Plan Review Details - Permit 22081338
Plan Review Stops For Permit 22081338
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By cthroop Date 2022-12-16 Time 16:36 Rev Time 0.00
Received By cthroop Date 2022-12-16 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 08:23 Rev Time 0.00
Received By cthroop Date 2022-11-03 Time 16:27 Sent To  
Notes
2022-11-04 08:27:241ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 2.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE
 ENHANCED CALCULATED DESIGN PRESSURES OF ZONES 2 AND 3.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By mpeterso Date 2022-11-29 Time 15:39 Rev Time 0.00
Received By mpeterso Date 2022-11-29 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By mpeterso Date 2022-10-13 Time 16:27 Rev Time 0.00
Received By mpeterso Date 2022-10-13 Time 16:13 Sent To  
Notes
2022-10-13 16:40:51ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL THE REQUIRED OUTSIDE RECPTACLES, AT
 THE REAR OF THE HOUSE AS REQUIRED BY NEC 210.52(E)(3)
 BALCONIES, DECKS, AND PORCHES. BALCONIES, DECKS, AND
 PORCHES
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-01-25 Cont ID  
Sent By amhamilt Date 2023-01-25 Time 09:07 Rev Time 0.00
Received By amhamilt Date 2023-01-25 Time 09:07 Sent To  
Notes
2023-01-25 09:07:46**SEE CORRECTED ELEVATION SHEET ATTACHED HERE**

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-12-08 Cont ID  
Sent By amhamilt Date 2022-12-08 Time 15:48 Rev Time 0.00
Received By amhamilt Date 2022-12-08 Time 15:48 Sent To  
Notes
2022-12-08 15:50:03THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE REVISE EXTERIOR OPENING SCHEDULE TO REMOVE
 REFERENCES TO GREY GLASS--PROPERTY IS IN HISTORIC
 DISTRICT AND ONLY CLEAR GLASS IS PERMITTED. LOW E
 COATING PERMISSIBLE ON SIDE AND REAR ELEVATIONS IF
 DESIRED (PLEASE INDICATE IF LOW E COATING WILL BE
 APPLIED).
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-10-19 Cont ID  
Sent By amhamilt Date 2022-10-19 Time 10:21 Rev Time 0.00
Received By amhamilt Date 2022-10-19 Time 10:21 Sent To  
Notes
2022-10-19 10:22:28THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 ADDITIONS/ALTERATIONS REQUIRE SUBMITTAL OF COA FORM AND
 HEARING BY HISTORIC PRESERVATION BOARD, PLEASE REACH
 OUT FOR FORM AND FOR MORE DETAILS.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-26 Cont ID  
Sent By aoliver Date 2023-01-26 Time 10:18 Rev Time 0.00
Received By aoliver Date 2023-01-18 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-16 Cont ID  
Sent By cthroop Date 2022-12-16 Time 16:36 Rev Time 0.00
Received By cthroop Date 2022-11-21 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 08:27 Rev Time 0.00
Received By cthroop Date 2022-09-26 Time 08:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 16:28 Rev Time 0.00
Received By lmarchan Date 2023-02-02 Time 08:30 Sent To  
Notes
2023-02-06 16:28:10NO IMPACT FEES DUE. LEM
2023-02-02 08:35:032/2/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 06:58 Rev Time 0.00
Received By cthroop Date 2022-11-04 Time 06:58 Sent To  
Notes
2022-11-04 06:59:38IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-01-20 Cont ID  
Sent By medwards Date 2023-01-19 Time 17:32 Rev Time 0.00
Received By medwards Date 2023-01-19 Time 17:32 Sent To  
Notes
2023-01-19 17:33:10 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-29 Cont ID  
Sent By medwards Date 2022-11-29 Time 10:16 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 10:16 Sent To  
Notes
2022-11-29 10:34:54THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOULD
 SHOW THE ENTRE HOUSE PLUS THE NEW ADDITION TO SHOW THAT
 THE EXISTING EQUIPMENT IS SIZED TO CONDITION THE
 EXISTING SPACE AND THE NEW ADDITION. THE EQUIPMENT
 SIZING CALCULATIONS SUBMITTED ARE FOR 243 SQ. FT.
 PLEASE PROVIDE THE CALCULATIONS FOR THE EXISTING PLUS
 ALL OF THE ADDITION. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 16:32 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 16:32 Sent To  
Notes
2022-10-04 16:33:151ST REVIEW FMC
 PERMIT: 22081338
  
 CODES IN EFFECT: 2020
  
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
  
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW POWDER ROOM WILL NEED A BATH EXHAUST FAN.
 PLEASE SHOW THE REQUIRED BATH EXHAUST FAN AND
 TERMINATION LOCATION ON THE MECHANICAL DRAWING. FRC
 R303.4
  
 2) PLEASE SHOW THAT THE EXISTING MECHANICAL SYSTEMS ARE
 SIZED TO CARRY THE NEW LOADS CREATED FOR THE ADDITIONAL
 SPACES. FRC R403.7
  
 3) PROVIDE THE DUCT SIZE, GRILLE SIZE AND CFM???S OF
 AIR FOR THE RELOCATED DUCT IN THE NEW STUDY. FBC
 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By rwbrown Date 2022-11-22 Time 14:03 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By rwbrown Date 2022-10-05 Time 15:31 Rev Time 0.00
Received By rwbrown Date 2022-10-05 Time 15:27 Sent To  
Notes
2022-10-05 15:32:451ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - YOU WILL NEED TO
 INCLUDE THE POWDER BATH RENOVATION ON THE 1ST FLOOR
 WITH YOUR RISER DIAGRAM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-11-04 Cont ID  
Sent By cthroop Date 2022-11-04 Time 08:22 Rev Time 0.00
Received By cthroop Date 2022-11-03 Time 16:27 Sent To  
Notes
2022-11-04 08:23:50PROVISO ON PLAN PAGE S-2: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By mpeterso Date 2022-11-29 Time 15:40 Rev Time 0.00
Received By mpeterso Date 2022-11-29 Time 15:40 Sent To  
Notes
2022-11-29 15:40:48ALL PLANS PASSED SIGNATURE REVIEW. MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 16:41 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 16:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-08 Cont ID  
Sent By amhamilt Date 2022-12-08 Time 15:47 Rev Time 0.00
Received By amhamilt Date 2022-12-08 Time 15:47 Sent To  
Notes
2022-12-08 15:47:59REMOVAL OF REAR ADDITION BRINGS PROJECT INTO COMPLIANCE
 FOR LOT COVERAGE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-19 Cont ID  
Sent By amhamilt Date 2022-10-19 Time 10:20 Rev Time 0.00
Received By amhamilt Date 2022-10-19 Time 10:20 Sent To  
Notes
2022-10-19 10:21:29THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 ADDITION APPEARS TO EXCEED BOTH LOT COVERAGE AND FAR
 MAXIMUMS FOR THIS LOT. PLEASE REACH OUT TO DISCUSS.
  
 SEE HISTORIC COMMENT.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  