Plan Review Stops For Permit 22080953 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2022-12-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-12-12 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-12-12 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-11-08 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-11-08 |
Time |
13:35 |
Sent To |
|
|
Notes |
2022-11-08 13:40:02 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-5.2 PLEASE SHOW THE GRAB BAR DETAILS FOR | | THE ADDED SHOWER PER FBC A 213.2 TOILET ROOMS AND | | BATHING ROOMS. WHERE BATHING ROOMS ARE PROVIDED, EACH | | BATHING ROOM SHALL COMPLY WITH 603. | | | | 2) GRAB BAR HEIGHT SHOWN ON DRAWING A-5.2 MAXIMUM | | HEIGHT SHOULD BE TO THE TOP OF THE GRIPPING SURFACE PER | | FBC A 609.4POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-09-02 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-09-02 |
Time |
12:45 |
Sent To |
|
|
Notes |
2022-09-02 12:50:40 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) REVISION SHOWS A RESTROOM WITH A SHOWER ADDED TO A | | GROUND FLOOR OFFICE - PLEASE SHOW THE RESTROOM WITH | | SHOWER ACCESSIBLE DETAILS (FLOOR SPACE, GRAB BAR ETC.) | | PER FBC 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE | | TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL | | COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH | | BATHING ROOM SHALL COMPLY WITH 603. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-12-19 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-12-19 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-11-21 |
Time |
15:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-09-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-09-26 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-09-21 |
Time |
15:22 |
Sent To |
|
|
Notes |
2022-09-26 10:43:56 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | FIRE ALARM REVISION TO BE DONE ON A FIRE ALARM PLAN AND | | PERMIT. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-10-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-10-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-10-27 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-08-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-08-24 |
Time |
11:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-12-16 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-12-05 |
Time |
09:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-11-21 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-10-26 |
Time |
07:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-10-03 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-10-03 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-08-22 |
Time |
08:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-12-16 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-12-16 |
Time |
15:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2022-11-14 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-11-14 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-11-14 |
Time |
13:37 |
Sent To |
|
|
Notes |
2022-11-14 13:37:27 | 2ND REVIEW FMC | | PERMIT: 22080953 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) A REVISED SHEET M-2.1B SHOWING THAT NOTE 15 WAS | | DELETED WAS NOT SUBMITTED IN THIS LATEST SUBMITTAL. | | PLEASE PROVIDE THE REVISED M-2.1B SHOWING NOTE 15 | | DELETED. | | | | 2) PLEASE SHOW WHERE AHU-7 IS LOCATED, WHICH SHEET? I | | CANNOT FIND IT ANYWHERE IN THIS SUBMITTAL, OTHER THAN | | ON SHEET M7.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-09-01 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-09-01 |
Time |
07:10 |
Sent To |
|
|
Notes |
2022-09-01 07:11:00 | 1ST REVIEW FMC | | PERMIT: 22080953 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) MEP NARRATIVE LISTS SHEET M-2.1A, THERE IS NO SUCH | | SHEET SUBMITTED IN THIS SUBMITTAL. | | | | 2) SHEET M-2.1B: THERE IS A NEW 2 INCH VENT PIPE FOR | | TANK ON THIS REVISED DRAWING BUT NOTHING TO EXPLAIN | | WHAT IT IS FOR. PROVIDE AN EXPLANATION. FBC 107.3.5 | | | | 3) SHEET M-2.1B: EXPLAIN NOTE 15. FBC 107.3.5 | | | | 4) SHEET M-4.2 WAS SUBMITTED BUT NO NARRATIVE WAS | | SUBMITTED EXPLAINING THE CHANGES. PLEASE SUBMIT A | | NARRATIVE FOR THIS SHEET. | | | | 5) SHEET M-5.2: IT APPEARS THAT A NEW ROOM WAS ADDED. | | PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL | | EQUIPMENT SIZING CALCULATIONS ALONG WITH THE EQUIPMENT | | SCHEDULE FOR THIS NEW ROOM. FBC 107.3.5 | | | | 6) SHEET M-5.2: THE DOTTED AREA AT THE BOTTOM LEFT OF | | THE DRAWING INDICATES TO REFER TO SHEET M-2.2A AND | | M-5.3 FOR HVAC LAYOUT IN THIS AREA. NEITHER SHEET HAS | | THIS DETAIL. PLEASE SHOW WHICH DRAWING SHOWS THIS | | INFORMATION. FBC 107.3.5 | | | | 7) SHEET M-7.1: IN THE COMMON AREA SPLIT SYSTEM | | SCHEDULE THE NEW AHU-7 IS LISTED FOR AN OFFICE, THIS | | NEW UNIT IS FOR THE NEW ROOM THAT IS LISTED ON SHEET | | M-5.2 AS PART OF THE CLUB HOUSE SEATING AREA. PROVIDE | | ACCURATE INFORMATION ABOUT THIS NEW UNIT. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2022-12-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-12-12 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-12-12 |
Time |
07:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2022-11-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-11-04 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-11-04 |
