Plan Review Details - Permit 22081397
Plan Review Stops For Permit 22081397
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-10-13 Cont ID  
Sent By cthroop Date 2022-10-13 Time 14:48 Rev Time 0.00
Received By cthroop Date 2022-10-11 Time 16:40 Sent To  
Notes
2022-10-12 08:36:324TH NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, CBO, BU, BN, PX, CFM
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
 FEMA TECH BULLETIN #1
  
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION A9 (C) STATES "TOTAL NET AREA OF FLOOD
 OPENINGS IS 2000 SQ. IN."
 NOTE: (IF FLOOD VENT MODEL 1540-520 IS 8.25"X16.25",
 THEN EACH VENT CAN ONLY BE 134 SQ. IN.'S FOR A MAX OF
 1340 SQ. IN.'S.)
  
 NET AREA OF ENGINEERED FLOOD VENTS SHALL BE CALCULATED
 BY A DESIGN PROFESSIONAL PER FEMA TECH. BULLETIN #1,
 PAGE 34, FIGURE 25.
  
 2. COMMENT IN SECTION D STATES "SMART VENT MODEL
 1540-520 ARE RATED FOR 200 SQ. IN. PER UNIT". (THIS
 SHOULD STATE 200 SQ. FT. PER UNIT). PLEASE CORRECT.
  
 3. COMMENT IN SECTION D STATES SECTION C2E: A/C PAD AT
 SOUTHSIDE=8.96.
 EQUIPMENT SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DESIGN FLOOD ELEVATION (DFE) OF 9'0"NAVD. PLEASE
 CORRECT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-21 Cont ID  
Sent By rmcphers Date 2022-09-21 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2022-09-21 Time 13:55 Sent To  
Notes
2022-09-21 14:03:54ELEVATION CERTIFICATE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 PER FEMA ELEVATION INSTRUCTIONS
  
 CORRECTIONS NEEDED -
  
 1) A9(A) = SHOULD SHOW 1801 SQ. FT. - SEE APPROVED PLAN
  
 2) A9(B) = SHOULD SHOW 10 - SEE APPROVED PLAN
  
 3) A9(C) = SHOULD SHOW 2000 SQ. FT - SEE APPROVED PLAN
  
 4) SECTION "D" - FOR THE GARAGE THE INCORRECT SQUARE
 FOOTAGE AND THE INCORRECT NUMBER OF FLOOD VENTS ARE
 NOTED - SEE APPROVED PLANS.
  
 5) PHOTOS - PLEASE PROVIDE 2 ADDITIONAL PHOTOS - FOR A
 2 STORY BUILDING A PHOTO LABELED "RIGHT SIDE VIEW" AND
 A PHOTO LABELED "LEFT SIDE VIEW" ARE REQUIRED.
  
 6) THE PROVIDED SURVEY SHOWS FLOOD ELEVATION AE 6 -
 SHOULD SHOW AE 6 AND 7.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcphers Date 2022-09-21 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By rmcphers Date 2022-08-31 Time 08:17 Rev Time 0.00
Received By rmcphers Date 2022-08-30 Time 09:14 Sent To  
Notes
2022-08-30 09:46:08ELEVATION CERTIFICATE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 PER FEMA ELEVATION INSTRUCTIONS
  
 CORRECTIONS NEEDED -
  
 1) A9(C) = WHEN THE FLOOD VENTS ARE ENGINEERED OPENINGS
 A STATEMENT IS REQUIRED FROM THE DESIGNER OF RECORD -
 FBC R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD
 ELEVATION. (2.1) THE TOTAL NET AREA OF NON-ENGINEERED
 OPENINGS SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2)
 FOR EACH SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE
 THE ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE
 ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS
 ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN
 PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL
 PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND
 EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF
 ASCE 24.
  
