Plan Review Details - Permit 22080112
Plan Review Stops For Permit 22080112
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-25 Cont ID  
Sent By ppetty Date 2022-10-25 Time 11:45 Rev Time 0.00
Received By ppetty Date 2022-10-25 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-09-07 Cont ID  
Sent By ppetty Date 2022-09-07 Time 11:23 Rev Time 0.00
Received By ppetty Date 2022-09-07 Time 08:58 Sent To  
Notes
2022-09-07 11:24:11PLEASE SEE F/D NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By pleduc Date 2022-10-21 Time   Rev Time 0.00
Received By pleduc Date 2022-10-17 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By pleduc Date 2022-08-26 Time   Rev Time 0.00
Received By pleduc Date 2022-08-19 Time 12:35 Sent To  
Notes
2022-08-19 12:30:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FA 3.001 - THERE ARE INDICATION FO FBC
 REFERENCES TO THE REQUIRMENTS OF THE COMMAND CENTER;
 HOWEVER, THEY ARE NO REFERENCES TO THE FLORIDA FIRE
 PREVENTION CODE; NFPA 1 & 101.
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
  
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
 (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE.
 (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY
 COMMAND CENTER.
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION
 OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 NFPA 101
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
  
 PLEASE REVIEW AND ENSURE EACH O THE REQUIREMENTS ARE
 MET.
  
  
 2) AS THIS IS A LARGE COMPLEX MIXED OCCUPANCY, AND TO
 ASSIST IS FIREGROUND FUNCTIONALITIES, I AM REQUESTING A
 REVIEW OF LOCATIONS FOR ANNUNCIATOR PANELS AT EACH OF
 OCCUPACNCIES.
  
 EACH OCCUPANCY SHOULD HAVE IT'S OWN SEPARATE
 ANNUNCIATOR PANEL THAT CAN FUNCTION THE SAME AS THE
 FACP, BUT CLOSER TO EACH AFFECTED AREA.
  
  
 I.E. OFFICE LOBBY, HOTEL LOBBY, RESIDENTIAL TOWER
 LOBBY, DAYCARE CENTER, PARKING PODIUM, ETC.
  
 NFPA 72
  
 10.17.3* ANNUNCIATOR ACCESS AND LOCATION.
  
 A.10.17.3 THE PRIMARY PURPOSE OF ANNUNCIATION IS TO
 ENABLE RESPONDING PERSONNEL TO QUICKLY
 AND ACCURATELY DETERMINE THE STATUS OF EQUIPMENT OR
 EMERGENCY CONTROL FUNCTIONS THAT MIGHT
 AFFECT THE SAFETY OF OCCUPANTS.
  
 10.17.3.1 ALL REQUIRED ANNUNCIATION MEANS SHALL BE
 READILY ACCESSIBLE TO RESPONDING
 PERSONNEL.
  
 10.17.3.2 ALL REQUIRED ANNUNCIATION MEANS SHALL BE
 LOCATED AS REQUIRED BY THE AUTHORITY HAV ING
 JURISDICTION TO FACILITATE AN EFFICIENT RESPONSE TO THE
 SITUATI
  
 10.17.5.3 WHERE THE SYSTEM SERVES MORE THAN ONE
 BUILDING, EACH BUILDING SHALL BE ANNUNCI ATED SEPARATEL
  
 THE LOCATIONS CAN BE COORDINATED WITH THE OFFICE OF THE
 FIRE MARSHAL.
  
 PLEASE REVIEW AND CONTACT MY OFFICE VIA EMAIL WITH PDF
 FLOOR PLANS FOR EACH AREA OR PROVIDE DETAILED PROPOSED
 FLOOR PLAN LOCATIONS ON THE RESUBMITTAL.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 07:02 Rev Time 0.00
Received By medwards Date 2022-10-14 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-07 Cont ID  
Sent By ppetty Date 2022-09-07 Time 11:36 Rev Time 0.00
Received By ppetty Date 2022-08-18 Time 06:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 07:01 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By medwards Date 2022-08-26 Time 11:20 Rev Time 0.00
Received By medwards Date 2022-08-26 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 07:01 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 07:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-07 Cont ID  
Sent By ppetty Date 2022-09-07 Time 11:36 Rev Time 0.00
Received By ppetty Date 2022-09-07 Time 11:36 Sent To  
Notes
***NONE***