Plan Review Details - Permit 22081071
Plan Review Stops For Permit 22081071
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-19 Cont ID  
Sent By pleduc Date 2023-01-19 Time   Rev Time 0.00
Received By pleduc Date 2023-01-19 Time 11:02 Sent To  
Notes
2023-01-19 11:03:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) RELOCATED DROPS MAY NOT BE ABLE TO BE ISOLATED;
 HOWEVER, THE FLOOR AREA MAY AND BE TESTED AT 200PSI FOR
 2HRS.
  
 IF NOT OR LESS THAN 20 HEADS:
  
 2) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 3) USE FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE
 CALCULATIONS MINUS 5 PSI PER FLOOR FOR ELEVATION
 PRESSURE LOSS.
 PER NFPA 13
  
 3.3.24 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED
 STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO
 SPRINKLER SYSTEM COMPONENTS EXCLUSIVE OF SURGE
 PRESSURES AND EXCLUSIVE OF PRESSURE FROM THE FIRE
 DEPARTMENT CONNECTION.
  
 25.2 ACCEPTANCE REQUIREMENTS.
  
 25.2.1* HYDROSTATIC TESTS.
 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.5,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
 25.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.3
 BAR) SHALL BE TESTED AS DESCRIBED IN 25.2.1.1, AT A
 PRESSURE OF 50 PSI (3.4 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
 25.2.1.3 WHERE COLD WEATHER WILL NOT PERMIT TESTING
 WITH WATER, AN INTERIM AIR TEST SHALL BE PERMITTED TO
 BE CONDUCTED AS DESCRIBED IN 25.2.2. THIS PROVISION
 SHALL NOT REMOVE OR REPLACE THE REQUIREMENT FOR
 CONDUCTING THE HYDROSTATIC TEST AS DESCRIBED IN
 25.2.1.1.
 25.2.1.4 MODIFICATIONS TO EXISTING PIPING SYSTEMS SHALL
 REQUIRE TESTING AT SYSTEM WORKING PRESSURE.
 25.2.1.4.1 WHERE MODIFICATION IS MADE TO AN EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN
 200 PSI (13.8 BAR) FOR 2 HOURS.
 25.2.1.4.2 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH
 AS RELOCATED DROPS, SHALL REQUIRE TESTING AT SYSTEM
 WORKING PRESSURE.
 25.2.1.5* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR
 PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER
 ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI
 (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES.
 SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED
 SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  
 25.2.1.8* WHEN SYSTEMS ARE BEING HYDROSTATICALLY
 TESTED, TESTS SHALL BE PERMITTED TO BE CONDUCTED WITH
 PENDENT OR HORIZONTAL SIDEWALL SPRINKLERS OR PLUGS
 INSTALLED IN FITTINGS. ANY PLUGS SHALL BE REPLACED WITH
 PENDENT OR HORIZONTAL SIDEWALL SPRINKLERS AFTER THE
 TEST IS COMPLETED.
  
 25.2.1.10 PROVISION SHALL BE MADE FOR THE PROPER
 DISPOSAL OF WATER USED FOR FLUSHING OR TESTING
  
 4) PLEASE ENSURE THAT A MECHANICAL INSPECTION # 603 -
 FIRE SPRINKLER PIPE IS CALLED IN WITH FIRE SPRINKLER
 #310 ? FIRE SPRINKLER HEAD AND # 311 - PRESSURE TEST
 INSPECTIONS.
  
 5) CONTRACTOR TO PROVIDE FOR WORKING PRESSURE
 VERIFICATION (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM
 IS CHARGED/DISCHARGED UNDER WORKING PRESSURE. (I.E.
 VISUAL FOR LEAKS & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-25 Cont ID  
Sent By pleduc Date 2022-08-25 Time   Rev Time 0.00
Received By pleduc Date 2022-08-25 Time 16:12 Sent To  
Notes
2022-08-25 16:13:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) RELOCATED DROPS MAY NOT BE ABLE TO BE ISOLATED;
 HOWEVER, THE FLOOR AREA MAY AND BE TESTED AT 200PSI FOR
 2HRS.
  
