Plan Review Stops For Permit 22071146 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-12-01 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-12-01 |
Time |
13:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-29 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-11-29 |
Time |
07:47 |
Sent To |
|
|
Notes |
2022-11-29 13:00:53 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS | | TO INDICATE REROOFING LOW/FLAT SLOPE AREA; IF NOT | | INDICATE BY PLACING AN X IN LOW/FLAT SLOPE AREAS; IF TO | | RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF 2020 CODE | | VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT | | ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION | | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. REVISE | | ROOF DIAGRAM/SKETCH TO INCLUDE MEAN ROOF HEIGHT(S). | | SECOND REQUEST. | | 2. PLEASE ADDRESS THE SIGNATURE REVIEW COMMENTS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-07 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-11-07 |
Time |
11:37 |
Sent To |
|
|
Notes |
2022-11-07 12:04:20 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT | | APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT | | (JOINT TAPE/STRIPS) TO BE USED. INCLUDE COVER PAGE, | | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR | | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY | | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC | | ENGINEERING. (NOA NO. 21-1207.19) | | 2. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS | | TO INDICATE REROOFING LOW/FLAT SLOPE AREA; IF NOT | | INDICATE BY PLACING AN X IN LOW/FLAT SLOPE AREAS; IF TO | | RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF 2020 CODE | | VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT | | ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION | | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. REVISE | | ROOF DIAGRAM/SKETCH TO INCLUDE MEAN ROOF HEIGHT(S). | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-07-28 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-07-28 |
Time |
07:54 |
Sent To |
|
|
Notes |
2022-07-28 09:16:28 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1 PROVIDE THE FOLLOWING ADDITIONAL | | INFORMATION FOR MIAMI-DADE COUNTY NOA NO.: 21-1207.11 | | THE PROPOSED FLAT ROOF SYSTEM TO BE USED: INSTALLATION | | INSTRUCTIONS FOR SYSTEM USED AND LIMITATIONS PAGE. ALL | | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. PROJECT | | LOCATED IN EXPOSURE C CATEGORY AREA. SIGNED AND SEALED | | ENHANCED NAILING CALCULATIONS MAY BE REQUIRED. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2022-12-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-05 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-05 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-02 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-02 |
Time |
10:53 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-01 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-11-29 |
Time |
16:54 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-11-29 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-29 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-11-18 |
Time |
07:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-11-07 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-07 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-10-31 |
Time |
17:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-28 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-07-28 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-07-28 |
Time |
05:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
6 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-05 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-05 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-02 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-02 |
Time |
10:53 |
Sent To |
|
|
Notes |
2022-12-02 10:55:35 | SIGNATURE REVIEW APPROVED WITH PROVISO BECAUSE ROOF | | LEAKS. NEED TO PROVIDE ENGINEER'S REPORT WITH ORIGINAL | | SIGNATURE (SEE BELOW) BEFORE FINAL INSPECTION. | | | | 1- ENGINEER'S INSPECTION REPORT DONE BY MOFA Y. HASSOUN | | P.E. HAVE AN ENGINEER'S SELF-CERTIFIED DIGITAL | | SIGNATURE. ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | SIGNATURE. THIRD PARTY CERTIFICATION IS REQUIRED BY FAC | | 61G15-23.004. (NOTE: ENGINEER TO CONTACT THE BOARD OF | | ENGINEER'S FOR SELF-CERTIFIED DIGITAL SIGNATURE | | QUESTIONS). | | NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH THIRD | | PARTY CERTIFIED DIGITAL SIGNATURE OR PROVIDE HARD COPY | | WITH ENGINEER'S WET SIGNATURE. | | | | ENGINEERS | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-01 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-01 |
Time |
13:53 |
Sent To |
|
|
Notes |
2022-12-01 13:59:28 | SIGNATURE REVIEW | | | | 1- ENGINEER'S INSPECTION REPORT HAVE A COPY OF THE | | ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL VERIFIABLE | | DIGITAL SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC | | RECORDS. ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL | | SIGNATURE. | | | | | | ENGINEERS | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-29 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-11-29 |
Time |
07:47 |
Sent To |
|
|
Notes |
2022-11-29 13:00:14 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | | | SUBMITTED SIGNED AND SEALED ROOF-TO-WALL MITIGATION | | LETTER IS A COPY OF A WET SIGNATURE. PLEASE UPLOAD A | | VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO | | PROJECTDOX. THIRD REQUEST. | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN | | ORIGINAL. | | PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED | | PLAN/DOCUMENT TO PROJECTDOX | | PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO | | LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH | | BUILDING DEPRTMENT. | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6656. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-11-07 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-11-07 |
Time |
11:37 |
Sent To |
|
|
Notes |
2022-11-07 12:03:52 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | | | SUBMITTED SIGNED AND SEALED ROOF-TO-WALL MITIGATION | | LETTER IS A COPY OF A WET SIGNATURE. PLEASE UPLOAD A | | VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO | | PROJECTDOX. SECOND REQUEST. | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN | | ORIGINAL. | | PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED | | PLAN/DOCUMENT TO PROJECTDOX | | PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO | | LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH | | BUILDING DEPRTMENT. | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6656. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
Sent By |
jbrooks |
Date |
2022-07-28 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
jbrooks |
Date |
2022-07-28 |
Time |
09:14 |
Sent To |
|
|
Notes |
2022-07-28 09:14:57 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | | | SUBMITTED SIGNED AND SEALED ROOF-TO-WALL MITIGATION | | LETTER IS A COPY OF A WET SIGNATURE. PLEASE UPLOAD A | | VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO PROJECTDOX | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN | | ORIGINAL. | | PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED | | PLAN/DOCUMENT TO PROJECTDOX | | PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO | | LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH | | BUILDING DEPRTMENT. | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6656. | | |
|
|