Plan Review Details - Permit 22070634
Plan Review Stops For Permit 22070634
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-02-14 Cont ID  
Sent By rmcphers Date 2023-02-14 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2023-02-14 Time 09:10 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 08:33 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 08:33 Sent To  
Notes
2022-12-05 08:34:03PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcphers Date 2022-08-18 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2022-08-18 Time 15:51 Sent To  
Notes
2022-08-18 15:52:23PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-14 Cont ID  
Sent By rmcphers Date 2023-02-14 Time 08:59 Rev Time 0.00
Received By rmcphers Date 2023-02-14 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 08:16 Sent To  
Notes
2022-12-05 08:26:23BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-3 -- FIG. 604.5.1 AND FIG. 604.7 SHOW THE
 INCORRECT GRAB BAR HEIGHT - - PLEASE SHOW THE TOILET
 GRAB BAR HEIGHTS - FBC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 2) PLEASE SHOW THE SERVICE COUNTER HEIGHT AND CLEAR
 FLOOR SPACE TO COMPLY WITH FBC 904.4 SALES AND SERVICE
 COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP. 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcphers Date 2022-08-18 Time 16:29 Rev Time 0.00
Received By rmcphers Date 2022-08-18 Time 14:58 Sent To  
Notes
2022-08-18 16:25:24BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE SEATING LOCATIONS - FBC A
 226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
  
 2) DRAWING S-3 SHOWS CODE VERSION AS 2017 SHOULD BE
 2020 FBC ACCESSIBILITY
  
 3) DRAWING S-3 - PLEASE USE THE WORDS "REFLECTIVE
 SURFACE" WHEN REFERRING TO THE MIRROR DEMENSIONS FROM
 THE FLOOR. FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) PLEASE SHOW THE TOILET GRAB BAR HEIGHTS - FBC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 5) DRAWING LS-1 AND S-1 - THE "OCCUPANCY NOTES,
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND FLOOR
 SQUARE FOOTAGE" DO NOT MATCH.
  
 6) DRAWING S-1 AND LS-1 SHOW "DRAWING 1 OF 7" BUT THERE
 ARE NOT 7 DRAWINGS.
  
 7) PLEASE PROVIDE A DOOR SCHEDULE.
  
 8) PLEASE SHOW THE SERVICE COUNTER HEIGHT AND CLEAR
 FLOOR SPACE TO COMPLY WITH FBC 904.4SALES AND SERVICE
 COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 9) PLEASE SHOW THE PREVIOUS OCCUPANCY TYPE - FBC
 CHAPTER 3
  
 10) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1
  
 11) PLEASE SHOW RESTROOM WALL FINISHES TO COMPLY WITH
 FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By fgiaquin Date 2023-02-06 Time 23:33 Rev Time 0.00
Received By fgiaquin Date 2023-02-06 Time 21:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By fgiaquin Date 2022-12-07 Time 18:58 Rev Time 0.00
Received By fgiaquin Date 2022-12-06 Time 18:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-04 Cont ID  
Sent By fgiaquin Date 2022-08-04 Time   Rev Time 0.00
Received By fgiaquin Date 2022-08-04 Time 09:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-02 Cont ID  
Sent By cwalker Date 2023-02-02 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-02-02 08:35:23FIRE PROVISO COMMENTS:
  
 (1) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PERFORMED BY PROPERLY
 LICENSED AND QUALIFIED CONTRACTORS UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY EXISTING LIFE SAFETY SYSTEM
 (FIRE SPRINKLER AND/OR FIRE ALARM) SHALL BE PROTECTED
 FROM DAMAGE DURING ALL PHASES OF CONSTRUCTION.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE DURING ALL PHASES OF CONSTRUCTION.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By cwalker Date 2022-11-28 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-11-28 09:30:26FIRE PROVISO COMMENTS:
  
 (1) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PERFORMED BY PROPERLY
 LICENSED AND QUALIFIED CONTRACTORS UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY EXISTING LIFE SAFETY SYSTEM
 (FIRE SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4
 CONTINUOUS HOURS IN DURATION WILL REQUIRE THE
 IMPLEMENTATION OF A FIRE WATCH.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 DURING ALL PHASES OF CONSTRUCTION.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By cwalker Date 2022-07-21 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-21 12:59:44FIRE REVIEW COMMENTS:
  
 (1) SHEET S-1 INDICATES A BUSINESS OCCUPANCY WITH 41
 TOTAL OCCUPANCY. PER NFPA 101 THIS WOULD BE DEFINED AS
 A MERCANTILE OCCUPANCY. SHEET LS-1 INDICATES AN
 OCCUPANT LOAD OF 78, WHICH WOULD BE CLASSIFIED AS A
 PLACE OF ASSEMBLY PER NFPA. PLEASE CORRECT AND CLARIFY
 THE OCCUPANCY TYPE AND OCCUPANT LOAD CALCULATIONS SO
 THAT A PROPER CODE REVIEW MAY BE CONDUCTED. NFPA 1,
 1.14
  
 (2) THE PLAN INDICATES THE BUILDING HAS AN EXISTING
 FIRE SPRINKLER SYSTEM. THE SYSTEM MAY REQUIRE
 MODIFICATION TO PROVIDE 100% COVERAGE INCLUDING INSIDE
 THE WALK-IN COOLER. ANY AND ALL FIRE SPRINKLER WORK
 WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS.
  