 IF NOT OR LESS THAN 20 HEADS:
  
 2) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 3) USE FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE
 CALCULATIONS MINUS 5 PSI PER FLOOR FOR ELEVATION
 PRESSURE LOSS.
 PER NFPA 13
  
 3.3.24 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED
 STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO
 SPRINKLER SYSTEM COMPONENTS EXCLUSIVE OF SURGE
 PRESSURES AND EXCLUSIVE OF PRESSURE FROM THE FIRE
 DEPARTMENT CONNECTION.
  
 25.2 ACCEPTANCE REQUIREMENTS.
  
 25.2.1* HYDROSTATIC TESTS.
 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.5,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
 25.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.3
 BAR) SHALL BE TESTED AS DESCRIBED IN 25.2.1.1, AT A
 PRESSURE OF 50 PSI (3.4 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
 25.2.1.3 WHERE COLD WEATHER WILL NOT PERMIT TESTING
 WITH WATER, AN INTERIM AIR TEST SHALL BE PERMITTED TO
 BE CONDUCTED AS DESCRIBED IN 25.2.2. THIS PROVISION
 SHALL NOT REMOVE OR REPLACE THE REQUIREMENT FOR
 CONDUCTING THE HYDROSTATIC TEST AS DESCRIBED IN
 25.2.1.1.
 25.2.1.4 MODIFICATIONS TO EXISTING PIPING SYSTEMS SHALL
 REQUIRE TESTING AT SYSTEM WORKING PRESSURE.
 25.2.1.4.1 WHERE MODIFICATION IS MADE TO AN EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN
 200 PSI (13.8 BAR) FOR 2 HOURS.
 25.2.1.4.2 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH
 AS RELOCATED DROPS, SHALL REQUIRE TESTING AT SYSTEM
 WORKING PRESSURE.
 25.2.1.5* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR
 PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER
 ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI
 (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES.
 SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED
 SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  
 25.2.1.8* WHEN SYSTEMS ARE BEING HYDROSTATICALLY
 TESTED, TESTS SHALL BE PERMITTED TO BE CONDUCTED WITH
 PENDENT OR HORIZONTAL SIDEWALL SPRINKLERS OR PLUGS
 INSTALLED IN FITTINGS. ANY PLUGS SHALL BE REPLACED WITH
 PENDENT OR HORIZONTAL SIDEWALL SPRINKLERS AFTER THE
 TEST IS COMPLETED.
  
 25.2.1.10 PROVISION SHALL BE MADE FOR THE PROPER
 DISPOSAL OF WATER USED FOR FLUSHING OR TESTING
  
 4) PLEASE ENSURE THAT A MECHANICAL INSPECTION # 603 -
 FIRE SPRINKLER PIPE IS CALLED IN WITH FIRE SPRINKLER
 #310 ? FIRE SPRINKLER HEAD AND # 311 - PRESSURE TEST
 INSPECTIONS.
  
