Plan Review Details - Permit 22081021
Plan Review Stops For Permit 22081021
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-03-01 Cont ID  
Sent By shill Date 2023-03-01 Time 15:58 Rev Time 0.00
Received By shill Date 2023-03-01 Time 15:58 Sent To  
Notes
2023-03-01 15:59:20NO NEW DOCUMENTS SUBMITTED. SEE PREVIOUS PLAN REVIEWS.
 THERE ARE 16 DOCUMENTS IN THE SUPPORTING DOCUMENTS
 FILE. PLEASE EMAIL [email protected] AND HAVE
 DOCUMENTS NOT REQUIRED REMOVED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 09:22 Rev Time 0.00
Received By shill Date 2023-01-25 Time 09:22 Sent To  
Notes
2023-01-25 09:24:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A LETTER FROM THE MANUFACTURER THAT OCEAN
 VIEW (FLOORING PROPOSED), THERMACORE (FLAME SPREAD
 TEST), AND ALTAMONTE SPRINGS FLOORING (STC/IIC TESTS)
 ARE THE SAME PRODUCT. SEE PREVIOUS LISTS FOR CODE
 REFERENCES.
  
 A LETTER FROM HF DESIGN WAS SUBMITTED. THIS APPEARS TO
 BE THE SUPPLIER. PLEASE PROVIDE A LETTER FROM THE
 FLOORING MANUFACTURER, INCLUDING CONTACT INFORMATION
 (PREFERABLY EMAIL). ALTERNATIVELY, PROVIDE THE THREE
 TEST REPORTS (STC, ICC, FLAME SPREAD) FOR THE ASSEMBLY
 PROPOSED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-27 Cont ID  
Sent By shill Date 2022-12-27 Time 18:53 Rev Time 0.00
Received By shill Date 2022-12-27 Time 18:53 Sent To  
Notes
2022-12-27 18:53:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A LETTER FROM THE MANUFACTURER THAT OCEAN
 VIEW (FLOORING PROPOSED), THERMACORE (FLAME SPREAD
 TEST), AND ALTAMONTE SPRINGS FLOORING (STC/IIC TESTS)
 ARE THE SAME PRODUCT. SEE PREVIOUS LISTS FOR CODE
 REFERENCES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By shill Date 2022-11-30 Time 05:45 Rev Time 0.00
Received By shill Date 2022-11-30 Time 05:45 Sent To  
Notes
2022-11-30 05:53:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC EB 702.6, ALL NEW WORK SHALL COMPLY WITH THE
 MATERIALS AND METHODS IN THE FLORIDA BUILDING CODE,
 BUILDING. PLAN STATES THAT WHISPERMAT WILL BE INSTALLED
 IN THE BATHROOM BUT MAKES NO REFERENCE TO UNDERLYMENT
 FOR THE VINYL FLOOR.
  
 1. NUVELLE AND DENSITY OCEAN VIEW VINYL FLOORING
 (SUNCREST) INSTALLED OVER EXISTING TILE FLOORING IS
 PROPOSED. IT IS NOT CLEAR IF AN UNDERLAYMENT IS
 REQUIRED BECAUSE THE STC/IIC TEST REPORTS WERE NOT
 PROVIDED. A COMPLETE REVIEW CANNOT BE DONE AT THIS
 TIME.
  
 2. ASTM E-84 (FLAME SPREAD) TEST FOR THERMACORE VINYL
 FOORING. IT IS NOT CLEAR IF AN UNDERLAYMENT IS REQUIRED
 (NO FLAME SPREAD REQUIREMENT FOR FLOORING). THIS CAN BE
 ACCEPTED IN LIEU OF A FLAME SPREAD TEST FOR THE
 UNDERLAYMENT IF YOU PROVIDE A LETTER FROM THE
 MANUFACTURER WHICH STATES THAT THE PRODUCT TESTED IS
 THE SAME AS THE PRODUCT PROPOSED (NUVELLE DENSITY OCEAN
 VIEW).
  
 3. WHISPERMAT UNDER NEW TILE FLOORING IS ALSO PROPOSED,
 THAT IS ACCEPTABLE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-21 Cont ID  
Sent By rmcdouga Date 2022-11-21 Time 16:36 Rev Time 0.00
Received By shill Date 2022-11-21 Time 16:36 Sent To  
Notes
2022-11-21 16:43:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC EB 702.6, ALL NEW WORK SHALL COMPLY WITH THE
 MATERIALS AND METHODS IN THE FLORIDA BUILDING CODE,
 BUILDING. PLAN STATES THAT WHISPERMAT WILL BE INSTALLED
 IN THE BATHROOM BUT MAKES NO REFERENCE TO UNDERLYMENT
 FOR THE VINYL FLOOR.
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By cwalker Date 2022-12-07 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-11 Cont ID  
Sent By cwalker Date 2022-10-11 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-01 Cont ID  
Sent By shill Date 2023-03-01 Time 15:59 Rev Time 0.00
Received By shill Date 2023-02-06 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 09:24 Rev Time 0.00
Received By shill Date 2023-01-10 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-27 Cont ID  
Sent By shill Date 2022-12-27 Time 18:53 Rev Time 0.00
Received By shill Date 2022-12-06 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-30 Cont ID  
Sent By shill Date 2022-11-30 Time 05:53 Rev Time 0.00
Received By shill Date 2022-11-23 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-21 Cont ID  
Sent By shill Date 2022-11-21 Time 16:43 Rev Time 0.00
Received By shill Date 2022-10-08 Time 18:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By rwbrown Date 2022-11-08 Time 13:55 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved