Plan Review Details - Permit 22081164
Plan Review Stops For Permit 22081164
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-19 Cont ID  
Sent By cpuell Date 2022-09-19 Time 12:45 Rev Time 0.00
Received By cpuell Date 2022-09-19 Time 12:45 Sent To  
Notes
2022-09-19 12:45:42ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 10:05 Rev Time 0.00
Received By cthroop Date 2023-02-03 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By cthroop Date 2023-01-13 Time 11:30 Rev Time 0.00
Received By cthroop Date 2023-01-12 Time 15:37 Sent To  
Notes
2023-01-13 11:30:553RD BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE
 ROOM CREATES A SEPERATE ENCLOSED AREA (STORAGE).
  
 1. PROVIDE A STRUCTURAL DETAIL OF THE WALL BETWEEN THE
 GARAGE AND STORAGE ROOM. WALL SHALL BE DESIGNED PER
 R322.1.5 (FLOOD RESISTANT CONSTRUCTION)
 (ARCHITECTS RESPONSE-SMART FLOOD VENT INSTALLED IN
 INTERIOR WALL. FRAME WALL DETAIL PREVIOUSLY PROVIDED.)
  
 (NEW COMMENT: I HAVE REVIEWED THE CONSTRUCTION
 DOCUMENTS AND CANNOT FIND A DETAIL FOR THIS INTERIOR
 PARTITION. THE ONLY REFERENCE FOUND IS NOTE #13 ON PLAN
 PAGE A-0.00 THAT STATES ALL INTERIOR PARTITIONS TO BE
 METAL STUDS (20 GUAGE MIN) AT 16 INCH O.C. THIS DOES
 NOT COMPLY WITH THE REQUIREMENTS OF R322.
 R322.1.8FLOOD-RESISTANT MATERIALS.
 BUILDING MATERIALS AND INSTALLATION METHODS USED FOR
 FLOORING AND INTERIOR AND EXTERIOR WALLS AND WALL
 COVERINGS BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 SHALL BE FLOOD DAMAGE-RESISTANT
 MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2.
 TECHNICAL BULLITEN #2
 FLOOD DAMAGE-RESISTANT MATERIAL
 FLOOD [DAMAGE]-RESISTANT MATERIAL IS DEFINED BY THE
 NFIP AS ANY BUILDING PRODUCT [MATERIAL, COMPONENT OR
 SYSTEM] CAPABLE OF WITHSTANDING DIRECT AND PROLONGED
 CONTACT WITH FLOODWATERS WITHOUT SUSTAINING SIGNIFICANT
 DAMAGE.)
 (PLEASE DIRECT ME TO THE DETAIL "PREVIOUSLY PROVIDED"
 OR PROVIDE A STRUCTURAL DETAIL FOR THE INTERIOR
 PARTITION THAT COMPLYS WITH R322.)
  
  
 THERE ARE TWO FLOOD OPENING ON ADJACENT WALLS IN THE
 STORAGE ROOM. CORRECT.
 THE GARAGE AREA IS 998SF AND REQUIRES (5) SMART VENTS
 AT 200SF/VENT. ADD AN ADDITIONAL (2) SMART VENTS. (THIS
 IS INCORRECT. SEE BELOW:)
  
 (NEW COMMENT)
 (THE GARAGE AND THE STORAGE AREA ARE TWO SEPERATE
 AREAS)
 (UPON FURTHER REVIEW IT HAS BEEN DETERMINED THAT THE
 GARAGE IS 799SF BASED ON THE DEMENSIONS PROVIDED ON
 PLAN PAGE A-1.01.)
 (3'+9'+2'+9'+2'+9'+3')=37X21'6"=799.2SF) (3) SMART
 VENTS AT 200SF/VENT ARE REQUIRED. PROVIDED.
 (THE STORAGE AREA IS 210SF AS STATED.) (2) SMART VENTS
 ARE REQUIRED. PROVIDED.
 ELEVATION CERTIFICATE INSTRUCTIONS
 ITEM A8.A. PROVIDE THE SQUARE FOOTAGE OF THE CRAWLSPACE
 OR ENCLOSURE(S) BELOW THE LOWEST ELEVATED FLOOR OF AN
 ELEVATED BUILDING WITH OR WITHOUT PERMANENT FLOOD
 OPENINGS. TAKE THE MEASUREMENT FROM THE OUTSIDE OF THE
 CRAWLSPACE OR ENCLOSURE(S).
  