 5) CONTRACTOR TO PROVIDE FOR WORKING PRESSURE
 VERIFICATION (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM
 IS CHARGED/DISCHARGED UNDER WORKING PRESSURE. (I.E.
 VISUAL FOR LEAKS & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-20 Cont ID  
Sent By jgomez Date 2023-01-20 Time 10:08 Rev Time 0.00
Received By jgomez Date 2023-01-18 Time 08:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-17 Cont ID  
Sent By jgomez Date 2023-01-17 Time 11:09 Rev Time 0.00
Received By jgomez Date 2023-01-13 Time 18:55 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By jleahy Date 2022-08-26 Time 11:36 Rev Time 0.00
Received By jleahy Date 2022-08-24 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-20 Cont ID  
Sent By jgomez Date 2023-01-20 Time 10:08 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 15:44 Sent To  
Notes
2023-01-20 10:08:29633.102 F.S. (2022) DEFINITIONS. (CONTINUATION)
 THIS SUBSECTION MAY NOT BE CONSTRUED TO INCLUDE
 ENGINEERS OR ARCHITECTS WITHIN THE DEFINED TERMS AND
 DOES NOT LIMIT OR PROHIBIT A LICENSED FIRE PROTECTION
 ENGINEER OR ARCHITECT WITH FIRE PROTECTION DESIGN
 EXPERIENCE FROM DESIGNING ANY TYPE OF FIRE PROTECTION
 SYSTEM. A DISTINCTION IS MADE BETWEEN SYSTEM DESIGN
 CONCEPTS PREPARED BY THE DESIGN PROFESSIONAL AND SYSTEM
 LAYOUT AS DEFINED IN THIS SECTION AND TYPICALLY
 PREPARED BY THE CONTRACTOR. HOWEVER, A PERSON CERTIFIED
 UNDER THIS CHAPTER AS A CONTRACTOR I OR CONTRACTOR II
 MAY DESIGN NEW FIRE PROTECTION SYSTEMS OF 49 OR FEWER
 SPRINKLERS; MAY DESIGN THE ALTERATION OF AN EXISTING
 FIRE SPRINKLER SYSTEM IF THE ALTERATION CONSISTS OF THE
 RELOCATION, ADDITION, OR DELETION OF 49 OR FEWER
 SPRINKLERS, NOTWITHSTANDING THE SIZE OF THE EXISTING
 FIRE SPRINKLER SYSTEM; OR MAY DESIGN THE ALTERATION OF
 AN EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
 CONSISTS OF THE RELOCATION OR DELETION OF 249 OR FEWER
 SPRINKLERS, NOTWITHSTANDING THE SIZE OF THE EXISTING
 FIRE SPRINKLER SYSTEM, IF THERE IS NO CHANGE OF
 OCCUPANCY OF THE AFFECTED AREAS, AS DEFINED IN THE
 FLORIDA BUILDING CODE AND THE FLORIDA FIRE PREVENTION
 CODE, AND THERE IS NO CHANGE IN THE WATER DEMAND AS
 DEFINED IN NFPA 13, ???STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS,??? AND IF THE OCCUPANCY HAZARD
 CLASSIFICATION AS DEFINED IN NFPA 13 IS REDUCED OR
 REMAINS THE SAME AS A RESULT OF THE ALTERATION.
 CONFLICTS BETWEEN THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE SHALL BE RESOLVED PURSUANT
 TO S. 553.73(1)(D). 1A PERSON CERTIFIED AS A CONTRACTOR
 I, CONTRACTOR II, OR CONTRACTOR IV MAY DESIGN A NEW
 FIRE PROTECTION SYSTEM OR DESIGN THE ALTERATION OF AN
 EXISTING FIRE PROTECTION SYSTEM, THE SCOPE OF WHICH
 COMPLIES WITH NFPA 13D, ???STANDARD FOR THE
 INSTALLATION OF SPRINKLER SYSTEMS IN ONE- AND
 TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES,??? AS
 ADOPTED BY THE STATE FIRE MARSHAL, NOTWITHSTANDING THE
 NUMBER OF FIRE SPRINKLERS. CONTRACTOR-DEVELOPED PLANS
 MAY NOT BE REQUIRED BY ANY LOCAL PERMITTING AUTHORITY
 TO BE SEALED BY A REGISTERED PROFESSIONAL ENGINEER.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-17 Cont ID  
Sent By jgomez Date 2023-01-17 Time 11:05 Rev Time 0.00
Received By jgomez Date 2023-01-17 Time 10:25 Sent To  
Notes
2023-01-17 11:06:31SIGNATURE REVIEW.
  
 1- MORE THAN 49 SPRINKLER HEADS. FIRE SPRINKLER PLAN
 NEEDS TO BE SIGNED AND SEALED BY DESIGN PROFESSIONAL.
 SEC. 105.3.1.2(2) CITY AMENDMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By jleahy Date 2022-08-26 Time 11:36 Rev Time 0.00
Received By jleahy Date 2022-08-26 Time 11:34 Sent To  
Notes
2022-08-26 11:36:28FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS NOT SIGNED.