Plan Review Details - Permit 22070050
Plan Review Stops For Permit 22070050
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-07-21 Cont ID  
Sent By cpuell Date 2022-07-21 Time 09:37 Rev Time 0.00
Received By cpuell Date 2022-07-21 Time 09:37 Sent To  
Notes
2022-07-21 09:38:20ADDRESS APPROPRIATE FOR PROJECT.BASEMENT & 1ST FLOOR
 NEW MAILROOM

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-10-27 Cont ID  
Sent By dbattles Date 2022-10-27 Time 11:33 Rev Time 0.00
Received By dbattles Date 2022-10-27 Time 11:33 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-10-27 Cont ID  
Sent By aoliver Date 2022-10-27 Time 09:10 Rev Time 0.00
Received By aoliver Date 2022-10-27 Time 09:10 Sent To  
Notes
2022-10-27 09:10:16PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2022-08-26 Time 13:07 Sent To  
Notes
2022-08-26 13:42:28PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 11:40 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 11:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2022-08-26 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By mpeterso Date 2022-08-26 Time 08:43 Rev Time 0.00
Received By mpeterso Date 2022-08-26 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By pleduc Date 2022-07-26 Time   Rev Time 0.00
Received By pleduc Date 2022-07-22 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 11:45 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-27 Cont ID  
Sent By aoliver Date 2022-10-27 Time 09:10 Rev Time 0.00
Received By aoliver Date 2022-10-18 Time 15:56 Sent To  
Notes
2022-10-26 13:06:34PLEASE NOTE: UPDATED PLUMBING PLANS P-1 THROUGH P-5 ARE
 ON FILE AND REVIEWED BUT OLDER P-1 THROUGH P-5 FROM
 FIRST REVIEW CYCLE ARE ON FILE AS WELL
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 13:43 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 08:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2022-08-26 Time 13:42 Sent To  
Notes
2022-08-26 13:43:19NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-07-28 Cont ID  
Sent By medwards Date 2022-07-28 Time 15:05 Rev Time 0.00
Received By medwards Date 2022-07-28 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 07:50 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 07:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-10-26 Cont ID  
Sent By jesmith Date 2022-10-26 Time 13:09 Rev Time 0.00
Received By jesmith Date 2022-10-26 Time 13:04 Sent To  
Notes
2022-10-26 13:05:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070050 205 N DIXIE HWY
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 *PLEASE NOTE: IT APPEARS THAT POTENTIALLY UPDATED PLAN
 SHEETS A-108 AND A-109 ADDRESSING COMMENTS 2 THROUGH 5
 MAY HAVE NOT BEEN UPLOADED AS THE PLAN SHEETS ON FILE
 ARE FROM THE FIRST REVIEW CYCLE
 *PLEASE NOTE: UPDATED PLUMBING PLANS P-1 THROUGH P-5
 ARE ON FILE AND REVIEWED BUT OLDER P-1 THROUGH P-5 FROM
 FIRST REVIEW CYCLE ARE ON FILE AS WELL
  
 1) 1. SECOND REQUEST: PER FBC 1210.2.2, FBC PL 310.3,
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE PER FBC 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS SUCH AS EPOXY,
 DOES NOT MEET THE INTENT OF SECTION 1210.2.2. THE
 TYPICAL MATERIALS USED FOR THIS APPLICATION ARE CERAMIC
 TILE, FIBERGLASS REINFORCED PLASTIC (FRP) PANELS,
 PHENOLIC PANELS, LAMINATED PLASTIC PANELS, PAINTED
 STEEL AND STAINLESS STEEL.
 HARVARD JOLLY RESPONSE: THE WALLS ARE COATED WITH AN
 EPOXY TYPE COATING THAT PROVIDES A TILE-LIKE FINISH.
 IT HAS BEEN THE POSITION TAKEN BY THIS DEPARTMENT THAT
 PAINTED DRYWALL, EVEN WHERE COATED WITH HIGHLY DURABLE
 PAINTS SUCH AS EPOXY, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 2) 2. SECOND REQUEST: THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES NOT 15 INCHES MINIMUM TO 18 INCHES MAXIMUM
 FROM THE SIDE WALL OR PARTITION PER FBC ACC 604.2
 HARVARD JOLLY RESPONSE: SEE RESTROOM ELEVATIONS ON
 SHEET A-108.
 PLAN SHEET A-108 STILL SHOWS A MINIMUM 15 INCHES FROM
 SIDE WALL TO CENTER
  
