Plan Review Stops For Permit 22080961 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-09-19 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-09-19 |
Time |
12:53 |
Sent To |
|
|
Notes |
2022-09-19 12:53:19 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2022-12-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-27 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-27 |
Time |
10:48 |
Sent To |
|
|
Notes |
2022-12-27 10:49:47 | BUILDING REVIEW APPROVED WITH PROVISO | | 1-LOT DRAINAGE: CONTRACTOR TO COORDINATE WITH RETAINING | | WALL PERMIT #22120731. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-22 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-22 |
Time |
08:51 |
Sent To |
|
|
Notes |
2022-12-22 09:47:38 | BUILDING REVIEW APPROVED WITH PROVISO | | (NOTE: SUBMIT FOR REVIEW BEFORE INSPECTIONS TO AVOID | | CONFLICTS/DELAYS): | | | | 1-LOT DRAINAGE: CONTRACTOR TO COORDINATE WITH RETAINING | | WALL PERMIT #22120731. | | | | 2- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN | | CREDIT. NEED TO REVISE SHEET E-1 SHOWING THE LIVING | | ROOM CEILING FAN AND SIZE. ALSO, REVISE MASTER BEDROOM | | AND STUDY ROOM CEILING FAN SIZE TO COMPLY WITH TABLE | | R405.7.6 FBC-ENERGY CONSERVATION. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-21 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-21 |
Time |
14:15 |
Sent To |
|
|
Notes |
2022-12-21 14:54:02 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT # 22080961 | | 606 59TH ST. | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | CONFLICTS/DELAYS. REVISION FEES APPLY. | | | | ***IMPORTANT | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | BEFORE PERMIT ISSUANCE. | | | | 1-LOT DRAINAGE PROVISO: | | CONTRACTOR TO COORDINATE WITH RETAINING WALL PERMIT | | #22120731. | | | | 2- ENERGY CALCULATIONS: | | A)OK. | | B)OK. | | C)OK. | | D)OK. | | | | PREVIOUS COMMENT: | | E)ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL | | ROOMS AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION. | | ALSO, NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW | | COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION. | | NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON | | ROOM SIZE. | | | | RESPONSE TO REVISED PLAN E-1 UPLOADED ON 12/20/22: | | REVISED ELECTRICAL PLAN IS MISSING THE LIVING ROOM | | CEILING FAN AND SIZE. | | ALSO, MASTER BEDROOM AND STUDY ROOM SPECIFIED CEILING | | FAN SIZE DOESN'T COMPLY WITH TABLE R405.7.6 FBC-ENERGY | | CONSERVATION. REVISE PLAN AS REQUIRED. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-13 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-13 |
Time |
12:20 |
Sent To |
|
|
Notes |
2022-12-13 13:34:04 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT # 22080961 | | 606 59TH ST. | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | CONFLICTS/DELAYS. REVISION FEES APPLY. | | | | ***IMPORTANT | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | BEFORE PERMIT ISSUANCE. | | | | ***IMPORTANT | | CONTRACTOR TO SUBMIT PERMIT APPLICATION AND DETAILS AND | | SURVEY FOR DRAINAGE RETAINING WALL TO ALLOW FOR | | BUILDING PROVISO. | | | | | | ORIGINAL COMMENT: | | 1-LOT DRAINAGE | | PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE | | IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT | | PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE | | WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. | | SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY | | AMENDMENTS. | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | ADJACENT PROPERTIES. | | | | RESPONSE: | | PROPOSED DRAINAGE PLAN SPECIFIES A RETAINING WALL ON | | THE WEST SIDE. A SEPARATE PERMIT IS REQUIRED FOR THE | | CONSTRUCTION OF THIS WALL. PROVIDE COMPLETE STRUCTURAL | | DETAILS/SPECIFICATIONS UNDER A SEPARATE PERMIT. SEC. | | R301.1 FBC-RESIDENTIAL. SEC. 105.1 CITY AMENDMENTS. | | | | 2- ENERGY CALCULATIONS: | | A)OK. | | B)OK. | | C)OK. | | D)OK. | | | | ORIGINAL COMMENT: | | E)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT. | | PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS. | | REVISE AS REQUIRED OR ENGINEER OF RECORD TO REVISE | | PLANS SHOWING COMPLIANCE WITH THIS SECTION. SEC. | | R405.7.6 FBC-ENERGY CONSERVATION. | | | | RESPONSE: | | ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL ROOMS | | AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION. ALSO, | | NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW | | COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION. | | NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON | | ROOM SIZE. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-10-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-25 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-25 |
Time |
12:50 |
Sent To |
|
|
Notes |