 2.
  
 3.
  
 (NEW COMMENTS)
 (THE BUILDING SQUARE FOOT DATA ON PLAN PAGE SP-1.01
 STATES PROPOSED 3 CAR GARAGE, STORAGE: 998 S.F. (LESS
 THAN 1000 S.F)
 (THE CORRECT DATA IS 3 CAR GARAGE 799 S.F. STORAGE 210
 S.F. 1009 S.F.) >1000 S.F.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-19 Cont ID  
Sent By cthroop Date 2022-12-19 Time 14:19 Rev Time 0.00
Received By cthroop Date 2022-12-19 Time 05:38 Sent To  
Notes
2022-12-19 14:58:532ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE
 ROOM CREATES A SEPERATE ENCLOSED AREA (STORAGE).
  
 1. PROVIDE A STRUCTURAL DETAIL OF THE WALL BETWEEN THE
 GARAGE AND STORAGE ROOM. WALL SHALL BE DESIGNED PER
 R322.1.5 (FLOOD RESISTANT CONSTRUCTION)
  
 1. THERE ARE TWO FLOOD OPENING ON ADJACENT WALLS IN THE
 STORAGE ROOM. THE GARAGE AREA IS 998SF AND REQUIRES (5)
 SMART VENTS AT 200SF/VENT. ADD AN ADDITIONAL (2) SMART
 VENTS.
  
 R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW
 THE DESIGN FLOOD ELEVATION SHALL:
 1. 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING
 ACCESS OR STORAGE.
 2. 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE
 FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH
 SECTION R322.2.2.1:
  
 2. PROVIDE THE PROPOSED SMART VENT MODEL NUMBER ON PLAN
 PAGE A-1.01.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 3. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-26 Cont ID  
Sent By cthroop Date 2022-10-26 Time 12:01 Rev Time 0.00
Received By cthroop Date 2022-10-24 Time 12:09 Sent To  
Notes
2022-10-26 12:16:531ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). FLOOD ZONE AE 7.
 SUBMIT A CONSTRUCTION DRAWING ELEVATION CERTIFICATE FOR
 THE PROPOSED GARAGE. (SEE COMMENTS UNDER THE NFIP
 REVIEW)
  
 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
  
 3. ENERGY SUBMITTAL IS MISSING THE CEILING INSULATION.
 SHOW INSULATION TYPE AND R VALUE ON PLANS.
 R401.2COMPLIANCE.
  
 4.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE
 ENHANCED CALCULATED DESIGN PRESSURES OF ZONES 2 AND 3.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 5. SITE DRAINAGE PLAN C-1 SHOWS TOP OF GARAGE FLOOR TO
 BE 6'0" NAVD. PLAN PAGE A-1.01 SHOWS TOP OF GARAGE
 FLOOR TO BE 5'O" NAVD.
 PLEASE CLARIFY?
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 6. PROVIDE THE LOCATION, TYPE OF VENT AND COVERAGE
 PROVIDED FOR EACH GARAGE FLOOD VENT.
 GARAGE IS 998 SF.
 R322
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-30 Cont ID  
Sent By fgiaquin Date 2023-01-30 Time 22:22 Rev Time 0.00
Received By fgiaquin Date 2023-01-30 Time 22:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By fgiaquin Date 2022-12-06 Time 15:31 Rev Time 0.00
Received By fgiaquin Date 2022-12-06 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By fgiaquin Date 2022-10-06 Time 18:35 Rev Time 0.00
Received By fgiaquin Date 2022-10-05 Time 22:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-11-28 Cont ID  
Sent By rrossano Date 2022-11-28 Time   Rev Time 0.00
Received By rrossano Date 2022-11-28 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 10:14 Rev Time 0.00
Received By lmarchan Date 2023-01-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-13 Cont ID  
Sent By cthroop Date 2023-01-13 Time 12:49 Rev Time 0.00
Received By cthroop Date 2023-01-04 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-20 Cont ID  
Sent By cthroop Date 2022-12-20 Time 16:41 Rev Time 0.00
Received By cthroop Date 2022-11-21 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-26 Cont ID  
Sent By cthroop Date 2022-10-26 Time 12:16 Rev Time 0.00
Received By cthroop Date 2022-09-16 Time 05:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 16:42 Rev Time 0.00
Received By lmarchan Date 2023-02-03 Time 09:47 Sent To  
Notes
2023-02-06 16:42:03NO FEES DUE FOR IMPACT. LEM
2023-02-03 09:48:03EMAILED IMPACT FOR REVIEW AS REQUESTED BY DYLAN BATTLES
 -AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-01-13 Cont ID  
Sent By cthroop Date 2023-01-13 Time 12:49 Rev Time 0.00
Received By cthroop Date 2023-01-13 Time 12:49 Sent To  
Notes
2023-01-13 12:50:18IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By cthroop Date 2022-10-24 Time 16:11 Rev Time 0.00
Received By cthroop Date 2022-10-24 Time 12:09 Sent To  
Notes
2022-10-24 16:11:49IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By medwards Date 2023-01-19 Time 11:55 Rev Time 0.00
Received By medwards Date 2023-01-19 Time 11:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By medwards Date 2022-11-29 Time 08:45 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 08:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 06:00 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 06:00 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 10:04 Rev Time 0.00
Received By cthroop Date 2023-02-03 Time 13:15 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By cthroop Date 2023-01-13 Time 12:49 Rev Time 0.00
Received By cthroop Date 2023-01-12 Time 15:37 Sent To  
Notes
2023-01-13 12:18:583RD NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DETACHED GARAGE. FLOOD ZONE AE 7. DESIGN FLOOD
 ELEVATION 9'0"NAVD.
  
