Plan Review Details - Permit 22070126
Plan Review Stops For Permit 22070126
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-07-14 Cont ID  
Sent By cpuell Date 2022-07-14 Time 09:26 Rev Time 0.00
Received By cpuell Date 2022-07-14 Time 09:26 Sent To  
Notes
2022-07-14 09:28:33INTERIOR RENO FOR ALL 16 UNITS. ADDRESSES UPDATED FROM
 3012 BROADWAY 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16 TO
 3012 BROADWAY 101,102,103,104,105,106,107,108,201,202,2
 03,204,205,206,207,208

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By cpuell Date 2022-07-12 Time 12:31 Rev Time 0.00
Received By cpuell Date 2022-07-12 Time 12:31 Sent To  
Notes
2022-07-12 12:39:3116 UNITS IN THIS BUILDING, WILL THE SCOPE OF WORK BE
 FOR ALL UNITS? CURRENTLY THE UNIT NUMBERS ARE NOT
 APPROPRIATELY NUMBERED, PLEASE HAVE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESSING ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By jwitmer Date 2022-09-07 Time 06:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By jwitmer Date 2022-08-17 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2022-08-17 Time 11:26 Sent To  
Notes
2022-08-17 14:52:37COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 09:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-27 Cont ID  
Sent By jwitmer Date 2022-09-27 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2022-09-27 Time 09:22 Sent To  
Notes
2022-09-27 11:42:13WOOD FLOOR SYSTEMS
 IIC-ESR-2540 ES FLOOR CEILING ASSEMBLIES (WOOD)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-07 Cont ID  
Sent By jwitmer Date 2022-09-07 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2022-09-07 Time 06:58 Sent To  
Notes
2022-09-07 08:07:22WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070126
 ADD: 3012 BROADWAY
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 NOTES: 1) COVERSHEET SUBMITTED DATED 7/05/2022 IS FOR
 WINDOW/DOOR PERMIT 22060734 ONLY.
 2) COVERSHEET SUBMITTED DATE 7/12/2022 R-2 RESIDENTIAL
 APARTMENT BUILDING
  
 2ND REVIEW
 DATE: WED. SEPT. 07TH/ 2022
 ACTION: DENIED
  
 COVERSHEET DATED (SUBMMITTED 7/12/2022). R2 RESIDENTIAL
 APARTMENT BUILDING, VOIDED.
 1)RESPONSE SHEET STATES: THE UNDERLAYMENT PRODUCT
 SPECIFICATIONS HAVE BEEN SUBMITTED WITH RESPONSE
 PACKAGE. SHEET C-1.
 1ST ROUND COMMENTS. DEFERRED SUBMITTALS ARE DENIED,
 SOUND ABATEMENT IS AN CODE ISSUE THAT NEEDS TO BE
 ADDRESSED BEFORE PERMIT ISSUANCE, AS PER ASSISTANT B.
 O. RICHARD GATHRIGHT. BUILDING TYPE III-V HAVE A LOWER
 FLAME SPREAD THAN TYPE I-II BUILDINGS!!!
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 2ND REQUEST. FLAME SPREAD, TYPE III-TYPE V
 CONSTRUCTION: FBC-B-2020 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2A) NOTES FOR COMPLIANCE: COVERSHEET SUBMITTAL DATE
 7/12/2022 UNDER THE LISTING OF PROJECT DATA LIST THIS
 AS A LEVEL 1 ALTERATION. PLEASE REVIEW THE SCOPING FOR
 LEVEL 2 ALTERATIONS SECTION 504.1 2020 FBC EXISTING
 BUILDING CODE. THE RECONFIGURATION OR SPACE, THE
 ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
 RECONFIGURATION OR EXTENSION OF ANY SYSTEM OR THE
 INSTALLATION OF ANY ADDITIONAL EQUIPMENT, LEVEL 2.
  