 3) 3. SECOND REQUEST: THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING A MINIMUM OF
 54 INCHES TOTAL FROM THE REAR WALL PER FBC ACC 604.5.1
 HARVARD JOLLY RESPONSE: SEE RESTROOM ELEVATIONS ON
 SHEET A-108.
 DETAIL DOES NOT SHOW MAXIMUM 54 INCHES TOTAL. THIS IS
 IMPORTANT BECAUSE DUE TO THE 12 INCHES MAXIMUM VERBIAGE
 USED IN THE CODE, A 42 INCH LONG GRAB BAR WOULD NOT
 PROVIDE 54 INCHES MINIMUM IF THE SPACE FROM THE REAR
 WALL WAS LESS THAN 12 INCHES.
  
 4) 4. RESTROOM ELEVATION ACKNOWLEDGED
  
 5) 5. SECOND REQUEST: PER FBC ACC 602.2, PROVIDE A
 CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 FOR THE
 MULTI-PURPOSE ROOM SINK.
 HARVARD JOLLY RESPONSE: SEE CABINET DETAIL 11/A-109.
 CABINET DETAIL 11/A-109 PROVIDES A CABINET ELEVATION
 BUT DOES NOT PROVIDE A CLEAR FLOOR SPACE
  
 6) 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 ELEVATION DETAIL FOR DRINKING FOUNTAIN(S). SHOW
 COMPLIANCE WITH FBC ACC 306 KNEE AND TOE CLEARANCE,
 602.4 SPOUT HEIGHT AND 602.7 SPOUT HEIGHT FOR STANDING
 PERSONS.
 JLRD RESPONSE: THE COOLER SPECIFIED IS AN ADA WATER
 COOLER WITH BOTTLE FILLER TYPE.
 IT IS ACKNOWLEDGED THE SPECIFIED COOLER IS ADA
 COMPLIANT. RESPECTFULLY, THE REQUEST IS FOR AN
 ELEVATION DETAIL FOR THE INSTALLATION AS IT IS ONLY
 COMPLIANT IF INSTALLED TO COMPLY WITH FBC ACC 306 KNEE
 AND TOE CLEARANCE, 602.4 SPOUT HEIGHT AND 602.7 SPOUT
 HEIGHT FOR STANDING PERSONS.
  
 7) 9. JLRD RESPONSE: THE APPROVED SHOP DRAWINGS FOR
 EACH OF THE ITEMS REQUESTED WILL SUBMITTED BY THE
 CONTRACTOR
 NEW COMMENT: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER???S
 SPECIFICATION AND INSTALLATION GUIDES FOR THE EMERGENCY
 SHOWER/EYEWASH, DRINKING FOUNTAIN(S) AND THE WATER
 HEATER. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK.
  
 8) 16. SECOND REQUEST: EWH-1: PER WPB FBC 107.2.1
 PROVIDE COLD WATER WITH SHUT-OFF VALVE TO EWH-1 WATER
 HEATER AND PROVIDE INSTALLATION DETAIL. FBC PL 503.1
 DETAIL IS PROVIDED BUT NO VALVE IS SHOWN; TO BE CLEAR,
 AN ACCESSIBLE, DEDICATED SHUT OFF VALVE FOR THE WATER
 HEATER IS REQUIRED.
  
