Plan Review Details - Permit 22081161
Plan Review Stops For Permit 22081161
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-11-19 Cont ID  
Sent By cpuell Date 2022-11-19 Time 09:41 Rev Time 0.00
Received By cpuell Date 2022-11-19 Time 09:41 Sent To  
Notes
2022-11-19 09:42:38ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By pvalenti Date 2023-01-31 Time 07:05 Rev Time 0.00
Received By pvalenti Date 2023-01-31 Time 07:00 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By pvalenti Date 2022-12-19 Time 07:58 Rev Time 0.00
Received By pvalenti Date 2022-12-19 Time 07:58 Sent To  
Notes
2022-12-19 08:04:08PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS PLAN REVIEW DENIED:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-07 Cont ID  
Sent By pvalenti Date 2023-02-07 Time 12:38 Rev Time 0.00
Received By pvalenti Date 2023-02-07 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-31 Cont ID  
Sent By pvalenti Date 2023-01-31 Time 07:22 Rev Time 0.00
Received By pvalenti Date 2023-01-31 Time 07:00 Sent To  
Notes
2023-01-31 07:37:39PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - ELECTRIC, OK
 NOTE: SUB-PERMIT # 23011279 IS IN APPLICATION. THIS
 SUB-PERMIT MUST BE APPROVED PRIOR TO DEMO WORK.
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. A PLUMBING SUB-PERMIT TO INCLUDE THE CAPPING OF
 EXISTING PLUMBING LINES IS REQUIRED (SUBMIT APPLICATION
 TO BUILDING DIVISION);
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By pvalenti Date 2022-12-19 Time 08:09 Rev Time 0.00
Received By pvalenti Date 2022-12-19 Time 07:58 Sent To  
Notes
2022-12-19 08:12:28PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART
 MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-26 Cont ID  
Sent By jleahy Date 2023-01-26 Time 11:22 Rev Time 0.00
Received By jleahy Date 2023-01-26 Time 11:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-01-20 Cont ID  
Sent By mpeterso Date 2023-01-20 Time 11:40 Rev Time 0.00
Received By mpeterso Date 2023-01-20 Time 11:36 Sent To  
Notes
2023-01-20 11:42:03ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENT REGARDING ELECTRICAL SUB PERMIT APP
 REQUIRED. PLEASE CORRECT AS OUTLINED BELOW.
  
 WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. THIS IS A BUILDING DEPARTMENT
 POLICY TO ENSURE ELECTRICAL SAFETY DURING DEMOLITION.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION FROM A
 LICENSED ELECTRICAL CONTRACTOR TO [email protected],
 [email protected], AND [email protected] . WHEN WE
 RECEIVE THE APPLICATION THE ELECTRICAL REVIEWERS WILL
 APPROVE THE PLAN REVIEW.
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 09:47 Rev Time 0.00
Received By mpeterso Date 2022-12-01 Time 09:21 Sent To  
Notes
2022-12-01 09:52:00ELECTRIC REVIEW FAILED
  
 1) APPLICATION INDICATES THAT MINOR ELECTRIC WORK IS TO
 BE DONE, HOWEVER THERE IS NO ELECTRIC WORK SHOWN ON
 PLANS. IN ADDITION PLEASE PROVIDE AN ELECTRIC PLAN AND
 WORK SCOPE. FBC 107.2
 2) THE SUBMITTAL ALSO STATES THIS IS A FOR DEMOLITION.
 IF THIS IS TRUE, PLEASE REMOVE THE PROPOSED FLOOR PLAN
 FROM THE SUBMITTAL. FBC 107.2
 3) A DEMOLITION PERMIT REQUIRES AN ELECTRICAL SUB
 PERMIT APPLICATION TO BE INCLUDED WITH THE SUBMITTAL AS
 PER OUR BUILDING OFFICIALS POLICY. THIS IS A BUILDING
 DEPARTMENT POLICY TO ENSURE ELECTRICAL SAFETY DURING
 DEMOLITION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-01-23 Cont ID  
Sent By rrossano Date 2023-01-23 Time   Rev Time 0.00
Received By rrossano Date 2023-01-23 Time   Sent To  
Notes
2023-01-23 10:26:46PASSED WITH PROVISOS:
  
 PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED
 BY BUILDING DEPT. (UTILITY SIGNOFFS - WATER/SEWER,
 ETC.)
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By RROSSANO Date 2022-12-19 Time   Rev Time 0.00
Received By rrossano Date 2022-12-19 Time   Sent To  
Notes
2022-12-19 09:48:59PLEASE ADDRESS BUILDING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-18 Cont ID  
Sent By cwalker Date 2022-11-18 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-27 Cont ID  
Sent By amhamilt Date 2022-12-27 Time 12:04 Rev Time 0.00
Received By amhamilt Date 2022-12-27 Time 12:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-07 Cont ID  
Sent By pvalenti Date 2023-02-07 Time 14:49 Rev Time 0.00
Received By lmarchan Date 2023-02-06 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-31 Cont ID  
Sent By pvalenti Date 2023-01-31 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2023-01-19 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-28 Cont ID  
Sent By aoliver Date 2022-12-28 Time 08:47 Rev Time 0.00
Received By aoliver Date 2022-11-17 Time 07:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By mpeterso Date 2023-01-20 Time 11:42 Rev Time 0.00
Received By mpeterso Date 2023-01-20 Time 11:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 09:52 Rev Time 0.00
Received By mpeterso Date 2022-12-01 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-27 Cont ID  
Sent By amhamilt Date 2022-12-27 Time 12:04 Rev Time 0.00
Received By amhamilt Date 2022-12-27 Time 12:04 Sent To  
Notes
***NONE***