Plan Review Details - Permit 22070227
Plan Review Stops For Permit 22070227
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 12:21 Rev Time 0.00
Received By shill Date 2022-09-01 Time 12:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 09:15 Rev Time 0.00
Received By shill Date 2022-08-06 Time 09:14 Sent To  
Notes
2022-08-06 09:14:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IT APPEARS THAT PROFLEX MSC90 IS PROPOSED. THE STC/IIC
 TEST USED AN 8" CONCTRETE SLAB. THEREFORE THIS BUILDING
 NEEDS TO HAVE AN 8" OR THICKER SLAB. PROVIDE
 INFORMATION HAS TO HOW THIS HAS BEEN DETERMINED OR
 PROPOSE A DIFFERENT PRODUCT THAT HAS THE TEST REPORTS
 NOTED IN PREVIOUS LIST FOR STC AND IIC. .
  
 FBC 1207
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 12:29 Rev Time 0.00
Received By shill Date 2022-07-27 Time 12:29 Sent To  
Notes
2022-07-27 12:29:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-13 Cont ID  
Sent By jleahy Date 2022-09-13 Time 16:42 Rev Time 0.00
Received By jleahy Date 2022-09-13 Time 16:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By pleduc Date 2022-08-03 Time   Rev Time 0.00
Received By pleduc Date 2022-08-03 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By pleduc Date 2022-07-12 Time   Rev Time 0.00
Received By pleduc Date 2022-07-12 Time 12:11 Sent To  
Notes
2022-07-12 12:22:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF REMOVE EXISTING FLOOR,
 HOWEVER, THERE IS NO INDICATION OF THE REPLACEMENT
 FLOOR TYPE/PRODUCT/MATERIAL.
  
 THERE IS AN INDICATION OF INSTALL NEW TILES FLOOR.
  
 THERE IS ALSO A SPEC SHEET FOR THE FLOOR UNDERLAYMENT,
 BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE ACTUAL
 PROPOSED REPLACEMENT FLOORING.
  
 TILE FLOORING CAN HAVE DIFFERENT MEANING OR DEFINITIONS
 AND CAN MANUFACTURED AROUND THE WORLD AND NOT ALL ARE
 TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS A GENERAL OUTLINE OF WHAT APPEARS TO BE A
 FLOOR AREA. IS THE NEW FLOORING PROPOSED FOR ALL AREAS
 OF THE UNIT?
  
 PER NFPA 1
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD PLEASE PROVIDE A DETAILED FLOOR
 PLAN SHOWING ALL THE PROPOSED LOCATIONS OF THE NEW
 FLOORING, WALL & DOOR LOCATIONS, KITCHEB & BATHS, ETC.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-16 Cont ID  
Sent By shill Date 2022-09-16 Time 08:51 Rev Time 0.00
Received By shill Date 2022-08-24 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 09:17 Rev Time 0.00
Received By shill Date 2022-08-02 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 12:30 Rev Time 0.00
Received By shill Date 2022-07-11 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 10:10 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 10:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 12:23 Rev Time 0.00
Received By shill Date 2022-09-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 12:29 Rev Time 0.00
Received By shill Date 2022-07-27 Time 12:29 Sent To  
Notes
***NONE***