 (3) PROVIDE A DOOR SCHEDULE WITH THE TYPE OF HARDWARE
 TO BE USED FROM THE SIDE OF EGRESS PER THE CORRECT
 OCCUPANCY CLASSIFICATION, INCLUDING THE WALK-IN COOLER.
  
 (4) INDICATE THE MEANS OF EGRESS FOR THE WALK-IN COOLER
 AND OCCUPIED SPACES AND INCLUDE MARKING THE MEANS OF
 EGRESS AND EMERGENCY LIGHTING FOR THE SPACE.
  
 (5) THE MECHANICAL HOOD WILL REQUIRE SEPARATE PERMIT
 SUBMITTAL AND APPROVAL.
  
 (6) THE HOOD FIRE SUPPRESSION SYSTEM WILL REQUIRE A
 SEPARATE PERMIT SUBMITTAL AND APPROVAL.
  
 (7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 (8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RESUBMITTAL OF THE ABOVE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-02-02 Cont ID  
Sent By rwbrown Date 2023-02-02 Time 11:14 Rev Time 0.00
Received By rwbrown Date 2023-02-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-12-06 Cont ID  
Sent By jesmith Date 2022-12-06 Time 13:58 Rev Time 0.00
Received By jesmith Date 2022-11-30 Time 16:24 Sent To  
Notes
2022-12-06 13:58:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070634 4065 N HAVERHILL RD # B1
  
 2ND REVIEW
  
 GAS COMMENTS: DENIED
  
  
 NEW COMMENT #1: GENERAL: THE SUBMITTED PLUMBING PLAN
 (SINGLE PAGE) IS MIXING EXISTING WITH NEW AND IS VERY
 UNCLEAR REGARDING THE MATTER; ADDITIONALLY, IT IS
 CRAMMING ALL THE INFORMATION FOR GAS AND PLUMBING ONTO
 A SINGLE PAGE. PER WPB FBC 107.2.1, TO PROVIDE CLARITY,
 PLEASE PROVIDE A SEPARATE EXISTING/DEMO PLAN, A
 SEPARATE PROPOSED PLAN AS APPLICABLE. BE PREPARED TO
 ADD PAGES AS APPLICABLE TO PROVIDE ADEQUATE
 INFORMATION.
  
  
 NEW COMMENT #2: SHOW COMPLIANCE FOR ELECTRICAL BONDING
 PER 2020 FGC 310
  
  
 1. SIGNATURES APPROVED
  
  
  
 4. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE INDICATE
 THE TYPE OF GAS (LP OR NATURAL)
 TO BE CLEAR, PLEASE NOTE NATURAL OR LP ON THE PLAN
  
  
  
 5 SECOND REQUEST: PER WPB FBC 107.2.1, WPB FBC
 107.3.5.1.5, FBC FG 301.1, INCLUDE ON THE RISER DIAGRAM
 THE FOLLOWING:
 ***A.THE LOCATION OF SHUTOFFS AND REGULATORS.
 ***B.SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN
 REGULATORS
 TO BE CLEAR, PLEASE INCLUDE SYSTEM PRESSURE BETWEEN
 METER/REGULATOR AND 9.5-13 INCH WC REGULATOR
 ***C.INCLUDE ALL PIPE LENGTHS (SEGMENTS), BTU LOADS,
 AND DISTANCES TO THE APPLIANCES THAT WERE USED TO
 CALCULATE MINIMUM PIPE SIZES USING THE SIZING TABLES
 FROM THE 2020 FBC FG 402 (INCLUDE REFERENCES TO THE
 TABLE(S) USED)
  
 TO BE CLEAR,
  
 * PROVIDE LENGTHS OF ALL PIPE SEGMENTS (VERTICAL AND
 HORIZONTAL) FROM 9.5-13 INCH WC REGULATOR TO ALL
 APPLIANCES AND OUTLETS AND FROM METER/REGULATOR TO
 9.5-13 INCH WC REGULATOR; SHOW FULL RUNOUTS TO
 APPLIANCES.
  