 2B) NOTES FOR COMPLIANCE: 2020 EXISTING BUILDING CODE.
 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3) SEMI-COMPLIED. RESPONSE SHEET: FIRE ALARM PULLS &
 HORN STROBES HAVE BEEN ADDED TO EACH FLOOR. THE 1ST
 FLOOR SHOWS THE FIRE ALARM PULL STATION & HORN STROBE
 BUT THE 2ND FLOOR DOES NOT HAVE THE SYMBOLS FOR THE
 PULL STATION AND HORN STROBE ONLY HP4, PLEASE UPDATE
 THE ELEC. FLOOR PLAN.
 1ST ROUND OF COMMENTS. COVERSHEET SUBMITTAL DATE
 7/12/22/ SMOKE ALARMS 703.2 IS FOR LEVEL 1. THIS IS A
 LEVEL 2 ALTERATION AND THE FIRE ALARMS NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-EXIST. CODE SECTION
 804.4.1.6.AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE FOR EXISTING GROUP R-2.
  
 4) COMPLIED, NON TRANSIENT DOES NOT NEED TO MEET
 ACCESSIBILITY OR FAIR HOUSING BUILT BEFORE MARCH13,
 1991.
  
 5) SEMI COMPLIED. 2ND REQUEST, PLEASE SHOW THE BOTTOM
 OF THE HANDRAIL AND GUARDRAIL SYSTEM, BOTTOM LANDING.
 PLEASE ALSO REVIEW SECTION 1014.16 HANDRAIL EXTENSIONS,
 PLEASE SHOW THE FULL LENGTH OF THE HANDRAIL, GUARDRAIL
 ASSEMBLY.
 1ST ROUND OF COMMENTS. SHEET A-2 SHOWS THE NEW
 GUARDRAIL / HANDRAIL SYSTEM AT 36 INCHES. 2020 EXISTING
 BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE 2020 FLORIDA BUILDING
 CODE, BUILDING. PLEASE REVIEW SECTION 1014.2 FOR THE
 HEIGHT REQUIREMENTS. PLEASE ALSO REVIEW SECTION 1014.16
 HANDRAIL EXTENSIONS, PLEASE SHOW THE FULL LENGTH OF THE
 HANDRAIL, GUARDRAIL ASSEMBLY.
  
 6) SEMI-COMPLIED, PLEASE SHOW A SIDE VIEW OF THE
 GUARDRAIL AND COMPLIANCE WITH 2020 FBC-BUILDING CODE
 SECTION 1015.4(2).
 1ST ROUND OF COMMENTS. SHEET A-2 SHOWS THE NEW
 GUARDRAIL / HANDRAIL SYSTEM AT 36 INCHES. 2020 EXISTING
 BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE 2020 FLORIDA BUILDING
 CODE, BUILDING. 2020 FBC-BUILD. CODE SECTION 1015.3
 GUARDS SHALL NOT BE LESS THAN 42 INCHES IN HEIGHT HIGH
 MEASURED VERTICALLY FROM ON STAIRWAYS FROM THE LINE
 CONNECTING THE LEADING EDGE OF THE TREAD NOSING.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.22061353
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By jwitmer Date 2022-08-17 Time 14:51 Rev Time 0.00
Received By jwitmer Date 2022-08-17 Time 11:26 Sent To  
Notes
2022-08-17 14:51:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070126
 ADD: 3012 BROADWAY
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 NOTES: 1) COVERSHEET SUBMITTED DATED 7/05/2022 IS FOR
 WINDOW/DOOR PERMIT 22060734 ONLY.
 2) COVERSHEET SUBMITTED DATE 7/12/2022 R-2 RESIDENTIAL
 APARTMENT BUILDING
  
