Plan Review Details - Permit 22081123
Plan Review Stops For Permit 22081123 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-12-02 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-11-30 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-11-28 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-11-28 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-11-23 |
Time |
05:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-12-01 |
Time |
07:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-12-01 |
Time |
07:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-11-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-11-23 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-11-23 |
Time |
08:26 |
Sent To |
|
|
Notes |
2022-11-23 08:38:10 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT-22981123 | | 11/23/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | BACKFLOW PREVENTER IN ACCORDANCE WITH SEC. 608.16 FBC | | P, AND SECS. C, D, & E WPB UTILITIES CROSS-CONNECTION | | MANUAL. POTABLE WATER BACKFLOW PREVENTERS SHALL BE | | CERTIFIED AS LEAD-FREE AND SHALL BE ON THE APPROVED | | DEVICE LIST PUBLISHED BY THE UNIVERSITY OF SOUTHERN | | CALIFORNIA (USC). | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
2 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-12-02 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-12-02 |
Time |
11:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
1 |
Status |
F |
Date |
2022-11-28 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-11-28 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-11-28 |
Time |
10:44 |
Sent To |
|
|
Notes |
2022-11-28 10:45:20 | PER RJENKINS - DENIED, NO BACKFLOW SPECS SUBMITTED |
|
|
|