Plan Review Details - Permit 22061699
Plan Review Stops For Permit 22061699
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By rmcdouga Date 2022-09-02 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2022-09-02 Time 08:55 Sent To  
Notes
2022-09-02 10:43:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) ON PAGE 5 OF THE PLANS, A 1' LAP OF THE #4 REBAR IS
 SPECIFIED. FBC 2107.2.1 REQUIRES THE LAP TO BE 40 BAR
 DIAMETERS.
  
 3) SPECIFY THE TYPE OF CONCRETE BLOCK THAT WILL BE
 USED. THE PLANS SHOW THAT THE CONCRETE BLOCKS ONLY HAVE
 VERTICAL STEEL REINFORCING. NO HORIZONTAL REINFORCING
 IS SPECIFIED. PROVIDE CALCULATIONS TO SHOW THAT THE
 BLOCK CAN WITHSTAND THE LATERAL FORCES OF THE WATER AND
 SOIL. FBC 107.2.1
  
 4) THERE IS NO EMPIRICAL DESIGN FOR MASONRY SWIMMING
 POOLS. SUBMIT SIGNED AND SEALED ENGINEERING FOR THE
 MASONRY PORTIONS OF THE POOL. FBC-R606.1 GENERAL
 MASONRY CONSTRUCTION SHALL BE DESIGNED AND CONSTRUCTED
 IN ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND
 SECTION R301.2.1.1, TMS 402, TMS 403 OR TMS 404.
 FBC-R606.1.1 PROFESSIONAL REGISTRATION NOT REQUIRED
 WHEN THE EMPIRICAL DESIGN PROVISIONS OF APPENDIX A OF
 TMS 402, THE PROVISIONS OF TMS 403, OR THE PROVISIONS
 OF THIS SECTION ARE USED TO DESIGN MASONRY, PROJECT
 DRAWINGS, TYPICAL DETAILS AND SPECIFICATIONS ARE NOT
 REQUIRED TO BEAR THE SEAL OF THE ARCHITECT OR ENGINEER
 RESPONSIBLE FOR DESIGN, UNLESS OTHERWISE REQUIRED BY
 THE STATE LAW OF THE JURISDICTION HAVING AUTHORITY.
  
 5) SPECIFY THE REQUIRED SPACING OF THE VERTICAL AND
 HORIZONTAL STEEL REINFORCING IN THE POURED CONCRETE
 WALLS AND THE SPACING IN EACH DIRECTION IN THE POOL
 FLOOR. FBC 107.2.1
  
 6) INGROUND SWIMMING POOLS ARE REQUIRED TO COMPLY WITH
 ANSI/APSP/ICC5.
 A) SECTION 4.1 REQUIRES STRUCTURAL DESIGN AND MATERIALS
 USED SHALL BE IN ACCORDANCE WITH ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES AND METHODS.
 B) SHOW COMPLIANCE WITH SECTION 5.5 FOR THE SLOPE OF
 THE POOL FLOOR.
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
 PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF
 THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By ppetty Date 2022-08-03 Time 10:52 Rev Time 0.00
Received By ppetty Date 2022-08-03 Time 09:12 Sent To  
Notes
2022-08-03 10:52:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 334.12-B(4) ROMEX NOT PERMITTED IN WET LOCATION.
 2. 210.20 BRANCH CIRCUT SEEMS OVERLOADED PROVIDE LOAD
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By amhamilt Date 2022-07-26 Time 17:27 Rev Time 0.00
Received By amhamilt Date 2022-07-26 Time 17:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-02 Cont ID  
Sent By rmcdouga Date 2022-09-02 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2022-07-18 Time 05:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By ccole Date 2022-07-26 Time 12:53 Rev Time 0.00
Received By ccole Date 2022-07-26 Time 12:53 Sent To  
Notes
2022-07-26 12:55:131ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22061699
 7/26/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6: PROVIDE TDH CALCULATIONS- SECS. 4.4.9,
 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 FBC
 RES.
  
 2) SHEET P6: PROVIDE THE PUMP CURVE ON THE SHEET MARKED
 UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- SECS.
 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3
 FBC RES.
  
 3) P6: PROVIDE A HYDROSTATIC RELIEF DEVICE AND SHOW THE
 INSTALLATION LOCATION- SEC. R4501.21.4 FBC RES.
  
 4) P6: LIST THE MAKE AND MODEL THE ANTI- ENTRAPMENT
 SUCTION OUTLET COVERS AND DRAIN ASSEMBLIES AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS- SEC. R4501.6.6 FBC RES.
  
 5) P6: PLEASE CLARIFY THE PURPOSE OF THE ?-INCH PEX
 WATER SUPPLY PIPE. IS THE PIPE CONNECTED TO AN AUTOFILL
 FOR THE POOL? PLEASE NOTE ON THE PLAN IF APPLICABLE AND
 SHOW THE PEX LINE CONNECTION LOCATION TO THE WATER
 SOURCE- SEC. 107.2.1 WPB. PLEASE NOTE A PVB BACKFLOW
 PREVENTER IS REQUIRED AT THE AUTOFILL. PLEASE PROVIDE
 NOTES ON THE PLAN INCLUDING THE MAKE AND MODEL OF THE
 BACKFLOW PREVENTER- SECS. P2902.3 & P2902.5.4.1 FBC
 RES.
  
 6) P6: BACKFLOW PREVENTION IS REQUIRED FOR THE WATER
 SERVICE IN ACCORDANCE WITH SECS. C, D, & E WPB
 UTILITIES CROSS CONNECTION MANUAL. A SEPARATE PERMIT IS
 REQUIRED FOR INSTALLATION OF THE DEVICE. PLEASE PLACE A
 NOTE ON THE PLAN.
  
 7) P6: PROVIDE A LIST OF CODES AND CONFORMANCE
 STANDARDS USED IN THE DESIGN OF THE POOL- REFER TO SEC.
 R4501.6.1 FBC RES.
  
 8) P6: THE CODE SECTION NUMBERS LISTED UNDER THE NOTES
 ARE NOT CORRECT OR CONSISTENT WITH CHAPTER 45 OF THE
 FBC RES. PLEASE CORRECT THE NOTES- SEC. 107.2.1 WPB.
  
 9) P6: THE PLANS SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By rmcdouga Date 2022-09-02 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2022-09-02 Time 10:44 Sent To  
Notes
2022-09-02 10:48:50FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By vbroglia Date 2022-07-27 Time 11:25 Rev Time 0.00
Received By vbroglia Date 2022-07-27 Time 11:25 Sent To  
Notes
2022-07-27 11:41:207/27/2022
  
 A SEPARATE PERMIT IS REQUIRED FOR POOL EQUIPMENT
  
 POOL EQUIPMENT CANNOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
 REQUIERED REAR SETBACK FOR PROPERTY IS 12 FEET,
 EQUIPMENT CAN HAVE A SETBACK OF 8 FEET FROM REAR
 PROPERTY LINE
  
 POOL EQUIPMENT CANNOT BE 1 FOOT FROM REAR PROPERTY
 LINE.
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  