2023-01-24 16:03:59 | RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22080253 |
| 8403 IRONHORSE CT. |
| |
| NOTE: |
| NEED TO ADDRESS THE SIGNATURE REVIEW ALSO. SEE COMENT |
| AT THE BOTTOM OF THIS PAGE. |
| |
| |
| 2- ACCORDING SHUTTERS: |
| |
| PREVIOUS COMMENT: |
| A) SHUTTERS INSTALLATION SCHEDULE SPECIFY CONCRETE AS |
| THE SUBSTRATE WHERE SHUTTERS ARE GOING TO BE INSTALLED |
| (TOP AND BOTTOM). TYPICALLY THE BOTTOM OF WINDOW |
| OPENINGS IS CONCRETE BLOCK. REVISE INSTALLATION |
| SCHEDULE USING THE ANCHOR FOR CONCRETE BLOCK SUBSTRATE |
| AT THE BOTTOM OR PROVIDE PROOF SHOWING BOTTOM OF |
| OPENINGS HAS POURED CONCRETE WITH THE STRENGTH |
| SPECIFIED ON ANCHOR SCHEDULE OF PRODUCT APPROVAL |
| SUBMITTED. |
| SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NOTE: |
| ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON |
| 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE |
| ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE |
| THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER |
| CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION |
| SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED |
| WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH |
| ACCORDING SHUTTERS. |
| THIS IS WHY THERE IS SO MUCH CONFUSION. |
| THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION |
| SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE |
| CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED |
| ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE |
| COMMENTS. |
| |
| PREVIOUS COMMENT: |
| B) REVISE SHUTTER GLASS SEPARATION SPECIFIED ON SHUTTER |
| INSTALLATION SCHEDULE FOR OPENINGS WITH A SHUTTER SPAN |
| LONGER THAN 99 INCHES. SEE SHEET 13 OF 13 OF SHUTTERS |
| PRODUCT APPROVAL AND REVISE AS REQUIRED. NEED 3-1/2 |
| INCH GLASS SEPARATION. |
| SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NOTE: |
| ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON |
| 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE |
| ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE |
| THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER |
| CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION |
| SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED |
| WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH |
| ACCORDING SHUTTERS. |
| THIS IS WHY THERE IS SO MUCH CONFUSION. |
| THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION |
| SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE |
| CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED |
| ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE |
| COMMENTS. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| SIGNATURE REVIEW: |
| |
| THOMAS J. TWOMEY P.E DWG 1 OF 1 SUBMITTED WITH FLORIDA |
| PRODUCT APPROVAL FL320-R10 NEEDS ORIGINAL |
| SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN |
| SUBMITTING FOR PUBLIC RECORDS. |
| |
| NOTE: UPLOAD THIS DRAWING IN THE DRAWINGS FOLDER. |
| |
| |
| |