 *PROVIDE SIZES OF ALL SEGMENTS
  
 *CLARIFY PRESSURE OF EACH SYSTEM FROM 9.5-13 INCH WC
 REGULATOR TO ALL APPLIANCES AND OUTLETS AND FROM
 METER/REGULATOR TO 9.5-13 INCH WC REGULATOR
  
 *PROVIDE TABLES (FBC FG 402) USED IN SIZING OF THE TWO
 SYSTEMS
  
  
  
  
 6. SECOND REQUEST: PER WPB FBC 107.2.1, LABEL ON THE
 RISER DIAGRAM ALL TYPES OF GAS PIPING MATERIALS BEING
 INSTALLED. FBC FG 403.1
  
  
  
 8. SECOND REQUEST: PER WPB FBC 107.2.1, INCLUDE
 CALCULATIONS FOR COMBUSTION AIR PER 2020 FBC FG 304.1
  
  
  
 9. SECOND REQUEST: PER WPB FBC 107.2.1, WPB FBC
 107.3.5.1.5, FBC FG 301.1, PROVIDE A PLAN SHOWING THE
 PIPING DISTRIBUTION, UTILITIES METER/REGULATOR,
 EMERGENCY SHUT OFF VALVE, MP REGULATORS, LISTED
 SHUT-OFF VALVES, EACH APPLIANCE, ITS LOCATION AND
 CORRESPONDING BTU LOAD ON THE PLAN. RECONCILE PLAN VIEW
 AND RISER DIAGRAM
  
 TO BE CLEAR, A PLAN VIEW IS REQUIRED WHICH SHOWS
 *DISTRIBUTION OF GAS PIPE
 *LOCATION AND ID OF EACH APPLIANCE WITH BTU LOAD,
 *LOCATION OF METER/ REGULATOR
 *9.5-13 INCH WC REGULATOR
 *SHUT OFF VALVES
 *EMERGENCY SHUT OFF VALVE
  
  
  
  
 10. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PROVIDE
 THE DELIVERY PRESSURE FROM THE UTILITIES
 METER/REGULATOR
 PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED (AS
 SEEMS TO BE THE CASE) THE DOWNSTREAM SIDE OF THE MP
 REGULATOR IS A SECOND SYSTEM AND SHALL BE CALCULATED
 SEPARATELY.
  
 TO BE CLEAR, PROVIDE DELIVERY PRESSURE FROM UTILITIES
 METER/REGULATOR TO 9.5-13 INCH WC REGULATOR IN ADDITION
 TO PROVIDED DELIVERY PRESSURE FROM 9.5-13 INCH WC
 REGULATOR TO APPLIANCES
  
  
  
 11. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 DISTANCE FROM EACH REG TO FURTHEST POINT (PER SYSTEM)
  
 TO BE CLEAR, PROVIDE DISTANCE FROM UTILITIES
 METER/REGULATOR TO 9.5-13 INCH WC REGULATOR AND THEN
 FROM 9.5-13 INCH WC REGULATOR TO FURTHEST APPLIANCE
 CONNECTION
  
  
  
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By jesmith Date 2022-07-26 Time 16:44 Rev Time 0.00
Received By jesmith Date 2022-07-26 Time 16:43 Sent To  
Notes
2022-07-26 16:44:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070634 4065 N HAVERHILL RD # B1
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1. THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND
 GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE
 AND DATE. SEE SIGNATURES.
  
 2. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG 402.2, AND 301.3. THE INSTALLATION
 MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE
 ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1.
  
 3.PER WPB FBC 107.2.1, PLEASE HIDE ALL STICKY NOTES ON
 PDFS AS THEY INTERFERE WITH INTERPRETING THE PLANS.
  
 4. PER WPB FBC 107.2.1, PLEASE INDICATE THE TYPE OF GAS
 (LP OR NATURAL)
  
 5 PER WPB FBC 107.2.1, INCLUDE ON THE RISER DIAGRAM THE
 FOLLOWING:
 A. THE LOCATION OF SHUTOFFS AND REGULATORS.
 B. SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN
 REGULATORS
 C. INCLUDE ALL PIPE LENGTHS (SEGMENTS), BTU LOADS, AND
 DISTANCES TO THE APPLIANCES THAT WERE USED TO CALCULATE
 MINIMUM PIPE SIZES USING THE SIZING TABLES FROM THE
 2020 FGC 402 (INCLUDE REFERENCES TO THE TABLE(S) USED)
  
 6. PER WPB FBC 107.2.1, LABEL ON THE RISER DIAGRAM ALL
 TYPES OF GAS PIPING MATERIALS BEING INSTALLED 2020 FGC
 403
  
 7. PER WPB FBC 107.2.1, PROVIDE SIZE AND MATERIAL FOR
 UNDERGROUND SLEEVE; PROVIDE DETAIL(S) FOR
 TERMINATIONSINTERIOR AND EXTERIOR
  
