Plan Review Details - Permit 22061657
Plan Review Stops For Permit 22061657
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-08-09 Cont ID  
Sent By jgomez Date 2022-08-09 Time 10:01 Rev Time 0.00
Received By jgomez Date 2022-08-09 Time 09:27 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 14:06 Rev Time 0.00
Received By shill Date 2022-08-01 Time 14:06 Sent To  
Notes
2022-08-01 14:06:58TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED. WE DO NOT
 NEED EITHER DOCUMENT. PLEASE DO THE FOLLOWING, UPLOAD
 TO PROJECTDOX WHEN RESUBMITTING:
  
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 13:32 Rev Time 0.00
Received By shill Date 2022-07-26 Time 13:27 Sent To  
Notes
2022-07-26 13:32:49PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-09 Cont ID  
Sent By jgomez Date 2022-08-09 Time 10:01 Rev Time 0.00
Received By jgomez Date 2022-08-09 Time 09:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 14:11 Rev Time 0.00
Received By shill Date 2022-08-01 Time 14:11 Sent To  
Notes
2022-08-01 14:12:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 2. THIS BUILDING HAS A 7" SLAB, SOUND TEST FOR AN 8"
 SLAB WAS SUBMITTED. THE STC/IIC NEEDS TO BE TESTED WITH
 A 7" OR THINNER SLAB, SEE COMMENT #3.
  
 3. SEE PREVIOUS LIST FOR CODE REFERENCES
  
 PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD. PROFLEX MAXXIM 90
 IS PROPOSED, WE DO NOT HAVE THOSE TEST REPORTS ON FILE.
 EITHER SELECT A PRODUCT FOR WHICH WE HAVE TEST REPORTS
 ON FILE, OR PROVIDE THE FOLLOWING:
  
 A, B. STC/IIC - RESPONSE LETTER STATES THAT WAS ALREADY
 SUBMITTED. THAT TEST REPORT WAS DONE WITH AN 8" SLAB.
 THIS UNIT HAS A 7" SLAB.
  
 C. FLAME SPREAD - 2ND REVIEW, TEST REPORT IS FOR
 SUPERSIM 90, NOT MAXXIM 90.
  
 IF YOU WOULD LIKE TO CHANGE THE PRODUCT PROPOSED FROM
 PROFLEX MAXXIM 90 TO SUPERSIM 90, REVISE PLAN. TEST
 REPORTS THAT WE HAVE ON FILE WILL BE UPLOADED FOR YOU.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 13:27 Rev Time 0.00
Received By shill Date 2022-07-26 Time 13:27 Sent To  
Notes
2022-07-26 13:30:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO SPECIFY TILE BACKERBOARD, FBC B 2509.
  
 2. THIS BUILDING HAS A 7" SLAB, SOUND TEST FOR AN 8"
 SLAB WAS SUBMITTED. THE STC/IIC NEEDS TO BE TESTED WITH
 A 7" OR THINNER SLAB, SEE COMMENT #3.
  
 3. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD. PROFLEX MAXXIM 90
 IS PROPOSED, WE DO NOT HAVE THOSE TEST REPORTS ON FILE.
 EITHER SELECT A PRODUCT FOR WHICH WE HAVE TEST REPORTS
 ON FILE, OR PROVIDE THE FOLLOWING:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By cwalker Date 2022-07-05 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-09 Cont ID  
Sent By jgomez Date 2022-08-09 Time 10:01 Rev Time 0.00
Received By jgomez Date 2022-08-06 Time 07:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 14:12 Rev Time 0.00
Received By shill Date 2022-07-29 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 13:37 Rev Time 0.00
Received By shill Date 2022-07-01 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 07:03 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 06:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By ccole Date 2022-07-06 Time 16:56 Rev Time 0.00
Received By ccole Date 2022-07-06 Time 16:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 13:33 Rev Time 0.00
Received By shill Date 2022-07-26 Time 13:33 Sent To  
Notes
***NONE***