Plan Review Details - Permit 22080961
Plan Review Stops For Permit 22080961
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-19 Cont ID  
Sent By cpuell Date 2022-09-19 Time 12:53 Rev Time 0.00
Received By cpuell Date 2022-09-19 Time 12:53 Sent To  
Notes
2022-09-19 12:53:19ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 10:49 Rev Time 0.00
Received By jgomez Date 2022-12-27 Time 10:48 Sent To  
Notes
2022-12-27 10:49:47BUILDING REVIEW APPROVED WITH PROVISO
 1-LOT DRAINAGE: CONTRACTOR TO COORDINATE WITH RETAINING
 WALL PERMIT #22120731.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-12-22 Cont ID  
Sent By jgomez Date 2022-12-22 Time 09:47 Rev Time 0.00
Received By jgomez Date 2022-12-22 Time 08:51 Sent To  
Notes
2022-12-22 09:47:38BUILDING REVIEW APPROVED WITH PROVISO
 (NOTE: SUBMIT FOR REVIEW BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
  
 1-LOT DRAINAGE: CONTRACTOR TO COORDINATE WITH RETAINING
 WALL PERMIT #22120731.
  
 2- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. NEED TO REVISE SHEET E-1 SHOWING THE LIVING
 ROOM CEILING FAN AND SIZE. ALSO, REVISE MASTER BEDROOM
 AND STUDY ROOM CEILING FAN SIZE TO COMPLY WITH TABLE
 R405.7.6 FBC-ENERGY CONSERVATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-21 Cont ID  
Sent By jgomez Date 2022-12-21 Time 14:53 Rev Time 0.00
Received By jgomez Date 2022-12-21 Time 14:15 Sent To  
Notes
2022-12-21 14:54:02NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT # 22080961
 606 59TH ST.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
 1-LOT DRAINAGE PROVISO:
 CONTRACTOR TO COORDINATE WITH RETAINING WALL PERMIT
 #22120731.
  
 2- ENERGY CALCULATIONS:
 A)OK.
 B)OK.
 C)OK.
 D)OK.
  
 PREVIOUS COMMENT:
 E)ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL
 ROOMS AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION.
 ALSO, NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW
 COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION.
 NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON
 ROOM SIZE.
  
 RESPONSE TO REVISED PLAN E-1 UPLOADED ON 12/20/22:
 REVISED ELECTRICAL PLAN IS MISSING THE LIVING ROOM
 CEILING FAN AND SIZE.
 ALSO, MASTER BEDROOM AND STUDY ROOM SPECIFIED CEILING
 FAN SIZE DOESN'T COMPLY WITH TABLE R405.7.6 FBC-ENERGY
 CONSERVATION. REVISE PLAN AS REQUIRED.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-13 Cont ID  
Sent By jgomez Date 2022-12-13 Time 13:33 Rev Time 0.00
Received By jgomez Date 2022-12-13 Time 12:20 Sent To  
Notes
2022-12-13 13:34:04NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT # 22080961
 606 59TH ST.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
 ***IMPORTANT
 CONTRACTOR TO SUBMIT PERMIT APPLICATION AND DETAILS AND
 SURVEY FOR DRAINAGE RETAINING WALL TO ALLOW FOR
 BUILDING PROVISO.
  
  
 ORIGINAL COMMENT:
 1-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE
 IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT
 PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY
 AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 PROPOSED DRAINAGE PLAN SPECIFIES A RETAINING WALL ON
 THE WEST SIDE. A SEPARATE PERMIT IS REQUIRED FOR THE
 CONSTRUCTION OF THIS WALL. PROVIDE COMPLETE STRUCTURAL
 DETAILS/SPECIFICATIONS UNDER A SEPARATE PERMIT. SEC.
 R301.1 FBC-RESIDENTIAL. SEC. 105.1 CITY AMENDMENTS.
  
 2- ENERGY CALCULATIONS:
 A)OK.
 B)OK.
 C)OK.
 D)OK.
  
 ORIGINAL COMMENT:
 E)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT.
 PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS.
 REVISE AS REQUIRED OR ENGINEER OF RECORD TO REVISE
 PLANS SHOWING COMPLIANCE WITH THIS SECTION. SEC.
 R405.7.6 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL ROOMS
 AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION. ALSO,
 NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW
 COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION.
 NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON
 ROOM SIZE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jgomez Date 2022-10-25 Time 14:40 Rev Time 0.00
Received By jgomez Date 2022-10-25 Time 12:50 Sent To  
Notes
2022-10-25 14:40:34NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT # 22080961
 606 59TH ST.
  