 1ST REVIEW
 DATE: WED. AUUST 17TH/ 2022
 ACTION: DENIED
  
 COVERSHEET DATED (SUBMMITTED 7/12/2022). R2 RESIDENTIAL
 APARTMENT BUILDING:
 1) DEFERRED SUBMITTALS ARE DENIED, SOUND ABATEMENT IS
 AN CODE ISSUE THAT NEEDS TO BE ADDRESSED BEFORE PERMIT
 ISSUANCE, AS PER ASSISTANT B. O. RICHARD GATHRIGHT.
 BUILDING TYPE III-V HAVE A LOWER FLAME SPREAD THAN TYPE
 I-II BUILDINGS!!!
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD, TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2020 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2A) COVERSHEET SUBMITTAL DATE 7/12/2022 UNDER THE
 LISTING OF PROJECT DATA LIST THIS AS A LEVEL 1
 ALTERATION. PLEASE REVIEW THE SCOPING FOR LEVEL 2
 ALTERATIONS SECTION 504.1 2020 FBC EXISTING BUILDING
 CODE. THE RECONFIGURATION OR SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT, LEVEL 2.
  
 2B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3) COVERSHEET SUBMITTAL DATE 7/12/22/ SMOKE ALARMS
 703.2 IS FOR LEVEL 1. THIS IS A LEVEL 2 ALTERATION AND
 THE FIRE ALARMS NEED TO SHOW COMPLIANCE WITH THE 2020
 FBC-EXIST. CODE SECTION 804.4.1.6.AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE FOR EXISTING GROUP R-2.
  
 4) SHEET A-1:
 4A) THE 1ST FLOOR PLAN SHOWS THE END UNIT TO BE
 ACCESSIBLE, IT IS NOT CLEAR IF THE INTERIOR FLOOR LEVEL
 IS THE SAME HEIGHT AS THE CONCRETE SLAB ON THE EXTERIOR
 OR WITHIN ? INCH OF THE SAME HEIGHT. 2020 FBC-ACCESS.
 CODE CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN
 LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES,
 THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2.
  
 4B) THE FLOOR PLAN OF THE ACCESSIBLE UNIT NEEDS TO SHOW
 A ELEVATION VIEW. THE KITCHEN SINK SHOWS A FORWARD
 APPROACH BUT NOT GOING UNDER THE SINK CABINET, A SIDE
 APPROACH DOES NOT WORK SINCE THE SINK IS AGAINST THE
 WALL. 2020 ACCESS CODE 606.2 CLEAR FLOOR SPACE. 606.5
 EXPOSED PIPES AND SURFACES. 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4C) PLEASE PROVIDE ELEVATION VIEWS OF THE ACCESSIBLE
 RESTROOM TO SHOW COMPLIANCE WITH PLUMBING ELEMENTS AND
 ACCESSORIES, 2020 FBC-ACCESSIBILITY CODE CHAPTER 6.
  
 5) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM
 AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE 2020 FLORIDA BUILDING CODE, BUILDING. PLEASE
 REVIEW SECTION 1014.2 FOR THE HEIGHT REQUIREMENTS.
 PLEASE ALSO REVIEW SECTION 1014.16 HANDRAIL EXTENSIONS,
 PLEASE SHOW THE FULL LENGTH OF THE HANDRAIL, GUARDRAIL
 ASSEMBLY.
  
 6) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM
 AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE 2020 FLORIDA BUILDING CODE, BUILDING. 2020
 FBC-BUILD. CODE SECTION 1015.3 GUARDS SHALL NOT BE LESS
 THAN 42 INCHES IN HEIGHT HIGH MEASURED VERTICALLY FROM
 ON STAIRWAYS FROM THE LINE CONNECTING THE LEADING EDGE
 OF THE TREAD NOSING.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.22061353
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-10-24 Cont ID  
Sent By fgiaquin Date 2022-10-24 Time 19:12 Rev Time 0.00
Received By fgiaquin Date 2022-10-24 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-10-11 Cont ID  
Sent By fgiaquin Date 2022-10-11 Time 20:53 Rev Time 0.00
Received By fgiaquin Date 2022-10-11 Time 19:04 Sent To  
Notes
2022-10-11 20:53:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1. PER YOUR REPSONSE LETTER THE OVERHEAD SERVICE
 CONDUCTORS ARE "EXISTING". REGARDLESS THAT OVERHEAD
 SERVICE ENTRANCE CONDUCTORS ARE EXISTING YOU ARE
 PROPOSING AN INCREASED SERVICE SIZE FROM 400AMPS TO
 600AMPS. OVERHEAD SERVICE ENTRANCE CONDUCTORS AND
 CONDUIT MUST BE OF SUFFICENT SIZE. NEC 230.23A FBC
 107.2.1
  