  
 1. A VALID DIGITAL SIGNATURE IS REQUIRED ON THE
 ELEVATION CERTIFICATE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 2. LINE A8A) SHOULD BE THE TOTAL SQUARE FOOTAGE OF THE
 GARAGE AND STORAGE AREA. THIS IS 1009SF. SEE
 CALCULATION UNDER BLDG REVIEW.
  
 3. LINE C2D) SHOULD BE N/A. THIS IS A DETACHED GARAGE
 ACCESSORY STRUCTURE.
  
 4. LINE C2E) DATA MISSING. STATE THE ELEVATION OF THE
 BOTTOM OF THE WALL MOUNTED A/C CU. MINIMUM OF 9'0"NAVD.
  
 5. LINE C2F) SHOULD BE 3.36'.
  
 6. LINE C2G) SHOULD BE 4.92'.
  
 7. REFERENCE SECTION D COMMENTS FOR THE FOLLOWING:
 7A. MACHINERY SHOULD BE THE WALL MOUNTED A/C CU.
 7B. THERE ARE ONLY 5 SMART VENTS INSTALLED. SEE LINE
 A8B OF EC.
 7C. ADD COMMENT FROM THE EC INSTRUCTIONS AS FOLLOWS:
 THE INTERIOR GARAGE FLOOR IS USED FOR THE SMART VENT
 INSTALLED IN THE INTERIOR PARTITION.
 EC INSTRUCTIONS: ITEM A8.B-D. ENTER IN ITEM A8.B THE
 NUMBER OF PERMAMENT FLOOD OPENINGS IN THE CRAWLSPACE OR
 ENCLOSURE(S) THAT ARE NO HIGHER THAN 1.0 FOOT ABOVE THE
 HIGHER OF THE EXTERIOR OR INTERIOR GRADE OR FLOOR
 IMMEDIATELY BELOW THE OPENING. (A PERMAMENT FLOOD
 OPENING IS A FLOOD VENT OR OTHER OPENING THAT ALLOWS
 THE FREE PASSGAE OF WATER AUTOMATICALLY IN BOTH
 DIRECTIONS WITHOUT HUMAN INTERVENTION.) IF THE INTERIOR
 GRADE ELEVATION IS USED, NOTE THIS IN THE COMMENTS AREA
 OF SECTION D.
  
 NOTICE: THE FOLLOWING (2) ELEVATION CERTIFICATES ARE
 REQUIRED.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-12-20 Cont ID  
Sent By cthroop Date 2022-12-20 Time 16:41 Rev Time 0.00
Received By cthroop Date 2022-12-19 Time 05:38 Sent To  
Notes
2022-12-19 15:51:462ND NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DETACHED GARAGE. FLOOD ZONE AE 7. DESIGN FLOOD
 ELEVATION 9'0"NAVD.
  
 1. SUBMIT A CONSTRUCTION DRAWING ELEVATION CERTIFICATE
 FOR REVIEW. THE EC SUBMITTED FOR REVIEW IS DATED
 4/9/2019 AND DOES NOT APPLY TO THIS STRUICTURE.
  
 NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE
 ROOM CREATES A SEPERATE ENCLOSED AREA.
  
 2. INCLUDE THE SQUARE FOOTAGE OF THE GARAGE AND STORAGE
 ROOM FOR TOTAL SQUARE FOOTAGE.
  
 3. TWO (2) VENTS ARE INSTALLED IN THE STORAGE ROOM.
  
 4. TWO (2) ADDITIONAL VENTS ARE REQUIRED IN THE GARAGE
 AREA.
  
 5. THE ELEVATION CERTIFICATE REQUIRES A VALID DIGITAL
 SIGNATURE OF THE SURVEYOR.
  
 NOTICE: PROVIDE THE FOLLOWING (3) ELEVATION
 CERTIFICATES AS REQUIRED.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By cthroop Date 2022-10-25 Time 08:20 Rev Time 0.00
Received By cthroop Date 2022-10-24 Time 12:20 Sent To  
Notes
2022-10-25 08:44:081ST NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BU, BN, PX, CFM
 PLANS EXAMINER II
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4729-17
 FEMA DESK REFERENCE P 758
 NATIONAL FLOOD INSURANCE PROGRAM (NFIP)
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR
 THIS SITE ARE AE 7 AND AE 8.
 DESIGN FLOOD ELEVATIONS ARE 9'0"NAVD AND 10'0"NAVD.
  
 1.THE PROPOSED FREE STANDING GARAGE IS LOCATED IN FLOOD
 ZONE AE 7.
 SUBMIT A CONSTRUCTION DRAWING ELEVATION CERTIFICATE FOR
 REVIEW PER FEMA/NFIP, FBC R322 AND CITY ORDINANCE NO.
 4729-17.
  
 NOTICE: (3) ELEVATION CERTIFICATES ARE REQUIRED.
  
 1.A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 IS REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO C/O.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By rwbrown Date 2022-09-16 Time 10:33 Rev Time 0.00
Received By rwbrown Date 2022-09-16 Time 10:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-12-19 Cont ID  
Sent By cthroop Date 2022-12-19 Time 11:03 Rev Time 0.00
Received By cthroop Date 2022-12-19 Time 05:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By cthroop Date 2022-10-24 Time 16:12 Rev Time 0.00
Received By cthroop Date 2022-10-24 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 10:04 Rev Time 0.00
Received By cthroop Date 2023-02-03 Time 13:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By cthroop Date 2023-01-13 Time 12:48 Rev Time 0.00
Received By cthroop Date 2023-01-12 Time 15:37 Sent To  
Notes
2023-01-13 12:48:403RD SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES INCLUDING ELEVATION CERTIFICATE
 EXCEPT MECHANICAL PLAN (CONTRACTOR SIGNED)
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-19 Cont ID  
Sent By cthroop Date 2022-12-19 Time 11:02 Rev Time 0.00
Received By cthroop Date 2022-12-19 Time 05:38 Sent To  
Notes
2022-12-19 11:03:512ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES EXCEPT MECHANICAL (CONTRACTOR
 SIGNED)
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-26 Cont ID  
Sent By cthroop Date 2022-10-26 Time 11:19 Rev Time 0.00
Received By cthroop Date 2022-10-24 Time 12:09 Sent To  
Notes
2022-10-26 11:20:271ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES EXCEPT MECHANICAL (CONTRACTOR
 SIGNED)
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-01-27 Cont ID  
Sent By ASangele Date 2023-01-27 Time 11:10 Rev Time 0.00
Received By asangele Date 2023-01-27 Time 11:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-01-11 Cont ID  
Sent By VBroglia Date 2023-01-11 Time 14:27 Rev Time 0.00
Received By vbroglia Date 2023-01-11 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By ajones Date 2022-12-20 Time 11:21 Rev Time 0.00
Received By ajones Date 2022-12-20 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By afowlkes Date 2022-09-22 Time 10:13 Rev Time 0.00
Received By afowlkes Date 2022-09-22 Time 10:13 Sent To  
Notes
2022-09-22 10:14:1609/22/22 FAILED
  
 PER CITY CODE, ROOFED ACCESSORY STRUTURES SHALL BE
 LOCATED NO CLOSER THAN 6 FT TO THE PRIMARY STRUCTURE
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431