Time |
12:06 |
Sent To |
|
|
Notes |
2022-11-04 14:05:30 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 22080953 | | 11/4/2022 | | | | CODES IN EFFECT: | | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) A-5.2: THE ARCHITECT HAS DESIGNED A NEW ACCESSIBLE | | OFFICE BATHROOM WITH ACCESSIBLE FIXTURES WITH THE | | EXCEPTION OF PROVIDING GRAB BARS IN THE ROLL-IN SHOWER | | WHICH HE STATES IS A SHOWER FOR PRIVATE USE. EXCEPTION | | 1 UNDER SEC. 608.3 ALLOWS GRAB BAR REINFORCEMENT TO BE | | INSTALLED IN THE SHOWER ONLY FOR SINGLE OCCUPANT | | THROUGH A PRIVATE OFFICE, HOWEVER THE PLANS SHOW THE | | ENTRANCE FROM A COMMON USE AREA THAT APPEARS TO BE A | | BREAKROOM. PLEASE PROVIDE THE GRAB BARS IN THE SHOWER | | AND SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS | | FOR THE SHOWER ON THE ENLARGED DRAWING- SEC. 608.2.2.1 | | FBC ACC. | | | | 2) P2.1B: THE REVISED PLAN APPEARS TO SHOW THE BOOSTER | | PUMP (BP-1) LOCATED OVER A WALL AND NOT IN THE ROOM. | | PLEASE CORRECT THE DRAWING- SEC. 107.2.1 WPB. | | | | 3) P2.1B: THE PLAN SHOWS REVISIONS TO THE FUEL TANK AND | | FUEL LINE IN THE FIRE PUMP ROOM WHICH SHALL BE DETAILED | | AND EXPLAINED IN THE MECHANICAL REVISION NARRATIVE- | | SEC. 107.2.1 WPB. | | | | 4) P2.2A: PROVIDE A THERMOSTATIC MIXING VALVE TO LIMIT | | THE TEMPERATURE OF THE HOT WATER FROM NEW THE TWH-3 TO | | THE MOP SINK- SEC. 607.1.1 FBC P. | | | | 5) P2.2.A: REFER TO SEC. 310.3 FBC P, AND SEC. 1210.2.2 | | FBC B AND INDICATE THE TYPE OF WALL SURROUND MATERIAL | | TO BE INSTALLED AT THE MOP SINK. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-08-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-08-30 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-08-30 |
Time |
13:18 |
Sent To |
|
|
Notes |
2022-08-30 15:32:32 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22080953 | | 8/30/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P-2.0A: SUBMIT ENLARGED AND DIMENSIONED | | ARCHITECTURAL PLANS AND DETAILS FOR THE NEW OFFICE | | BATHROOM SHOWING COMPLIANCE WITH THE FBC ACC WHERE | | REQUIRED- SEC. 213.1 FBC ACC, & SECS. 107.2.1 & | | 107.3.5.1.3 WPB. DETAILS REQUIRED- | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | WATER CLOSET- SEC. 604.3. | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | LAVATORY- SEC. 606.2. | | C) TURNING SPACE DIAMETERS- SEC. 304.3. | | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALLS- | | SEC. 604.2. | | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED | | FLOOR- SECTION 604.4 (SEE EXCEPTION 1). | | F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE | | FROM THE FINISHED FLOOR- SEC. 606.3 (SEE EXCEPTION 1). | | G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE | | REFLECTIVE SURFACE- SEC. 603.3 | | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4. (SEE | | EXCEPTION 1). | | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE | | 604.7. | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. | | 606.2 (SEE EXCEPTION 2). | | L) SHOWER WIDTH AND DEPTH DIMENSIONS- SEC. 608.2.2 | | M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | SHOWER- SECTION 608.2.2.1 | | N) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3.2. (SEE SEC. | | 608.3 EXCEPTION 1). | | O) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE | | SHOWER- SEC. 608.5.2. | | | | 2) P-2.0A: PROVIDE A SHOWER PAN DETAIL- SEC. 421.5.2 | | FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-08-23 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-08-23 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-12-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-12-12 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-12-12 |
Time |
08:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-11-08 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-11-08 |
Time |
14:13 |
Sent To |
|
|
Notes |
2022-11-08 14:15:25 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) DRAWINGS SP-1, A-3.1, A-5.2, M-4.2, P-2.1A, P-2.2A | | DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-11-21 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-11-21 |
Time |
15:45 |
Sent To |
|
|
Notes |
2022-11-21 15:46:16 | ELECTRICAL PAGES ARE COPIES JLEAHY | 2022-09-01 07:13:04 | MECHANICAL SHEETS- M-4.2 IS MISSING THE ORIGINAL | | DIGITAL SIGNATURE FROMTHE DESIGNER. | 2022-08-30 14:58:37 | PLUMBING SHEETS P-2.1.A & P-2.2.A HAVE COPIED DIGITAL | | SIGNATURES AND SEALS WHICH CANNOT BE VERIFIED- FL. | | STATUTE- 471.025. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2022-11-21 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2022-11-21 |
Time |
16:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2022-09-29 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2022-09-29 |
Time |
16:16 |
Sent To |
|
|
Notes |
2022-09-29 16:20:16 | 1. GROSS BUILDING AREA WAS INCREASED FROM 288,824SF TO | | 290,183SF. PROJECT DOES NOT HAVE SUFFICIENT TDRS FOR | | THE GBA INCREASE. A TDR TRANSFER WILL BE NEEDED TO | | AUTHORIZE THE ADDITIONAL SF. | | 2. THE DESIGN OF THE SOUTH ELEVATION AT THE LOBBY LEVEL | | IS SUBSTANTIALLY CHANGED FROM SITE PLAN APPROVAL OR | | MASTER PERMIT 20120712. THE GLASS TILE DESIGN CANNOT BE | | REMOVED. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|