 2. SERVICE ENTRANCE CONDUCTORS FROM METER TO SERVICE
 DISCONNECT ARE NOT OF SUFFICIENT SIZE FOR A 600AMP
 SERVICE. NEC 230.31
  
 3. NO EQUIPMENT GROUNDING CONDUCTOR PERMITTED FROM
 METER-CAN TO SERVICE DISCONNECTING MEANS. THIS IS A
 PARRALLEL PATH BACK TO THE GROUNDED CONDUCTOR (NEUTRAL)
 PLEASE REMOVE EQUIPMENT GROUND, THE EQUIPMENT GROUNDING
 CONDUCTOR ORIGINATES ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANSNEC 250.24
  
  
 4. PARALLELL CONDUCTORS TO METER CENTER (UNGROUNDED
 CONDUCTORS, GROUNDED CONDUCTORS, AND EQUIPMENT
 GROUNDING CONDUCTORS) ARE NOT OF SUFFICENT SIZE FOR
 600AMP PARALLEL FEEDERS.
 NEC 215.2 NEC 240.4 NEC 310.10H NEC 250.122
  
 5. NO OVERCURRENT PROTECTION SHOWN FOR UNIT BREAKERS ON
 METER CENTER. FBC 107.2.1
  
 6. WHAT IS METER CENTER AMPERAGE/VOLTAGE/PHASE RATING?
 FBC 107.2.1
  
 7. WHAT IS VOLTAGE AND PHASE OF SERVICE? NOT LABELED ON
 PLAN. SINGLE PHASE? THREE PHASE?
  
 8. HOUSE PANEL IS SHOWN AS 100AMPS BUT ON PANEL
 SCHEDULE IT'S SHOWN AS A 60AMP MAIN BREAKER PANEL.
 PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1
  
 9. THERE IS A BRANCH CIRCUIT FROM HOUSE PANEL THAT
 SHOWS A SINGLE #3 CU CONDUCTOR IN A 1/4'' CONDUIT???
 THERE IS NO 1/4'' CONDUIT PERMITTED AND A SINGLE #3 CU
 CONDUCTOR IS NOT A COMPLETE BRANCH CIRCUIT. PROVIDE
 CORRECTION.
  
 10. **** PREVIOUS PLAN REVIEW COMMENT SATISFIED
  
 11. WHAT WIRE TYPE IN UNITS IS BEING PROPSOED? MC?
 ROMEX? FBC 107.2.1
  
 12. SMOKE ALARMS MUST BE 3 FT AWAY FROM TIPS OF FAN
 BLADES, BATHROOM DOORS, FORCED AIR, AND 10FT AWAY FROM
 COOKING EQUIPMENT PER NFPA 72. PROVIDE CORRECTIONS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-09-14 Cont ID  
Sent By fgiaquin Date 2022-09-14 Time 20:50 Rev Time 0.00
Received By fgiaquin Date 2022-09-07 Time 19:41 Sent To  
Notes
2022-09-14 19:49:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1. PER YOUR REPSONSE LETTER THE OVERHEAD SERVICE
 CONDUCTORS ARE "EXISTING". REGARDLESS THAT OVERHEAD
 SERVICE ENTRANCE CONDUCTORS ARE EXISTING YOU ARE
 PROPOSING AN INCREASED SERVICE SIZE FROM 400AMPS TO
 600AMPS. OVERHEAD SERVICE ENTRANCE CONDUCTORS AND
 CONDUIT MUST BE OF SUFFICENT SIZE. NEC 230.23A FBC
 107.2.1
  
 2. SERVICE ENTRANCE CONDUCTORS FROM METER TO SERVICE
 DISCONNECT ARE NOT OF SUFFICIENT SIZE FOR A 600AMP
 SERVICE. NEC 230.31
  
