Plan Review Stops For Permit 22081417 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-02-28 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-02-28 |
Time |
15:30 |
Sent To |
|
|
Notes |
2023-02-28 15:30:59 | APPLICATION UPDATED TO 740 N DIXIE HWY |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2023-01-05 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-01-05 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-01-05 |
Time |
08:20 |
Sent To |
|
|
Notes |
2023-01-05 08:20:33 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-09-27 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-09-27 |
Time |
17:00 |
Sent To |
|
|
Notes |
2022-09-27 17:03:49 | THIS PROJECT HAS TWO PARCEL WITH TWO ADDRESSES 740 N | | DIXIE HWY AND 840 N DIXIE HWY APPLICATION FORM HAS 1840 | | N DIXIE HWY AND 740 N DIXIE HWY WRITTEN ON IT PLEASE | | CORRECT THIS. THE PLANS INDICATE THAT THE TRAILER WILL | | BE ON THE PARCEL WITH THE ADDRESS OF 740 N DIXIE HWY, | | PLEASE CONFIRM TO [email protected] OR CALL | | 561-805-6659 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-03-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-03-01 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-03-01 |
Time |
15:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-02-03 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-02-03 |
Time |
09:50 |
Sent To |
|
|
Notes |
2023-02-03 13:07:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | 2ND BUILDING REVIEW DENIED: | | | | 1.) FBC B 1609.1, PLEASE UPDATE THE WINDLOAD | | INFORMATION ON PLAN SHEET C1 TO THE CURRENT 2020 | | FLORIDA BUILDING CODE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-10-26 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-10-26 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-10-25 |
Time |
16:30 |
Sent To |
|
|
Notes |
2022-10-26 07:34:53 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1.) FBC B 1609.1, PLEASE UPDATE THE WINDLOAD | | INFORMATION ON PLAN SHEET C1 TO THE CURRENT 2020 | | FLORIDA BUILDING CODE. | | 2.) FBC A 203.2 (EXCEPTION), IF THE INTENT IS TO NOT | | COMPLY WITH ACCESSIBILITY REQUIREMENTS FOR CONSTRUCTION | | TRAILER RAMP AND ADJACENT PARKING, PLEASE PROVIDE A | | NOTARIZED LETTER ACKNOWLEDGING THAT THERE WILL BE NO | | PERSONNEL MEETINGS / ASSEMBLIES HELD IN THE | | CONSTRUCTION TRAILERS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-08 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-03-08 |
Time |
13:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2023-01-06 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-01-06 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-01-06 |
Time |
12:51 |
Sent To |
|
|
Notes |
2023-01-06 12:51:38 | SEE SIGNATURE REVIEW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-10-13 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-10-13 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-10-13 |
Time |
15:23 |
Sent To |
|
|
Notes |
2022-10-13 15:30:32 | ELECTRICAL REVIEW FAILED | | 1) PLEASE PROVIDE A TEMPORARY ELECTRICAL SERVICE RISER | | AND ELECTRIC LOAD CALCULATION FOR ENTIRE SEVICE, | | INCLUDE ALL TRAILERS AND | | OTHER ELECTRIC LOADS. NEC 215.5 | | 2) PROVIDE A SITE PLAN SHOWING LOCATION OF TEMPORARY | | SERVICE. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-12-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-12-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-12-28 |
Time |
13:35 |
Sent To |
|
|
Notes |
2022-12-28 13:35:48 | FIRE COMMENT: | | | | PROVIDE FOR ONE MOUNTED - 10LB ABC FIRE EXTINGUISHER | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-09-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-09-27 |
Time |
11:36 |
Sent To |
|
|
Notes |
2022-09-27 11:56:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO SEPARATION DIMENSION INDICATED BETWEEN | | THE PROPOSED TRAILER LOCATION AND THE PROPOSED NEW | | STRUCTURE OR EXISTING STRUCTURES. | | | | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; | | | | TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE | | REQUIRED IN EACH TRAILER. | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | NOTES: | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | AUTHORITY HAVING JURISDICTION. | | | | PLEASE PROVIDE FOR THE REQUIRED SEPARATION OR PROVIDE | | FIRE SPRINKLER PROTECTION. | | | | FYI: THE INSTALLATION OF ABC DRY CHEMICAL SPRINKLERS | | PER MANUFACTURERS RECOMMENDATIONS MAY BE CONSIDERED IN | | LIEU OF WET FIRE SPRINKLERS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-08 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-24 |
Time |
06:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-02-03 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-12-27 |
Time |
07:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-11-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-11-22 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-09-26 |
Time |
08:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-27 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-27 |
Time |
08:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2022-10-05 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-10-05 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-10-05 |
Time |
12:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-02-28 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-02-28 |
Time |
09:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-01-06 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-01-06 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-01-06 |
Time |
12:51 |
Sent To |
|
|
Notes |
2023-01-06 12:52:26 | SIGNATURE REVIEW FAILED | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | DIGITALLY SEALED AND SIGNED. | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-10-13 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-10-13 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-10-13 |
Time |
15:30 |
Sent To |
|
|
Notes |
2022-10-13 15:33:35 | SIGNATURE REVIEW FAILED | | ALL PLANS EITHER DO NOT DETAIL DIGITAL SIGNATURE, A | | DIGITAL SIGNATURE THAT CAN BE VERIFIED USING BLUEBEAM | | OR ADOBE SOFTWARE, OR DETAIL A CORRUPT DIGITAL | | SIGNATURE. PLEASE CORRECT AS OUTLINED BELOW. | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | DIGITALLY SEALED AND SIGNED. | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-12-28 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2022-12-28 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-12-28 |
Time |
14:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2022-11-21 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-11-21 |
Time |
13:30 |
Sent To |
|
|
Notes |
|
|