 9) 17. SLAB REPAIR DETAIL ACKNOWLEDGED
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-11 Cont ID  
Sent By jesmith Date 2022-08-11 Time 15:19 Rev Time 0.00
Received By jesmith Date 2022-08-11 Time 11:50 Sent To  
Notes
2022-08-11 15:16:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070050 205 N DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS:
  
 1. PER FBC 1210.2.2, FBC PL 310.3, WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE PER FBC 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 2. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES NOT 15 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
  
 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING A MINIMUM OF 54 INCHES TOTAL
 FROM THE REAR WALL PER FBC ACC 604.5.1
  
 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 5. PER FBC ACC 602.2, PROVIDE A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 FOR THE MULTI-PURPOSE ROOM
 SINK.
  
 6. PER FBC 606.5 WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 7. PER FBC ACC 602.1, PROVIDE PROVISION FOR DRINKING
 FOUNTAINS TO COMPLY WITH FBC ACC 307.1 PROTRUDING
 OBJECTS, 307.2 PROTRUSION LIMITS.
  
 8. PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL FOR
 DRINKING FOUNTAIN(S). SHOW COMPLIANCE WITH FBC ACC 306
 KNEE AND TOE CLEARANCE, 602.4 SPOUT HEIGHT AND 602.7
 SPOUT HEIGHT FOR STANDING PERSONS.
  
 9. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A)EMERGENCY SHOWER/EYEWASH
 ***B) DRINKING FOUNTAIN(S)
 ***C) WATER HEATER
  
 10. PER WPB FBC 107.2.1, PLEASE PROVIDE NOTE "REFER TO
 MAIN COUNTY COURTHOUSE (MCCH) CENTRALIZED MAILROOM
 PROJECT MANUAL DIVISION 22 FOR PLUMBING
 SPECIFICATIONS".
  
 13. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 15. PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY
 WITH FBC EC TABLE C404.2
  
 16. EWH-1: PER WPB FBC 107.2.1 PROVIDE COLD WATER WITH
 SHUT-OFF VALVE TO EWH-1 WATER HEATER AND PROVIDE
 INSTALLATION DETAIL
  
 17. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL
 ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 18. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 CALCULATIONS FOR SIZING OF WATER DISTRIBUTION.
  
 19. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 CALCULATIONS FOR SIZING OF SANITARY PIPING.
  
 20. P-2 SANITARY FLOOR PLAN SHOWS A FLOOR DRAIN IN THE
 MEN'S RESTROOM; P-4 SANITARY RISER DOES NOT. PER WPB
 FBC 107.2.1, PLEASE CLARIFY AND RECONCILE PLANS.
  
 21. PER WPB FBC 107.2.1, PLEASE SHOW WATER LINE FROM
 TRAP PRIMER FOR FLOOR DRAINS IN THE MEN'S AND WOMEN'S
 RESTROOMS ON P-2 AND P-4.
  
 22. PER WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR TRAP
 PRIMERS TO FLOOR DRAINS.
  
 23. PER WPB FBC 107.2.1 AND FBC PL 604.9 PROVIDE NOTE
 AT P-1/PLUMBING NOTE 10 AND P-5/TYPICAL WHA LOCATION
 DETAIL "WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE
 1010".
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 11:44 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 11:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-26 Cont ID  
Sent By dbattles Date 2022-10-26 Time 10:50 Rev Time 0.00
Received By dbattles Date 2022-10-26 Time 10:50 Sent To  
Notes
2022-10-26 12:15:51ELECTRONIC PLUMBING SIGNATURES ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-08-26 08:46:13ELECTRICAL SHEETS PASSED SIGNATURE REVIEW. MP
2022-08-11 11:54:46THE SELECTED CERTIFICATE HAS ERRORS; NOT VALID FOR
 USAGE. PROVIDE VALID ELECTRONIC SIGNATURES FOR
 PLUMBING. JS
2022-07-28 15:06:33MEHANICAL DIGITAL SIGNATURES APPROVED ME