 3. NO EQUIPMENT GROUNDING CONDUCTOR PERMITTED FROM
 METER-CAN TO SERVICE DISCONNECTING MEANS. THIS IS A
 PARRALLEL PATH BACK TO THE GROUNDED CONDUCTOR (NEUTRAL)
 PLEASE REMOVE EQUIPMENT GROUND, THE EQUIPMENT GROUNDING
 CONDUCTOR ORIGINATES ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANSNEC 250.24
  
  
 4. PARALLELL CONDUCTORS TO METER CENTER (UNGROUNDED
 CONDUCTORS, GROUNDED CONDUCTORS, AND EQUIPMENT
 GROUNDING CONDUCTORS) ARE NOT OF SUFFICENT SIZE FOR
 600AMP PARALLEL FEEDERS.
 NEC 215.2 NEC 240.4 NEC 310.10H NEC 250.122
  
 5. NO OVERCURRENT PROTECTION SHOWN FOR UNIT BREAKERS ON
 METER CENTER. FBC 107.2.1
  
 6. WHAT IS METER CENTER AMPERAGE/VOLTAGE/PHASE RATING?
 FBC 107.2.1
  
 7. WHAT IS VOLTAGE AND PHASE OF SERVICE? NOT LABELED ON
 PLAN. SINGLE PHASE? THREE PHASE?
  
 8. HOUSE PANEL IS SHOWN AS 100AMPS BUT ON PANEL
 SCHEDULE IT'S SHOWN AS A 60AMP MAIN BREAKER PANEL.
 PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1
  
 9. THERE IS A BRANCH CIRCUIT FROM HOUSE PANEL THAT
 SHOWS A SINGLE #3 CU CONDUCTOR IN A 1/4'' CONDUIT???
 THERE IS NO 1/4'' CONDUIT PERMITTED AND A SINGLE #3 CU
 CONDUCTOR IS NOT A COMPLETE BRANCH CIRCUIT. PROVIDE
 CORRECTION.
  
 10. YOUR LOAD CALCULATION USED IS FOR A MULTI-FAMILY
 DWELLING. THERE ARE NO PERMANENT SLEEPING PROVISIONS
 LABELED IN THESE UNITS AND UNDER THE FBC 2020
 DEFINTIONS THESE UNITS ARE NOT CONSIDERED DWELLINGS
 THEREFORE THE OPTIONAL LOAD CALCULATION OF NEC 220.84
 IS NOT PERMITTED.
  
 11. WHAT WIRE TYPE IN UNITS IS BEING PROPSOED? MC?
 ROMEX? FBC 107.2.1
  
 12. SMOKE ALARMS MUST BE 3 FT AWAY FROM TIPS OF FAN
 BLADES, BATHROOM DOORS, FORCED AIR, AND 10FT AWAY FROM
 COOKING EQUIPMENT PER NFPA 72. PROVIDE CORRECTIONS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-10 Cont ID  
Sent By fgiaquin Date 2022-08-10 Time 19:51 Rev Time 0.00
Received By fgiaquin Date 2022-08-09 Time 22:43 Sent To  
Notes
2022-08-10 19:51:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THERE ARE SEVERAL MAJOR CODE VIOLATIONS ON THIS PLAN.
 THE PLAN REVIEW HAS BEEN STOPPED. PLEASE KEEP IN MIND
 WHEN RESUBMITTING ADDITIONAL VIOLATIONS MAY BE NOTED.
 PLEASE LOOK OVER ENTIRE PLAN BEFORE RESUBMITTING.
  