 1-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE
 IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT
 PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY
 AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- ENERGY CALCULATIONS:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED CORRECT BUILDER'S NAME. NEED TO SPECIFY
 PERMIT OFFICE AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)NUMBER OF BEDROOMS IS INCORRECT. REVISE AS REQUIRED.
 SECTION R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)SIZE OF HOT WATER HEATER DOESN'T MATCH PLANS. REVISE
 AS REQUIRED. SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT.
 PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS.
 REVISE AS REQUIRED OR ENGINEER OF RECORD TO REVISE
 PLANS SHOWING COMPLIANCE WITH THIS SECTION. SEC.
 R405.7.6 FBC-ENERGY CONSERVATION.
  
 F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION UPDATED TO $265,636. OWES
 $4913.37.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-01-05 Cont ID  
Sent By mpeterso Date 2023-01-05 Time 11:15 Rev Time 0.00
Received By mpeterso Date 2023-01-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-12-22 Cont ID  
Sent By mpeterso Date 2022-12-22 Time 10:01 Rev Time 0.00
Received By mpeterso Date 2022-12-22 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-02 Cont ID  
Sent By mpeterso Date 2022-12-02 Time 14:51 Rev Time 0.00
Received By mpeterso Date 2022-12-02 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-12 Cont ID  
Sent By mpeterso Date 2022-10-12 Time 15:47 Rev Time 0.00
Received By mpeterso Date 2022-10-12 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-05 Cont ID  
Sent By mpeterso Date 2023-01-05 Time 11:16 Rev Time 0.00
Received By mpeterso Date 2022-12-20 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-14 Cont ID  
Sent By asangele Date 2022-12-14 Time 15:21 Rev Time 0.00
Received By asangele Date 2022-12-14 Time 15:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-25 Cont ID  
Sent By jgomez Date 2022-10-25 Time 15:03 Rev Time 0.00
Received By jgomez Date 2022-09-19 Time 08:17 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-01-04 Cont ID  
Sent By aoliver Date 2023-01-04 Time 08:33 Rev Time 0.00
Received By lmarchan Date 2022-12-22 Time 09:55 Sent To  
Notes
2023-01-03 11:16:42RECEIPT MU-2022-056900-0000 - $4,133.44 PAID AO
2022-12-22 09:56:10IMPACT FEE QUEST UPLOADED. PBCGOV EMAILED PER JG AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jgomez Date 2022-10-25 Time 15:01 Rev Time 0.00
Received By jgomez Date 2022-10-25 Time 14:59 Sent To  
Notes
2022-10-25 15:02:06IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 06:41 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 06:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-09-26 Cont ID  
Sent By rwbrown Date 2022-09-26 Time 13:54 Rev Time 0.00
Received By rwbrown Date 2022-09-26 Time 13:54 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-01-17 Cont ID  
Sent By dbattles Date 2023-01-17 Time 15:04 Rev Time 0.00
Received By dbattles Date 2023-01-17 Time 15:04 Sent To  
Notes
2023-01-17 15:04:33PRIVATE PROVIDER INSPECTIONS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-10-25 Cont ID  
Sent By jgomez Date 2022-10-25 Time 15:02 Rev Time 0.00
Received By jgomez Date 2022-10-25 Time 15:02 Sent To  
Notes
2022-10-25 15:03:03SHINGLES NOA 18-0215.01.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-21 Cont ID  
Sent By jgomez Date 2022-12-21 Time 15:58 Rev Time 0.00
Received By jgomez Date 2022-12-21 Time 15:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-02 Cont ID  
Sent By mpeterso Date 2022-12-02 Time 14:52 Rev Time 0.00
Received By mpeterso Date 2022-12-02 Time 14:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-25 Cont ID  
Sent By jgomez Date 2022-10-25 Time 10:07 Rev Time 0.00
Received By jgomez Date 2022-10-25 Time 10:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-12-29 Cont ID  
Sent By asangele Date 2022-12-29 Time 11:29 Rev Time 0.00
Received By asangele Date 2022-12-29 Time 11:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By asangele Date 2022-12-14 Time 15:21 Rev Time 0.00
Received By asangele Date 2022-12-14 Time 15:21 Sent To  
Notes
2022-12-14 15:22:28FAILED
 12/14/2022
  
 PLEASE ADDRESS PREVIOUS COMMENT MADE.
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By asangele Date 2022-09-22 Time 10:50 Rev Time 0.00
Received By asangele Date 2022-09-22 Time 10:50 Sent To  
Notes
2022-09-22 10:54:23FAILED
 9/22/2022
  
 NEW CONSTRUCTION ARE REQUIRED TO HAVE A LANDSCAPE
 PERMIT,
  
 PLEASE REACH OUT TO EITHER SMITH OR RAY ARE LANDSCAPE
 PLANNERS
  
 RAY: 561-822-1462
 SMITH: 561-822-1562
  
 SEPARATE PERMIT ALSO REQUIRED FOR
  
 DRIVEWAY
 MECHANICAL EQUIPMENT
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]