | WITH THE SCREENING REQUIREMENTS. THE OVERALL HEIGHT OF | | THE GENERATOR (INCLUDING ITS MOUNT) MUST BE SCREENED. | | | | 4) ZONING MET WITH CITYPLACE RETAIL STAFF AND THEY | | INDICATED THAT THE GENERATOR WOULD BE LOCATED TO THE | | SOUTH OF WHERE IT IS BEING SHOWN ON THE SITE PLAN. | | PLEASE VERIFY THE EXACT LOCATION OF THE GENERATOR. | | | | 5) PROVIDE SPECIFICATION SHEETS FOR THE GENERATOR, | | INCLUDING THE HEIGHT AND THE MOUNT HEIGHT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|