  
 1. WRONG SERVICE ENTRANCE CONDUCTOR SIZE, ARE YOU
 PROPOSING 2 SETS OR 4-300MCM CU COPPER FOR THE SERVICE
 MAST? IF SO PLEASE BE MORE CLEAR. NEC 230.23A FBC
 107.2.1
  
 2. 3/4'' CONDUIT NIPPLES TOO SMALL TO METER CENTER FOR
 FEEDERS, HOW MANY SETS OF PARALLEL FEEDERS ARE YOU
 PROPOSING? AGAIN PLAN IS NOT CLEAR. NEC 300.17 FBC
 107.2.1
  
 3. NO NEUTRAL (GROUNDED CONDUCTOR) BROUGHT TO METER
 CENTER NEC 215.2A2
  
 4. WIRES IN SERVICE MAST PER PLAN, 4-#300 CU AND 1-300
 CU NEUTRAL?? PLEASE EXPLAIN THE 5TH WIRE?
  
 5. 3/4'' CONDUIT TO HOUSE PANEL IS TO SMALL AND HAS NO
 NEUTRAL BROUGHT TO IT. NEC300.17 NEC215.A2
  
 6. SERVICE DISCONNECTING MEANS NOT SHOWN ON FLOOR PLAN
 FBC 107.2.1
  
 7. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12
  
 8. AFCI PROTECTION REQUIRED PER NEC 210.12A AND B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-09-22 Cont ID  
Sent By pleduc Date 2022-09-22 Time   Rev Time 0.00
Received By pleduc Date 2022-09-22 Time 12:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-08-24 Cont ID  
Sent By pleduc Date 2022-08-24 Time   Rev Time 0.00
Received By pleduc Date 2022-08-24 Time 14:28 Sent To  
Notes
2022-08-24 14:41:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 ON REVEIW OF FIRE COMMENT RESPONSES, FIRE COMMENT # 1
 HAS NOT BEEN TOTALY ADDRESSED .
  
 THOUGH THE DOOR IS AN EXISTING DOOR LEADING TO A EXIT
 STAIR AS PER 7.2.1.4.3 (1), HOWVER (2) IS NOT ADDRESS.
  
 THE APPLICABLE DOOR MUST HAVE HARDWARE THAT ALLOWS THE
 DOOR TO FULLY OPEN, 180 DEGREES
  
  
  
 *******************************************************
 **************************************
 PREVIOUS COMMENTS:
  
 1)
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
  
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENT.
  
  
 1A) COMPLIED
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By pleduc Date 2022-07-13 Time   Rev Time 0.00
Received By pleduc Date 2022-07-13 Time 14:01 Sent To  
Notes
2022-07-13 14:35:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) 2ND FLOOR PLANS - THERE ARE INDICATIONS OF THE
 INSTALLATION OF NEW EXTERIOR DOORS TO EACH UNIT.
  
 THESE DOOR OPEN OUT INTO THE PATH OF EXIT TRAVEL.
  
 THERE ARE NO DIMENSIONS INDICATED FOR THE REMIANING
 WIDTH OF THE REQUIRED EXIT WIDTH OF THE EXIT ACCESS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENT.
  
  
 1A) THERE IS NO DOOR SCHEDULE INDICATING THE LOCK/LATCH
 FOR THE NEW DOORS.
  
 PER NFPA 101, CH 31 EXISTING APARTMENT
  
 31.2.2.2 DOORS.
 30.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE
  
 31.3.6.2.3 DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS
 SHALL BE SELF CLOSING AND SELF-LATCHING.
  
 PLEASE REVIEW AND PROVIDE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-21 Cont ID  
Sent By aoliver Date 2022-12-21 Time 08:39 Rev Time 0.00
Received By aoliver Date 2022-12-12 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-24 Cont ID  
Sent By fgiaquin Date 2022-10-24 Time 19:12 Rev Time 0.00
Received By fgiaquin Date 2022-10-13 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-11 Cont ID  
Sent By fgiaquin Date 2022-10-11 Time 20:53 Rev Time 0.00
Received By fgiaquin Date 2022-09-21 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-20 Cont ID  
Sent By asangele Date 2022-09-20 Time 11:40 Rev Time 0.00
Received By asangele Date 2022-09-20 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-08-17 Time   Rev Time 0.00
Received By cdecoeur Date 2022-07-12 Time 08:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-01-17 Cont ID  
Sent By aoliver Date 2023-01-17 Time 11:57 Rev Time 0.00
Received By aoliver Date 2023-01-17 Time 11:57 Sent To  
Notes
2023-01-17 11:58:14NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2022-12-29 07:57:04EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-09-08 Cont ID  
Sent By jwitmer Date 2022-08-17 Time 14:51 Rev Time 0.00
Received By shill Date 2022-09-08 Time 12:06 Sent To  
Notes
2022-09-08 12:06:46PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 09:51 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By medwards Date 2022-07-27 Time 14:58 Rev Time 0.00
Received By medwards Date 2022-07-27 Time 14:58 Sent To  
Notes
2022-07-27 15:00:06PROVIDE A MECHANICAL SCOPE OF WORK FOR THIS PROJECT,
 INCLUDE MECHANICAL DRAWINGS, ENERGY CALCULATIONS AND
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-30 Cont ID  
Sent By jesmith Date 2022-08-30 Time 10:06 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2022-08-30 10:06:0622070126 3012 BROADWAY
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PROVISO: A DRYWELL SHALL BE PROVIDED FOR THE
 TERMINATION OF A/C CONDENSATE DRAINS (FBC PL 314.2.1).
 A REVISION SHOWING DRYWELL LOCATIONS AND A DRYWELL
 DETAIL SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR
 TO FINAL INSPECTION PER WPB FBC 107.2.1.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By jesmith Date 2022-07-28 Time 14:02 Rev Time 0.00
Received By jesmith Date 2022-07-28 Time 13:18 Sent To  
Notes
2022-07-28 14:02:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070126 3012 BROADWAY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PER WPB FBC 107.2.1 AND FBC PL 314.2, PROVIDE
 CONDENSATE DRAINS FOR THE A/C AIR HANDLERS. SHOW
 COMPLIANCE WITH FBC PL SECTIONS 314.2.1 THROUGH 314.2.5
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 09:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-27 Cont ID  
Sent By jwitmer Date 2022-09-27 Time 11:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 09:51 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 09:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-08-17 Time   Rev Time 0.00
Received By jwitmer Date 2022-08-17 Time 11:27 Sent To  
Notes
2022-07-28 14:13:17SIGNATURES ARE NOTED SIGNED AND VALID ON PDFS. THE
 CERTIFICATE DOES NOT SHOW UP. JS

Review Stop Z ZONING
Rev No 5 Status P Date 2022-12-27 Cont ID  
Sent By asangele Date 2022-12-27 Time 14:54 Rev Time 0.00
Received By asangele Date 2022-12-27 Time 14:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2022-12-20 Cont ID  
Sent By asangele Date 2022-12-20 Time 16:56 Rev Time 0.00
Received By asangele Date 2022-12-20 Time 16:56 Sent To  
Notes
2022-12-20 16:57:1612/20/2022
 FAILED
  
  
 LANDSCAPE PERMIT REQUIRED
  
 THE VALUE OF THE CONSTRUCTION ($310,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($242,655) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2022-10-14 Cont ID  
Sent By asangele Date 2022-10-14 Time 10:21 Rev Time 0.00
Received By asangele Date 2022-10-14 Time 10:21 Sent To  
Notes
2022-10-14 10:22:58FAILED
 10/14/2022
  
 REPEAT COMMENT PLEASE ADDRESS PREVIOUS COMMENTS MADE.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By asangele Date 2022-10-04 Time 11:05 Rev Time 0.00
Received By asangele Date 2022-10-04 Time 11:05 Sent To  
Notes
2022-10-04 11:07:1710/4/2022
 FAILED
  
 PLEASE ADDRESS PREVIOUS COMMENT MADE.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-20 Cont ID  
Sent By asangele Date 2022-09-20 Time 11:37 Rev Time 0.00
Received By asangele Date 2022-09-20 Time 11:37 Sent To  
Notes
2022-09-20 11:40:45FAILED
 9/20/2022
 LANDSCAPE PERMIT REQUIRED
  
 THE VALUE OF THE CONSTRUCTION ($310,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($242,655) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  