Plan Review Details - Permit 22070178
Plan Review Stops For Permit 22070178
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2023-01-31 Cont ID  
Sent By shill Date 2023-01-31 Time 16:34 Rev Time 0.00
Received By shill Date 2023-01-31 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 10:25 Rev Time 0.00
Received By shill Date 2023-01-25 Time 10:25 Sent To  
Notes
2023-01-25 10:26:38SEE PREVIOUS LIST, #2 NOT ADDRESSED. (#3 OK)
  
 PLEASE HAVE ENGINEER CONTACT ME TO DISCUSS PRIOR TO
 RESUBMITTING. IT IS NOT CLEAR IF HE DOES NOT UNDERSTAND
 THE COMMENTS, OR IF HE DOES NOT HAVE ACCESS TO THE
 PREVIOUS FIVE COMMENT LISTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-01-03 Cont ID  
Sent By shill Date 2023-01-03 Time 07:45 Rev Time 0.00
Received By shill Date 2023-01-03 Time 07:45 Sent To  
Notes
2023-01-03 07:58:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS REVIEW NOT ADDRESSED:
  
 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION
 RELATIVE TO THE PROPERTY LINES. - 5TH REVIEW, THERE ARE
 THREE DETAILS - ECCENTRIC FOOTER FOR SITE WALL, FOOTER
 FOR SITE WALL, FOOTER FOR "ENTRY PIER DETAIL". THE SITE
 PLAN GRAPHICALLY APPEARS TO DEPICT PIERS AT THE
 PROPERTY LINE. SINCE IT IS NOT CLEAR THAT THE FOOTINGS
 WILL NOT ENCROACH THE PROPERTY LINE AS DRAWING, REVISE
 THE SITE PLAN TO SHOW DETAILS PROPOSED. IT APPEARS THAT
 AN ECCENTRIC FOOTER PIER DETAIL IS REQUIRED, OR THE
 PIER SHOULD BE SET BACK FROM THE PROPERTY LINE IN SOME
 LOCATIONS.
  
 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA. - 5TH REVIEW, PLAN WAS REVISED TO INCLUDE
 LANGUAGE CITING FBC 1616 FOR FENCES. NOTE THAT A WALL
 AND COLUMNS ARE PROPOSED (A STRUCTURE), NOT A FENCE.
 ALSO NOTE THAT THE SECTION CITED IS FOR HIGH VELOCITY
 HURRICANE ZONE WHICH INCLUDES BROWARD AND DADE COUNTIES
 ONLY. THERE ARE NO WIND REQUIREMENTS IN PALM BEACH
 COUNTY (NON-HVHZ) FOR FENCES. THE PROPOSED CONSTRUCTION
 IS NOT A FENCE, IT IS CONSIDERED A STRUCTURE, SO
 RESISTANCE TO WIND IS REQUIRED. REVISE PLAN TO CLARIFY
 WIND DESIGN CRITERIA FOR THE SITE WALL AND PIERS.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:18 Rev Time 0.00
Received By shill Date 2022-12-06 Time 10:18 Sent To  
Notes
2022-12-06 10:19:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS REVIEW NOT ADDRESSED:
  
 1. FBC 107, SUBMIT THE SURVEY FOR THIS PROPERTY. - 4TH
 REVIEW, NOT SUBMITTED.
  
 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION
 RELATIVE TO THE PROPERTY LINES. - 4TH REVIEW, NOT
 ADDRESSED.
  
 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA. - 4TH REVIEW, A STRUCTURAL DETAIL WAS
 PROVIDED BUT I'M UNABLE TO LOCATE WIND DESIGN CRITERIA.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-29 Cont ID  
Sent By shill Date 2022-10-29 Time 15:18 Rev Time 0.00
Received By shill Date 2022-10-29 Time 15:18 Sent To  
Notes
2022-10-29 15:19:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS REVIEW NOT ADDRESSED:
  
 1. FBC 107, SUBMIT THE SURVEY FOR THIS PROPERTY.
  
 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION
 RELATIVE TO THE PROPERTY LINES.
  
 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-31 Cont ID  
Sent By shill Date 2022-08-31 Time 13:02 Rev Time 0.00
Received By shill Date 2022-08-31 Time 13:02 Sent To  
Notes
2022-08-31 13:03:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS REVIEW NOT ADDRESSED:
  
 1. FBC 107, SUBMIT THE SURVEY FOR THIS PROPERTY.
  
 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION
 RELATIVE TO THE PROPERTY LINES.
  
 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA.
  