 8.I PER WPB FBC 107.2.1, INCLUDE CALCULATIONS FOR
 COMBUSTION AIR PER 2020 FGC 304
  
 9. PER WPB FBC 107.2.1, PROVIDE A PLAN SHOWING THE
 PIPING DISTRIBUTION, UTILITIES METER/REGULATOR,
 EMERGENCY SHUT OFF VALVE, MP REGULATORS, LISTED
 SHUT-OFF VALVES, EACH APPLIANCE, ITS LOCATION AND
 CORRESPONDING BTU LOAD ON THE PLAN. RECONCILE PLAN VIEW
 AND RISER DIAGRAM
  
 10. PER WPB FBC 107.2.1, PROVIDE THE DELIVERY PRESSURE
 FROM THE UTILITIES METER/REGULATOR
 PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED (AS
 SEEMS TO BE THE CASE) THE DOWNSTREAM SIDE OF THE MP
 REGULATOR IS A SECOND SYSTEM AND SHALL BE CALCULATED
 SEPARATLY.
  
 11. PER WPB FBC 107.2.1, PROVIDE DISTANCE FROM REG TO
 FURTHEST POINT (PER SYSTEM)
  
 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR EMERGENCY
 HOOD SHUT DOWN VALVE. THE VALVE SHALL BE BELOW THE
 CEILING. UNION TO BE DOWN STREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-17.
  
 13. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE
 WITH FBC FG 409.4, 410.2(5)(6)(7).
  
 14.PER WPB FBC 107.2.1, SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR REGULATORS.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-03 Cont ID  
Sent By rwbrown Date 2023-03-03 Time 05:41 Rev Time 0.00
Received By rwbrown Date 2023-03-02 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-01 Cont ID  
Sent By rwbrown Date 2023-03-01 Time 06:03 Rev Time 0.00
Received By rwbrown Date 2023-02-24 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-14 Cont ID  
Sent By rmcphers Date 2023-02-14 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2023-02-01 Time 17:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-08 Cont ID  
Sent By aoliver Date 2022-12-08 Time 07:53 Rev Time 0.00
Received By aoliver Date 2022-11-23 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By rmcphers Date 2022-08-18 Time 16:35 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 05:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By rmcphers Date 2022-08-18 Time 16:29 Rev Time 0.00
Received By rmcphers Date 2022-08-18 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-02-03 Cont ID  
Sent By medwards Date 2023-02-03 Time 10:09 Rev Time 0.00
Received By medwards Date 2023-02-03 Time 10:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-29 Cont ID  
Sent By medwards Date 2022-11-29 Time 16:33 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 16:33 Sent To  
Notes
2022-11-29 16:33:412ND REVIEW FMC
 PERMIT: 22070634
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE MECHANICAL DRAWING TO INDICATE THAT THE
 RETURNS IN THE KITCHEN WILL COMPLY WITH FMC 601.5
 BELOW:
 601.5 RETURN AIR OPENINGS. RETURN AIR OPENINGS FOR
 HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS SHALL
 COMPLY WITH ALL OF THE FOLLOWING:
 1. OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET
 (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN
 COMBUSTION
 CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE LOCATED IN
 THE SAME ROOM OR SPACE.
  
 2) SECOND REQUEST: PROVIDE THE OUTDOOR AIR CALCULATIONS
 FOR THIS TENANT SPACE BASED ON EACH USE OF SPACE. THE
 OCCUPANCY CLASSIFICATION COLUMN OF TABLE 403.3.1.1
 SHALL BE USE. FMC 403.3.1.1
  
 3) SIDE NOTE: REMOVE THE MODEL ELES BLACK OVERLAYS FROM
 THE HOOD DRAWINGS BEFORE YOU SUBMIT THE DRAWINGS FOR
 THE SEPARATE HOOD PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By medwards Date 2022-07-26 Time 16:20 Rev Time 0.00
Received By medwards Date 2022-07-26 Time 16:20 Sent To  
Notes
2022-07-26 16:21:201ST REVIEW FMC
 PERMIT: 22070634
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 IS NOT A MECHANICAL PLAN, IT IS E-1 SHEET.
 PROVIDE THE MECHANICAL DESIGN FOR THIS PROJECT
 INCLUDING THE OUTDOOR AIR CALCULATIONS. FBC 107.2.1
  
 2) THE MECHANICAL DRAWING SHOULD ALSO SHOW A NOTE THAT
 STATES THE HOOD SYSTEM SHALL REQUIRE A SEPARATE PERMIT
 AND PLAN REVIEW.
  
 3) THE MECHANICAL DRAWING SHOULD ALSO SHOW A NOTE THAT
 STATES THE REFRIGERATION SYSTEM, WALK-IN COOLER, SHALL
 REQUIRE A SEPARATE PERMIT AND PLAN REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2023-03-03 Cont ID  
Sent By rwbrown Date 2023-03-03 Time 05:40 Rev Time 0.00
Received By rwbrown Date 2023-03-03 Time 05:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2023-03-01 Cont ID  
Sent By rwbrown Date 2023-03-01 Time 06:02 Rev Time 0.00
Received By rwbrown Date 2023-02-27 Time 08:03 Sent To  
Notes
2023-03-01 06:03:064TH PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THIS COMMENT WAS NOT ADDRESSED - THE WATER HEATER
 MUST HAVE A MIXING VALVE INSTALLED. THE WATER HEATER
 DETAIL DOES NOT SHOW ONE.
 2020 FPC 607.1.1/613.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-02-02 Cont ID  
Sent By rwbrown Date 2023-02-02 Time 10:41 Rev Time 0.00
Received By rwbrown Date 2023-02-02 Time 10:26 Sent To  
Notes
2023-02-02 11:07:063RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THIS COMMENT WAS NOT ADDRESSED - THE WATER HEATER
 MUST HAVE A MIXING VALVE INSTALLED. THE WATER HEATER
 DETAIL DOES NOT SHOW ONE.
 2020 FPC 607.1.1/613.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By jesmith Date 2022-11-30 Time 16:02 Rev Time 0.00
Received By jesmith Date 2022-11-28 Time 17:00 Sent To  
Notes
2022-11-30 16:02:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070634 4065 N HAVERHILL RD # B1
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 NEW COMMENT; GENERAL: THE SUBMITTED PLUMBING PLAN
 (SINGLE PAGE) IS MIXING EXISTING WITH NEW AND IS VERY
 UNCLEAR REGARDING THE MATTER; ADDITIONALLY, IT IS
 CRAMMING ALL THE INFORMATION FOR GAS AND PLUMBING ONTO
 A SINGLE PAGE. PER WPB FBC 107.2.1, TO PROVIDE CLARITY,
 PLEASE PROVIDE A SEPARATE EXISTING/DEMO PLAN, A
 SEPARATE PROPOSED PLAN. BR PREPARED TO ADD PAGES AS
 APPLICABLE TO PROVIDE ADEQUATE INFORMATION.
  
 1. SIGNATURES APPROVED
  
 2.THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION 'TBD' (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
 3. PARTIALLY COMPLIED: GREASE INTERCEPTOR: A SEPARATE
 PERMIT IS REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER
 THE MAIN PERMIT IS ALSO REQUIRED.
 ***E) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4.
 NEW COMMENT: CALCULATIONS FOR GREASE INTERCEPTOR SHALL
 NOT INCLUDE HAND SINKS. FBC PL 1003.2. IF MOP SINK AND
 PREP SINK DISCHARGE TO GREASY WASTE THEN THEY SHALL BE
 INCLUDED IN CALCULATIONS.
 NEW COMMENT: GREASE TRAP SUBMITTAL DOES NOT INDICATE
 THE SIZE OF THE INTERCEPTOR TO BE USED. PLEASE INDICATE
 THE MODEL NUMBER/SIZE ON THE SUBMITTAL. THE
 INLET/OUTLET PORTS SHALL BE SIZED TO ACCOMMODATE IN
 SIZE OF THE INLET AND OUTLET SIZE OF THE PIPING. FBC PL
 704.2
 NEW COMMENT: RISER DIAGRAM SHOWS A 2-WAY CLEANOUT
 UPSTREAM AND DOWNSTREAM OF THE INTERCEPTOR BUT THEY
 APPEAR TO BE A CROSS TEE IN THE DIAGRAM. PLEASE SHOW A
 2WAY CO TEE WITH A SMOOTH HORIZONTAL BOTTOM. A
 DEPRESSED/TRAPPED BOTTOM IS NOT ALLOWED
  
 7.SECOND REQUEST: PLAN SHEET S-3: PER FBC ACC 609.4,
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP (NOT THE CENTER) OF
 THE GRIPPING SURFACE
 REVISED DETAIL ON S-3 SHOWS 32 INCHES MAXIMUM TO
 CENTER; NOTES ON S-1 CORRECT THE SITUATION. PLEASE
 CORRECT OR ELIMINATE INCORRECT DIMENSIONS ON DETAIL.
  
 9. & 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 PLUMBING FLOOR PLAN SHOWING SANITARY AND WATER
 DISTRIBUTION. RECONCILE CONFIGURATION WITH THE RISER
 DIAGRAMS (I.E., ADDED BATHROOM IS BACK TO BACK ON FLOOR
 PLAN, RISER DIAGRAM SHOWS SIDE BY SIDE). ALL
 ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED TO WATER
 HEATER, RECIRCULATING PUMP, ETC., EXISTING AND NEW
 SHALL BE INCLUDED ON PLAN VIEW AND RISER DIAGRAMS.
 EXISTING SHALL BE NOTED AS SUCH. INCLUDE SERVICE ENTRY
 TO UNIT. SIZE ALL PIPING SEGMENTS.
 TO BE CLEAR, PLAN VIEW AND RISER DIAGRAM SHOULD REFLECT
 EACH OTHER
 ALL FIXTURES AND EQUIPMENT SHOWN ON THE PLANS REQUIRING
 CONNECTIONS SHALL BE SHOWN CONNECTED TO THE PIPING
 SYSTEMS
 NEW COMMENT: PROVIDE VTR FOR GREASY WASTE SYSTEM. FBC
 PL 904.1, 904.1.1, 904.1.2
  