 2) A9(C) = FOR EACH GARAGE SHOW THE FLOOD VENT SIZE
 CALCULATIONS FOR ENGINEERED OPENINGS SEE SECTION
 2.7.2.2 OF ASCE 24. 6. THE MINIMUM TOTAL NET AREA OF
 THE REQUIRED OPENINGS IN
 ENCLOSURE WALLS SHALL BE CALCULATED USING THE EQUATION
 - AO=0.033(1/C)(R)(AE) ---- OTHERWISE NON ENGINEERED
 OPENINGS = 1 SQ. INCH FOR EACH SQ. FOOT (SMART VENTS
 ARE ENGINEERED TO GIVE YOU 200 SQ. IN. PER VENT - YOU
 DO NOT HAVE ENOUGH VENTS IN EACH GARAGE TO MEET THE
 REQUIRED SQ. INCHES)
  
 3) B9 = SHOULD SHOW THE HIGHER OF THE 2 FLOOD
 ELEVATIONS OR BOTH (6 & 7)
  
 4) B12 = CHECK A BOX (YES OR NO)
  
 5) C2(D) = ADD AN ELEVATION (MAYBE THE LOWEST OF THE 2)
  
 6) SECTION "D" = PLEASE CHECK "CHECK HERE IF
 ATTACHMENTS" THE FLOOD VENT CERTIFICATION OR PRODUCT
 APPROVAL WOULD BE AN ATTACHMENT.
  
 7) PHOTOS = PLEASE ADD DATES TO EACH PHOTO
  
 8) PHOTOS = THE PHOTO DESCRIPTION SHOULD SAY "FRONT
 VIEW", "REAR VIEW", "LEFT SIDE VIEW" AND "RIGHT SIDE
 VIEW" (PHOTOS SHOULD BE OF THE HOUSE NOT THE SITEWALLS)
  
 9) PHOTOS = NEED TO SHOW A FLOOD VENT IN SOME OF THE
 PHOTOS.
  
 10) PLEASE PROVIDE A FINAL SURVEY.
  
 11) PLEASE PROVIDE THE FLOOD VENT CERTIFICATION - ICC
 EVALUATION REPORT OR MIAMI DADE NOA OR FLORIDA STATE
 PRODUCT APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 13:14 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 06:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-13 Cont ID  
Sent By cthroop Date 2022-10-13 Time 14:48 Rev Time 0.00
Received By cthroop Date 2022-10-08 Time 18:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By rmcphers Date 2022-09-21 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-09-19 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-31 Cont ID  
Sent By rmcphers Date 2022-08-31 Time 08:18 Rev Time 0.00
Received By rmcphers Date 2022-08-29 Time 12:00 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 13:11 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-10-13 Cont ID  
Sent By cthroop Date 2022-10-13 Time 14:48 Rev Time 0.00
Received By cthroop Date 2022-10-11 Time 16:40 Sent To  
Notes
2022-10-12 08:24:19SEE COMMENTS UNDER 4TH BUILDING REVIEW.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By rmcphers Date 2022-09-21 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2022-09-21 Time 14:04 Sent To  
Notes
2022-09-21 14:04:41SEE BUILDING PLAN REVIEW

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By rmcphers Date 2022-08-31 Time 08:17 Rev Time 0.00
Received By rmcphers Date 2022-08-31 Time 08:17 Sent To  
Notes
2022-08-31 08:18:20SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 13:13 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 13:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-12 Cont ID  
Sent By cthroop Date 2022-10-12 Time 08:21 Rev Time 0.00
Received By cthroop Date 2022-10-11 Time 16:40 Sent To  
Notes
2022-10-12 08:23:07NOTICE: PLAN PAGES A-101A AND A-101B ARE FOR REFERENCE
 ONLY. SEE MASTER PERMIT 20070078 FOR APPROVED PLANS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By rmcphers Date 2022-09-21 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-09-21 Time 14:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-31 Cont ID  
Sent By rmcphers Date 2022-08-31 Time 08:18 Rev Time 0.00
Received By rmcphers Date 2022-08-31 Time 08:18 Sent To  
Notes
***NONE***