Plan Review Details - Permit 22080984
Plan Review Stops For Permit 22080984
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By rmcdouga Date 2023-04-07 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2023-04-07 Time 11:10 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2022-10-27 Time 11:19 Sent To  
Notes
2022-10-27 11:21:43PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ???ASBESTOS???
 IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By rmcdouga Date 2023-04-07 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2023-04-07 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2022-10-27 Time 11:19 Sent To  
Notes
2022-10-27 12:46:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 FLOORING SOUND INSULATION INCLUDING FLAME SPREAD AND
 SMOKE DEVELOPED FOR THE APPLICABLE CONSTRUCTION
 CONDITIONS.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2) THE VALUE FOR THE WORK STATED ON THE APPLICATION
 APPEARS TO BE LOW. PLEASE SUBMIT AN ITEMIZED COST
 BREAKDOWN FOR ALL OF THE PROPOSED WORK. BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC
 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By mpeterso Date 2023-04-05 Time 15:37 Rev Time 0.00
Received By mpeterso Date 2023-04-05 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 14:10 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 14:10 Sent To  
Notes
2022-10-06 14:11:02SEE SIGNATURE REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By pleduc Date 2023-03-27 Time   Rev Time 0.00
Received By pleduc Date 2023-03-27 Time 11:10 Sent To  
Notes
2023-03-27 11:11:10FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-16 Cont ID  
Sent By pleduc Date 2022-09-16 Time   Rev Time 0.00
Received By pleduc Date 2022-09-16 Time 11:18 Sent To  
Notes
2022-09-16 11:18:46FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-07 Cont ID  
Sent By rmcdouga Date 2023-04-07 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2023-03-26 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2022-09-15 Time 15:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 11:58 Rev Time 0.00
Received By rmcdouga Date 2022-10-27 Time 11:19 Sent To  
Notes
2022-10-27 11:59:47NO ADDED LIVING SPACE AND NO CHANGE OF OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By medwards Date 2023-03-27 Time 09:13 Rev Time 0.00
Received By medwards Date 2023-03-27 Time 09:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 05:40 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 05:40 Sent To  
Notes
2022-09-20 05:41:071ST REVIEW FMC
 PERMIT: 22080984
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION SUBMITTED FOR THIS PROJECT IS FOR A
 DEMO PERMIT. THE DOCUMENTS SUBMITTED APPEAR TO BE FOR
 THE COMPLETE REMODEL OF THIS RESIDENCE. PLEASE EITHER
 RESUBMIT THE CORRECTED PERMIT APPLICATION OR ONLY
 SUBMIT DOCUMENTS ASSOCIATED WITH THE DEMO OF THIS
 PROJECT. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By ccole Date 2023-03-27 Time 11:11 Rev Time 0.00
Received By ccole Date 2023-03-27 Time 10:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-26 Cont ID  
Sent By ccole Date 2022-09-26 Time 14:01 Rev Time 0.00
Received By ccole Date 2022-09-26 Time 12:35 Sent To  
Notes
2022-09-26 14:02:371ST REVIEW FBC-2020 PLUMBING
 PERMIT-22080984
 9/26/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.1: THE REPLACED AND RELOCATED PLUMBING
 FIXTURES ARE LABELED AS EXISTING, PLEASE CORRECT- SEC.
 107.2.1 WPB.
  
 2) P.1: IT APPEARS THE MASTER BATHROOM ISOMETRIC IS
 LABELED ???SHOWERS???. PLEASE LABEL THE ISOMETRIC
 CORRECTLY AND INCLUDE THE LAVATORY PIPING- SEC.
 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By mpeterso Date 2023-04-05 Time 15:37 Rev Time 0.00
Received By mpeterso Date 2023-04-05 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 14:11 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 14:11 Sent To  
Notes
2022-10-06 14:13:10SIGNATURE REVIEW FAILED
  
 ALL PLANS REVIEWED USING BLUEBEAM AND ADOBE SOFTWARE
 DETAIL AN INVALDID DIGITAL SIGNATURE. PLEASE CORRECT AS
 OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  