 11. SECOND REQUEST: PER FBC PL 608.1, SPECIFY AND
 PROVIDE BACKFLOW PREVENTER FOR ICE MACHINES.
 TO BE CLEAR; A BFP IS REQUIRED FOR EACH ICE MACHINE.
 INDICATE THE SAME ON THE PLANS
  
 13. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 INSULATION SPECIFICATION SPEC FOR HOT WATER INSULATION
 COMPLY WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:
 ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY
 AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER
 HEATER.
  
  
 16.PARTIALLY COMPLIED: EXISTING WATER HEATER: PER WPB
 FBC 107.2.1, PROVIDE THE FOLLOWING;
 ***B) PROVIDE TEMPERATURE OF HOT WATER TO DISTRIBUTION
 ***E) WATER HEATER/RECIRC PUMP DETAIL SCHEDULE &
 DETAIL- PROVIDE DETAIL INTEGRATING WATER HEATER AND
 RECIRC PUMP; SHOW ALL VALVES AND APPURTENANCES.
 ***G) PLEASE CLARIFY MIXING VALVE AT WATER HEATER ON
 HOT WATER OUTLET.
 TO BE CLEAR, PROVIDE DETAIL FOR MIXING VALVE AND
 CONFORM TO ASSE 1017. FBC PL 607.1.1, 613.1
  
 21. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL
 FOR STEAM TABLE AND INDIRECT WASTE SHOWING COMPLIANCE
 WITH FBC PL 802.1.1.
  
 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD
 ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
 TO BE CLEAR, PROVIDE DETAIL
 NEW COMMENT: DOES THIS DRAIN CONTRIBUTE FAT, OIL OR
 GREASE (FOG) TO THE SYSTEM. IF SO, DISCHARGE THE
 RECEPTOR TO THE GREASY WASTE AND ADD TO THE
 CALCULATIONS FOR THE INTERCEPTOR. IF NOT, DISCHARGE TO
 SANITARY
  
 23. HOT WATER DISTRIBUTION IS CORRECTLY NOTED TO BE
 RECIRCULATING, BUT THERE IS NO LOOP. PER WPB FBC
 107.2.1, CLARIFY.
 TO BE CLEAR, SHOW COMPLETED LOOP
 NEW COMMENT: HOT WATER IS REQUIRED AT THE #7 MOP SINK
 AS WELL AS THE #8 PREP SINK WHICH IS NOT SHOWN IN THE
 WATER DISTRIBUTION RISER DIAGRAM. FBC PL 607.1
  
 31. SECOND REQUEST: ICE MAKER(S), HAND SINKS, STEAM
 TABLE AND SERVICE SINKS SHALL NOT DISCHARGE TO THE
 GREASY WASTE PER FBC PL 1003.2.
 TO BE CLEAR, #11 STEAM TABLE, #2 ICE MAKER DRAIN, #4
 ICE MAKER DRAIN SHALL NOT DISCHARGE TO GREASE
 INTERCEPTOR. FBC PL 1003.2. IT IS DETERMINED THE #7 MOP
 SINK (SERVICE SINK) MAY DISCHARGE TO THE GREASE
 INTERCEPTOR.
 NEW COMMENT: PROVIDE WASTE, HOT AND COLD WATER FOR #8
 PREP SINK PER FBC PL 301.3, 602.2, 607.1; IS IT A FOOD
 PREP SINK? IF SO, COMPLY WITH FBC PL 802.1.1 OR 801.1.7
 AS APPLICABLE. IF THE WASTE CONTRIBUTES FAT, OIL OR
 GREASE (FOG) WASTE RECEPTOR SHALL CONNECT TO GREASY
 WASTE. IF NOT, CONNECT RECEPTOR TO SANITARY.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By jesmith Date 2022-07-26 Time 15:14 Rev Time 0.00
Received By jesmith Date 2022-07-26 Time 08:46 Sent To  
Notes
2022-07-26 15:12:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070634 4065 N HAVERHILL RD # B1
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND
 GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE
 AND DATE. SEE SIGNATURES.
  
