Plan Review Details - Permit 22070617
Plan Review Stops For Permit 22070617
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-19 Cont ID  
Sent By jwitmer Date 2022-07-19 Time 13:38 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 15:40 Rev Time 0.00
Received By jleahy Date 2022-08-03 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By pleduc Date 2022-07-18 Time   Rev Time 0.00
Received By pleduc Date 2022-07-18 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2022-12-02 Cont ID  
Sent By ccole Date 2022-12-02 Time 08:11 Rev Time 0.00
Received By ccole Date 2022-11-28 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-11-17 Time   Rev Time 0.00
Received By aoliver Date 2022-11-01 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 15:40 Rev Time 0.00
Received By jleahy Date 2022-07-15 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 11:13 Rev Time 0.00
Received By medwards Date 2022-07-20 Time 11:13 Sent To  
Notes
2022-07-20 11:13:41NO MECHANICAL WORK SHOWN FOR THIS REVISION. ME

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-02 Cont ID  
Sent By ccole Date 2022-12-02 Time 08:12 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-17 Cont ID  
Sent By ccole Date 2022-11-17 Time 12:18 Rev Time 0.00
Received By ccole Date 2022-11-17 Time 10:58 Sent To  
Notes
2022-11-17 12:22:032ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22070617
 11/17/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P4 & P5: THE WATER RISER ON P5 IS MISSING THE
 SUPPLY LINES TO THE THE NEW SINKS IN THE COMPOUNDING
 ROOM AND THE WORK ROOM- SEC. 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By ccole Date 2022-07-22 Time 16:25 Rev Time 0.00
Received By ccole Date 2022-07-22 Time 14:30 Sent To  
Notes
2022-07-22 16:26:231ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22070617
 7/22/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P4 & P5: PROVIDE A PLUMBING FIXTURE SCHEDULE-
 SECS. 404, 419, 422, & 425 FBC P.
  
 2) P4 & P5: NEW SINKS IN THE WORK ROOM AND LAB ARE
 SHOWN. PLEASE CLARIFY THE USE OF THE SINKS AND WHAT THE
 CONTENT OF THE DRAINAGE WILL BE. REFER TO SEC. 803.1
 FBC P- INDIRECT WASTE RECEPTORS AND CHEMICAL DILUTION
 OR NEUTRALIZING DEVICES MAY BE REQUIRED.
  
 3) P4 & P5: HOT WATER SHALL BE DELIVERED FROM THE SINKS
 IN THE WORK ROOM AND LAB- SEC. 607.1 FBC P. THE PLANS
 INDICATE COLD WATER SUPPLY ONLY TO TWO OF THE THREE
 SINKS SHOWN IN THE LAB, AND THE WATER HEATER PIPING
 DETAIL INDICATES ONLY TEMPERED WATER SUPPLY WILL BE
 PROVIDED TO THE OTHER SINKS. PLEASE NOTE THAT TEMPERED
 WATER SHALL BE DELIVERED FROM THE LAVATORIES, HOWEVER
 HOT WATER AT A MINIMUM TEMPERATURE OF 110 DEGREES F
 SHALL BE DELIVERED FROM THE OTHER SINKS INCLUDING THE
 MOP SINK REFERENCED IN THE WATER HEATER DETAIL. PLEASE
 IDENTIFY THE MOP SINK LOCATION ON THE PLANS.
  
 4) P4 & P5: REFER TO SEC. 411.1 FBC P- IF AN EMERGENCY
 SHOWER AND EYE WASH STATION ARE REQUIRED BY OSHA OR
 OTHER GOVERNING AGENCIES, THE FIXTURES SHALL CONFORM TO
 ISEA Z358.1. IF APPLICABLE THE PLANS SHALL BE REVISED
 AND MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED.
  
 5) P4 & P5: PROVIDE EQUIPMENT SCHEDULES FOR THE
 47-GALLON STORAGE WATER HEATER AND THE TANKLESS WATER
 HEATERS SHOWN AT THE LAVATORIES- SEC. 502.1 FBC P AND
 C404.2 FBC EC.
  
 6) P4 & P5: SHOW THE MEANS OF TRAP SEAL PROTECTION FOR
 THE FLOOR DRAINS- SEC. 1002.4.1 FBC P. REFER TO COMMENT
 #2 ABOVE AND INDICATE THE CONTENT OF THE DRAINAGE BEING
 CONVEYED TO THE SANITARY SYSTEM FROM THE FLOOR DRAINS.
  
 7) P4 & P5: PROVIDE AN ENLARGED DETAIL SHOWING THE
 WATER SUPPLY CONNECTION TO THE FILTRATION EQUIPMENT AND
 LOCATION OF THE BACKFLOW PREVENTER- SEC. 608.3 FBC P.
  
 8) A3 & P4: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE OCCUPANCY IN COMPLIANCE WITH TABLE 403.1 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 BASED ON THE TABLE.
  
 9) A3 & P4: IDENTIFY THE TOILET ROOMS AS MALE, FEMALE,
 OR UNISEX- SEC. 403.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-21 Cont ID  
Sent By dbattles Date 2022-07-21 Time 12:44 Rev Time 0.00
Received By dbattles Date 2022-07-21 Time 12:44 Sent To  
Notes
2022-07-21 12:45:49DOCUMENTS UNDER MASTER 21020172

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-02 Cont ID  
Sent By ccole Date 2022-12-02 Time 08:12 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By ccole Date 2022-11-17 Time 12:23 Rev Time 0.00
Received By ccole Date 2022-11-17 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-21 Cont ID  
Sent By dbattles Date 2022-07-21 Time 12:49 Rev Time 0.00
Received By dbattles Date 2022-07-21 Time 12:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By ckimmerl Date 2022-07-25 Time 14:24 Rev Time 0.00
Received By ckimmerl Date 2022-07-25 Time 14:22 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved