Plan Review Details - Permit 22070625
Plan Review Stops For Permit 22070625
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-11-22 Cont ID  
Sent By dbattles Date 2022-11-22 Time 10:03 Rev Time 0.00
Received By dbattles Date 2022-11-22 Time 10:03 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-11-07 Cont ID  
Sent By dbattles Date 2022-11-07 Time 09:06 Rev Time 0.00
Received By dbattles Date 2022-11-07 Time 09:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 11:23 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-24 11:23:50TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-11-22 Cont ID  
Sent By dbattles Date 2022-11-22 Time 10:03 Rev Time 0.00
Received By dbattles Date 2022-11-22 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-07 Cont ID  
Sent By dbattles Date 2022-11-07 Time 09:28 Rev Time 0.00
Received By dbattles Date 2022-11-07 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 11:24 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-24 11:24:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070625
 ADD: 1900 CONSULATE PL # 1404
 CONT: HRN CONTRACTORS
 TEL: 786-486-0398
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 24TH/ 2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION STATES UNDER SCOPE OF WORK:
 INTERIOR REMODEL WITH VALUE OF $15,000 DOLLARS. THE
 PLANS SHOW THE KITCHEN WITH 3 WALLS OF CABINETS AND THE
 FLOOR PLAN WITH SOUND PROOFING THROUGHOUT THE UNIT. THE
 FLOOR PLAN DOES NOT GIVE SQUARE FOOTAGE OF UNIT NOR THE
 FINISH FLOOR MATERIAL.
  
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 FLOORING VALUATION. THE PERMIT VERIFICATION OF VALUE
 COULD NOT OCCUR THIS REVIEW SINCE THE SQ. FT. AREA AND
 FLOOR PRODUCT NOR UNDERLAYMENT WERE NOT PROVIDED. 109.3
 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING OR
 ALTERATION APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDING OR ALTERATION THE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF THE ALTERATION SHALL
 BE THE TOTAL REPLACEMENT VALUE TO INCLUDE THE
 DEMOLITION, DISPOSAL OF DEBRIS, FLOOR FLASH PATCH,
 UNDERLAYMENT COST AND LABOR, THE FLOOR FINISH COST OF
 MATERIALS AND LABOR PLUS, OVERHEAD AND PROFIT.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 2C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-11-22 Cont ID  
Sent By mpeterso Date 2022-11-22 Time 10:53 Rev Time 0.00
Received By mpeterso Date 2022-11-22 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-11-07 Cont ID  
Sent By mpeterso Date 2022-11-07 Time 12:33 Rev Time 0.00
Received By mpeterso Date 2022-11-07 Time 11:50 Sent To  
Notes
2022-11-07 12:50:00ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE A ACCURATE FLOOR PLAN SHOWING
 EXISTING ELECTRICAL CONDITIONS DETAILING EXISTING
 RECEPTACLES, SWITCHES, LIGHTING AND ELECTRIC PANELS IN
 PROPOSED WORK AREAS. PROVIDE A SEPARATE PROPOSED
 ELECTRIC FLOOR PLAN DETAILING ALL NEW , MODIFIED,
 RELOCATED OR ADDED LIGHTING, RECEPTACLES, SWITCHES,
 CLEARLY SHOW ALL COUNTER SPACES, VANITY, AND APPLIANCE
 LOCATIONS. FBC 107.2
 PLEASE COMPLY WITH ALL NEC CODES INCLUDING THE
 FOLLOWING
 NEC 210.8 GFCI PROTECTION,
 NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION,
 NEC 210.52 RECEPTACLE SPACING,
 NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES,
 NEC 250.140 GROUNDING
 NEC 210.11 (C)(3) BATHROOM BRANCH CIRCUITS
 AND SMOKE/CARBON ALARMS AS PER FBC R 314
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By mpeterso Date 2022-10-25 Time 14:13 Rev Time 0.00
Received By mpeterso Date 2022-10-25 Time 14:13 Sent To  
Notes
2022-10-25 14:17:48ELECTRICAL REVIEW FAILED
 NO ELECTRIC PLAN WAS SUBMITTED. PLEASE SUBMIT
 APPROPRIATE ELECTRICAL PLAN. PLEASE ENSURE ALL NEW,
 REPAIRED, REPLACED, MODIFIED ELECTRIC WORK SHOWN ON
 PLANS COMPLY WITH APPLICABLE NATIONAL ELECTRIC CODES.
 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By cwalker Date 2022-11-22 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-11-22 10:31:18FIRE PROVISO COMMENTS:
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
  
 ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WOULD REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDING
 PAINT DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
 ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-21 Cont ID  
Sent By cwalker Date 2022-10-21 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-21 09:44:20FIRE PROVISO COMMENTS:
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
  
 ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WOULD REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDING
 PAINT DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
 ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-22 Cont ID  
Sent By mpeterso Date 2022-11-22 Time 10:53 Rev Time 0.00
Received By mpeterso Date 2022-11-22 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-21 Cont ID  
Sent By lmarchan Date 2022-11-21 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2022-11-15 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-07 Cont ID  
Sent By mpeterso Date 2022-11-07 Time 12:50 Rev Time 0.00
Received By mpeterso Date   Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-25 Cont ID  
Sent By mpeterso Date 2022-10-25 Time 14:17 Rev Time 0.00
Received By mpeterso Date 2022-10-20 Time 14:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-11-22 Cont ID  
Sent By ccole Date 2022-11-22 Time 10:35 Rev Time 0.00
Received By ccole Date 2022-11-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-07 Cont ID  
Sent By ccole Date 2022-11-07 Time 12:11 Rev Time 0.00
Received By ccole Date 2022-11-07 Time 12:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By ccole Date 2022-10-25 Time 12:15 Rev Time 0.00
Received By ccole Date 2022-10-25 Time 11:57 Sent To  
Notes
2022-10-25 12:21:081ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22070625
 10/25/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PLUMBING
 CONTRACTOR OR QUALIFIER SHALL BE ON THE PLUMBING PLAN-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-11-22 Cont ID  
Sent By dbattles Date 2022-11-22 Time 10:02 Rev Time 0.00
Received By dbattles Date 2022-11-22 Time 10:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 11:24 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***