 2.THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION 'TBD' (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
 3. GREASE INTERCEPTOR: A SEPARATE PERMIT IS REQUIRED
 HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN PERMIT IS
 ALSO REQUIRED.
 ***A) PROVIDE AN ENLARGED PIPING DIAGRAM SHOWING THE
 LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED BY THE
 MANUFACTURER AND FBC PL 1003.9.
 ***B) PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR
 ON THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 THAT INDICATE THE LISTING AND LABELING OF THE UNIT- FBC
 PL 1003.3.5.
 ***C) PROVIDE A SITE SPECIFIC, DIMENSIONED INSTALLATION
 DIAGRAM SHOWING THE BURIAL DEPTH AND INLET AND OUTLET
 LOCATIONS, CLEAN OUT AND SAMPLING PORT LOCATIONS AND
 SIZES. PLEASE NOTE A SAMPLING PORT CONSISTING OF A
 4-INCH TWO-WAY CLEANOUT TO BE USED AS A SAMPLING PORT
 MAY BE REQUIRED. PLEASE CONTACT THE CITY OF WEST PALM
 BEACH UTILITIES DEPT. FOR ADDITIONAL REQUIRED
 INSPECTION AND TEST SAMPLING INFORMATION AND
 GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065
 OR 561-822-2274 OR EMAIL [email protected].
 ***D) PER FBC PL 305.7 & 1003.10, PLEASE SUBMIT SPECS
 FOR THE ACCESS AND LIDS.
 ***E) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4.
  
 4.PLAN SHEET S-3: ALL REFERENCES TO FLORIDA
 ACCESSIBILITY CODE SHALL BE NOTED 2020, NOT 2017 PER
 WPB FBC 107.2.1.
  
 5.PLAN SHEET S-3/TYPICAL ACCESSIBLE RESTROOM NOTE 4:
 PER FBC ACC 603.3, DIMENSION SHALL BE TO THE BOTTOM OF
 THE REFECTING SURFACE. PER WPB FBC 107.2.1, CLARIFY THE
 NOTE.
  
 6.PLAN SHEET S-3: THE SEAT HEIGHT OF A WATER CLOSET
 ABOVE THE FINISH FLOOR SHALL BE 17 INCHES (430 MM)
 MINIMUM AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE
 TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION PER FBC ACC 604.4.
  
 7.PLAN SHEET S-3: PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE
  
 8.PLAN SHEET S-1/WALL FINISHES: PER FBC 1210.2.2, FBC
 PL 310.3, WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE PER FBC 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET
 THE INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS
 USED FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 9. PER WPB FBC 107.2.1, PROVIDE PLUMBING FLOOR PLAN
 SHOWING WATER DISTRIBUTION. RECONCILE CONFIGURATION
 WITH THE RISER DIAGRAMS (I.E., ADDED BATHROOM IS BACK
 TO BACK ON FLOOR PLAN, RISER DIAGRAM SHOWS SIDE BY
 SIDE). ALL ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED
 TO WATER HEATER, RECIRCULATING PUMP, ETC., EXISTING AND
 NEW SHALL BE INCLUDED ON PLAN VIEW AND RISER DIAGRAMS.
 EXISTING SHALL BE NOTED AS SUCH. INCLUDE SERVICE ENTRY
 TO UNIT. SIZE ALL PIPING SEGMENTS.
  
 10. PER WPB FBC 107.2.1, PLUMBING FLOOR PLAN SHOWING
 SANITARY PIPING SHALL BE RECONCILED CONFIGURATIONS WITH
 THE RISER DIAGRAM (I.E., ADDED BATHROOM IS BACK TO BACK
 ON FLOOR PLAN, RISER DIAGRAM SHOWS SIDE BY SIDE). ALL
 ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED TO, GREASE
 INTERCEPTOR, FLOOR DRAINS, FLOOR SINKS, ETC., EXISTING
 AND NEW SHALL BE INCLUDED ON PLAN VIEW AND RISER
 DIAGRAMS. EXISTING SHALL BE NOTED AS SUCH. SIZE ALL
 PIPING SEGMENTS.
  
 11. PER FBC PL 608.1, SPECIFY AND PROVIDE BACKFLOW
 PREVENTER FOR ICE MACHINES.
  
 12. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR WATER, SANITARY TO INCLUDE PIPE, VALVES, FITTINGS
 AND JOINTS. COMPLY WITH FBC PL CHAPTERS 6, 7, AND 9
  
 13. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION SPEC FOR HOT WATER INSULATION COMPLY WITH
 FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:
 ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY
 AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER
 HEATER.
 ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A
 CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM.
 ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO
 RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING.
 ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A
 HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM.
 ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT
 TRACE OR IMPEDANCE HEATING).
  
