Plan Review Details - Permit 22071045
Plan Review Stops For Permit 22071045
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 06:56 Rev Time 0.00
Received By rmcdouga Date 2022-08-29 Time 06:56 Sent To  
Notes
2022-08-29 08:40:16FBC-R4501.19 FINAL ELECTRICAL AND BARRIER CODE
 INSPECTION SHALL BE COMPLETED PRIOR TO FILLING THE POOL
 WITH WATER.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By ppetty Date 2022-09-15 Time 09:54 Rev Time 0.00
Received By ppetty Date 2022-09-15 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-07 Cont ID  
Sent By jleahy Date 2022-08-07 Time 18:34 Rev Time 0.00
Received By jleahy Date 2022-08-07 Time 18:32 Sent To  
Notes
2022-08-07 18:35:12PLEASE PROVIDE A LOAD CALCULATION FOR THE ADDITIONAL
 LOADS 215.5 JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-15 Cont ID  
Sent By ppetty Date 2022-09-15 Time 09:54 Rev Time 0.00
Received By ppetty Date 2022-08-29 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2022-07-27 Time 08:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By ccole Date 2022-09-07 Time 15:10 Rev Time 0.00
Received By ccole Date 2022-09-07 Time 15:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 08:52 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 08:12 Sent To  
Notes
2022-08-01 08:53:481ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071045
 8/1/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: PROVIDE THE PUMP CURVE ON THE SHEET MARKED
 UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- SECS.
 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3
 FBC RES.
  
 2) SHEET 2: PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL
 BE INSTALLED AT THE METER TO PROTECT THE POTABLE WATER
 SERVICE- SECS. C, D, & E WPB UTILITIES CROSS CONNECTION
 MANUAL. THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE.
 A PVB BACKFLOW DEVICE IS ALSO REQUIRED FOR THE WATER
 SUPPLY PIPE TO THE AUTOFILL- SEC. P4501.9. FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By ccole Date 2022-09-07 Time 15:10 Rev Time 0.00
Received By ccole Date 2022-09-07 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 08:56 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 08:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By afowlkes Date 2022-08-01 Time 14:37 Rev Time 0.00
Received By afowlkes Date 2022-08-01 Time 14:37 Sent To  
Notes
***NONE***