2022-10-25 14:40:34 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT # 22080961 | | 606 59TH ST. | | | | 1-LOT DRAINAGE | | PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE | | IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT | | PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE | | WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. | | SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY | | AMENDMENTS. | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | ADJACENT PROPERTIES. | | | | 2- ENERGY CALCULATIONS: | | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM | | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS | | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO | | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF | | FORM. NEED CORRECT BUILDER'S NAME. NEED TO SPECIFY | | PERMIT OFFICE AND JURISDICTION NUMBER (THIS | | JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | C)NUMBER OF BEDROOMS IS INCORRECT. REVISE AS REQUIRED. | | SECTION R103.1.1.2 FBC-ENERGY CONSERVATION. | | | | D)SIZE OF HOT WATER HEATER DOESN'T MATCH PLANS. REVISE | | AS REQUIRED. SECTION R103.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | E)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT. | | PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS. | | REVISE AS REQUIRED OR ENGINEER OF RECORD TO REVISE | | PLANS SHOWING COMPLIANCE WITH THIS SECTION. SEC. | | R405.7.6 FBC-ENERGY CONSERVATION. | | | | F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY | | CONSERVATION. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | AMENDMENTS. VALUATION UPDATED TO $265,636. OWES | | $4913.37. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-01-05 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-01-05 |
Time |
11:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-12-22 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-12-22 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-12-02 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-12-02 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-10-12 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-10-12 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-01-05 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-01-05 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-12-20 |
Time |
16:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-14 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-12-14 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-12-14 |
Time |
15:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-10-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-25 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-09-19 |
Time |
08:17 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2023-01-04 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-01-04 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-12-22 |
Time |
09:55 |
Sent To |
|
|
Notes |
2023-01-03 11:16:42 | RECEIPT MU-2022-056900-0000 - $4,133.44 PAID AO | 2022-12-22 09:56:10 | IMPACT FEE QUEST UPLOADED. PBCGOV EMAILED PER JG AO |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2022-10-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-25 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-25 |
Time |
14:59 |
Sent To |
|
|
Notes |
2022-10-25 15:02:06 | IMPACT FEES | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | IMPACT FEE ASSESSMENT. | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2022-09-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-09-21 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-09-21 |
Time |
06:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-09-26 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2023-01-17 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2023-01-17 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2023-01-17 |
Time |
15:04 |
Sent To |
|
|
Notes |
2023-01-17 15:04:33 | PRIVATE PROVIDER INSPECTIONS |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2022-10-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-25 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-25 |
Time |
15:02 |
Sent To |
|
|
Notes |
2022-10-25 15:03:03 | SHINGLES NOA 18-0215.01. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-12-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-21 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-21 |
Time |
15:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-12-02 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-12-02 |
Time |
14:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-10-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-25 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-25 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-12-29 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-12-29 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-12-29 |
Time |
11:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2022-12-14 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-12-14 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-12-14 |
Time |
15:21 |
Sent To |
|
|
Notes |
2022-12-14 15:22:28 | FAILED | | 12/14/2022 | | | | PLEASE ADDRESS PREVIOUS COMMENT MADE. | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-09-22 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-09-22 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-09-22 |
Time |
10:50 |
Sent To |
|
|
Notes |
2022-09-22 10:54:23 | FAILED | | 9/22/2022 | | | | NEW CONSTRUCTION ARE REQUIRED TO HAVE A LANDSCAPE | | PERMIT, | | | | PLEASE REACH OUT TO EITHER SMITH OR RAY ARE LANDSCAPE | | PLANNERS | | | | RAY: 561-822-1462 | | SMITH: 561-822-1562 | | | | SEPARATE PERMIT ALSO REQUIRED FOR | | | | DRIVEWAY | | MECHANICAL EQUIPMENT | | | | | | | | ALEXIS SANGELEER | | ASSOCIATE PLANNER | | [email protected] |
|
|