 14. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 15. PER WPB FBC 107.2.1, PROVIDE NOTE ON PIPE HANGER
 DETAIL STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 16.EXISTING WATER HEATER: PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING;
 ***A) PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
 ***B) PROVIDE TEMPERATURE OF HOT WATER TO DISTRIBUTION
 ***C) PER WPB FBC 107.2.1, PROVIDE THE MANUFACTURER,
 MODEL, SIZE, SPECIFICATION AND INSTALLATION MANUAL FOR
 EXISTING WATER HEATER. BE SURE TO INDICATE STORAGE TYPE
 OR TANKLESS, GAS OR ELECTRIC.
 ***E) WATER HEATER/RECIRC PUMP DETAIL SCHEDULE &
 DETAIL- PROVIDE DETAIL INTEGRATING WATER HEATER AND
 RECIRC PUMP; SHOW ALL VALVES AND APPURTENANCES.
 ***F) PROVIDE SCHEDULE AND SPEC FOR THE RECIRC PUMP
 ***G) PLEASE CLARIFY MIXING VALVE AT WATER HEATER ON
 HOT WATER OUTLET
  
 17.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TMV (ASSE
 1070) AT LAVATORIES AND SINKS.
  
 18. WATER HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 19.PER WPB FBC 107.2.1, SHOW WATER HAMMER ARRESTORS IN
 WATER RISER.
  
 20. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THREE
 COMPARTMENT SINK AND INDIRECT WASTE SHOWING COMPLIANCE
 WITH FBC PL 802.1.
  
 21. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR STEAM TABLE
 AND INDIRECT WASTE SHOWING COMPLIANCE WITH FBC PL
 802.1.1.
  
 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD
 ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
  
 23. HOT WATER DISTRIBUTION IS CORRECTLY NOTED TO BE
 RECIRCULATING, BUT THERE IS NO LOOP. PER WPB FBC
 107.2.1, CLARIFY.
  
 24. P-1/SANITARY SLAB DETAIL: THE DETAIL SHOWS PIPE
 WITHIN THE SLAB. THE PIPING SHOULD BE IN THE SOIL
 BENEATH THE SLAB. PER WPB FBC 107.2.1, CLARIFY; PROVIDE
 A CORRECTED SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE
 TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE
 SHALL BE ONSITE FOR FINAL INSPECTION.
  
 25.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 26. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE AND
 SPEC
  
 27. PER WPB FBC 107.2.1, PROVIDE DRAIN SCHEDULE AND
 SPEC
  
 28. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE WITH
 DFU AND DRAIN SIZE/WATER SUPPLY FU AND CONNECTION SIZE
  
 29. PER WPB FBC 107.2.1, PROVIDE WATER SIZING
 CALCULATIONS
  
 30. PER WPB FBC 107.2.1, PROVIDE SANITARY SIZING
 CALCULATIONS
  
 31. ICE MAKER(S), HAND SINKS, STEAM TABLE AND SERVICE
 SINKS SHALL NOT DISCHARGE TO THE GREASY WASTE PER FBC
 PL 1003.2.
  
 32. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) RECIRCULATING PUMP
 ***C) BACKFLOW PREVENTER DEVICES
 ***D) THERMOSTATIC MIXING VALVES
 ***E)KITCHEN EQUIPMENT
  
 33. PER WPB FBC 107.2.1, PROVIDE A NOTE REQUIRING A
 SIGN TO BE DISPLAYED STATING "DRINKING WATER IS
 PROVIDED FREE OF CHARGE IN A FLAT BOTTOM GLASS/CUP"
  
 34.PER WPB FBC 107.2.1, PLEASE HIDE ALL STICKY NOTES ON
 PDFS AS THEY INTERFERE WITH INTERPRETING THE PLANS.
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-03 Cont ID  
Sent By rwbrown Date 2023-03-03 Time 05:40 Rev Time 0.00
Received By rwbrown Date 2023-03-03 Time 05:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-14 Cont ID  
Sent By rmcphers Date 2023-02-14 Time 09:07 Rev Time 0.00
Received By rmcphers Date 2023-02-14 Time 09:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 08:26 Sent To  
Notes
2022-11-30 08:21:00ELECTRONIC SIGNATURES FOR PLUMBING AND GAS PLANS ARE
 APPROVED. JS
2022-11-29 16:34:11MECHANICAL DIGITAL SIGNATURE APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcphers Date 2022-08-18 Time 16:34 Rev Time 0.00
Received By rmcphers Date 2022-08-18 Time 16:34 Sent To  
Notes
2022-08-18 16:35:20SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL SIGNED AND SEALED DRAWINGS DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-07-26 09:10:54THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND
 GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE
 AND DATE. JS

Review Stop Z ZONING
Rev No 2 Status P Date 2023-02-10 Cont ID  
Sent By VBroglia Date 2023-02-10 Time 15:54 Rev Time 0.00
Received By vbroglia Date 2023-02-10 Time 15:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-27 Cont ID  
Sent By afowlkes Date 2022-07-27 Time 15:52 Rev Time 0.00
Received By afowlkes Date 2022-07-27 Time 15:52 Sent To  
Notes
***NONE***