 4. THE DRAINAGE PLAN FOR THE HOUSE HAS NOT BEEN
 REVIEWED. THAT IS NOT WITHIN THE SCOPE OF THIS PERMIT.
 CLARIFY THAT FILL WILL NOT BE BROUGHT ON SITE UNDER
 THIS PERMIT, OR RESUBMIT AFTER THE HOUSE DRAINAGE PLAN
 HAS BEEN REVIEWED AND ACCEPTED, AND NOTE THAT FILL WILL
 BE BROUGHT IN UNDER THIS PERMIT (CAN BE DONE THROUGH A
 RESPONSE LETTER).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 06:16 Rev Time 0.00
Received By shill Date 2022-07-27 Time 06:15 Sent To  
Notes
2022-07-27 06:18:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SUBMIT THE SURVEY FOR THIS PROPERTY.
  
 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION
 RELATIVE TO THE PROPERTY LINES.
  
 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA.
  
 4. THE DRAINAGE PLAN FOR THE HOUSE HAS NOT BEEN
 REVIEWED. THAT IS NOT WITHIN THE SCOPE OF THIS PERMIT.
 CLARIFY THAT FILL WILL NOT BE BROUGHT ON SITE UNDER
 THIS PERMIT, OR RESUBMIT AFTER THE HOUSE DRAINAGE PLAN
 HAS BEEN REVIEWED AND ACCEPTED, AND NOTE THAT FILL WILL
 BE BROUGHT IN UNDER THIS PERMIT (CAN BE DONE THROUGH A
 RESPONSE LETTER).
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-02-01 Cont ID  
Sent By asangele Date 2023-02-01 Time 09:07 Rev Time 0.00
Received By asangele Date 2023-02-01 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 10:28 Rev Time 0.00
Received By shill Date 2023-01-18 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-06 Cont ID  
Sent By asangele Date 2023-01-06 Time 10:56 Rev Time 0.00
Received By asangele Date 2023-01-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:19 Rev Time 0.00
Received By shill Date 2022-12-01 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-29 Cont ID  
Sent By shill Date 2022-10-29 Time 15:19 Rev Time 0.00
Received By shill Date 2022-10-17 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-31 Cont ID  
Sent By shill Date 2022-08-31 Time 13:03 Rev Time 0.00
Received By shill Date 2022-08-23 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 06:18 Rev Time 0.00
Received By shill Date 2022-07-13 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 10:27 Rev Time 0.00
Received By shill Date 2023-01-25 Time 10:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-01-03 Cont ID  
Sent By shill Date 2023-01-03 Time 07:59 Rev Time 0.00
Received By shill Date 2023-01-03 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:19 Rev Time 0.00
Received By shill Date 2022-12-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-29 Cont ID  
Sent By shill Date 2022-10-29 Time 15:19 Rev Time 0.00
Received By shill Date 2022-10-29 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-31 Cont ID  
Sent By shill Date 2022-08-31 Time 13:03 Rev Time 0.00
Received By shill Date 2022-08-31 Time 13:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 06:18 Rev Time 0.00
Received By shill Date 2022-07-27 Time 06:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2023-02-01 Cont ID  
Sent By asangele Date 2023-02-01 Time 09:07 Rev Time 0.00
Received By asangele Date 2023-02-01 Time 09:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2023-01-06 Cont ID  
Sent By asangele Date 2023-01-06 Time 10:56 Rev Time 0.00
Received By asangele Date 2023-01-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-10-21 Cont ID  
Sent By asangele Date 2022-10-21 Time 10:28 Rev Time 0.00
Received By asangele Date 2022-10-21 Time 10:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By asangele Date 2022-08-29 Time 15:37 Rev Time 0.00
Received By asangele Date 2022-08-29 Time 15:37 Sent To  
Notes
2022-08-29 15:43:588/29/2022
 FAILED
  
 PLAN SUBMITTED IN THIS APPLICATION DO NOT MATCH.
  
 ARTICLE X SECTION 94-302
 WALL/FENCES CANNOT EXCEED 4FT IN HEIGHT ALONG THE FIRST
 25FT WITHIN THE FRONT SETBACK GRAY STREET
  
 ARTICLE X SECTION 94-306
 DECORATIVE FEATURES CAN ONLY EXCEED 10% OF THE DISTRICT
 HEIGHT REQUIREMENT.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By asangele Date 2022-07-19 Time 13:44 Rev Time 0.00
Received By asangele Date 2022-07-19 Time 13:44 Sent To  
Notes
2022-07-19 13:48:097/19/2022
 FAIL
 PLEASE LABEL HEIGHT OF PROPOSED SITE WALL/COLUMNS ON
 PLANS.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]