Plan Review Details - Permit 22081358
Plan Review Stops For Permit 22081358
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-11-17 Cont ID  
Sent By jgomez Date 2022-11-17 Time 17:23 Rev Time 0.00
Received By jgomez Date 2022-11-17 Time 16:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-11-17 Cont ID  
Sent By jgomez Date 2022-11-17 Time 10:56 Rev Time 0.00
Received By jgomez Date 2022-11-17 Time 10:56 Sent To  
Notes
2022-11-17 10:57:46DENIED:
 SAME COMMENT #2 FROM PREVIOUS REVIEW APPLIES.
  
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 SYSTEM NO. W-209 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 ADDITIONAL COMMENT:
 3- TALKED TO FERNANDO. HE SAID THE SHINGLES
 UNDERLAYMENT HE IS GOING TO INSTALL IS DIFFERENT THAN
 ONE UPLOADED TO PROJECTDOX. HE WILL SEND ME CORRECT
 PRODUCT APPROVAL AND CONFIRMATION OF FLAT ROOF SYSTEM
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 ORIGINAL COMMENTS:
  
 JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 HAS BEEN REVISED TO FL1654-R30.
 PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION
 REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 SYSTEM NO. W-209 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-11-07 Cont ID  
Sent By jbrooks Date 2022-11-07 Time 08:21 Rev Time 0.00
Received By jbrooks Date 2022-11-07 Time 07:32 Sent To  
Notes
2022-11-07 08:22:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 HAS BEEN REVISED TO FL1654-R30.
 PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION
 REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 SYSTEM NO. W-209 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-21 Cont ID  
Sent By jbrooks Date 2022-10-21 Time 12:36 Rev Time 0.00
Received By jbrooks Date 2022-10-21 Time 07:52 Sent To  
Notes
2022-10-21 12:37:35JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R11
 HAS BEEN REVISED TO FL11602-R13. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT ALL
 APPLICABLE OPTIONS FROM EACH CATEGORY. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. SECOND REQUEST.
 2. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS
 TO INDICATE REROOFING LOW/FLAT SLOPE AREA; IF NOT
 INDICATE BY PLACING AN X IN LOW/FLAT SLOPE AREAS; IF TO
 RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF 2020 CODE
 VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT
 ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. REVISE
 ROOF DIAGRAM/SKETCH TO INCLUDE MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-23 Cont ID  
Sent By jbrooks Date 2022-09-23 Time 08:56 Rev Time 0.00
Received By jbrooks Date 2022-09-23 Time 07:46 Sent To  
Notes
2022-09-23 08:56:44JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10124-R31
 HAS BEEN REVISED TO FL10124-R32. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCTS &
 INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION
 METHOD TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R11
 HAS BEEN REVISED TO FL11602-R13. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT ALL
 APPLICABLE OPTIONS FROM EACH CATEGORY. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-11-17 Cont ID  
Sent By jgomez Date 2022-11-17 Time 17:23 Rev Time 0.00
Received By jgomez Date 2022-11-17 Time 16:53 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-17 Cont ID  
Sent By jgomez Date 2022-11-17 Time 10:57 Rev Time 0.00
Received By jgomez Date 2022-11-16 Time 07:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-07 Cont ID  
Sent By jbrooks Date 2022-11-07 Time 08:22 Rev Time 0.00
Received By jbrooks Date 2022-10-27 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-21 Cont ID  
Sent By jbrooks Date 2022-10-21 Time 12:37 Rev Time 0.00
Received By jbrooks Date 2022-10-14 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-23 Cont ID  
Sent By jbrooks Date 2022-09-23 Time 08:56 Rev Time 0.00
Received By jbrooks Date 2022-09-22 Time 06:15 Sent To  
Notes
***NONE***