Plan Review Details - Permit 22061582
Plan Review Stops For Permit 22061582
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 7 Status P Date 2023-07-05 Cont ID  
Sent By aoliver Date 2023-07-05 Time 08:03 Rev Time 0.00
Received By aoliver Date 2023-07-05 Time 08:03 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 6 Status F Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 18:28 Rev Time 0.00
Received By jgomez Date 2023-06-29 Time 18:28 Sent To  
Notes
2023-06-29 18:29:15CONTRACTOR'S ASBESTOS ACKNOWLEDGMENT
 1-CONTRACTOR TO PROVIDE A SIGNED ACKNOWLEDGMENT LETTER,
 ON CONTRACTOR'S LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status F Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 14:52 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 14:52 Sent To  
Notes
2023-01-19 14:56:01ORIGINAL COMMENT:
  
 CONTRACTOR'S ASBESTOS ACKNOWLEDGMENT
 1-CONTRACTOR TO PROVIDE A SIGNED ACKNOWLEDGMENT LETTER,
 ON CONTRACTOR'S LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 RESPONSE:
 ASBESTOS ACKNOWLEDGMENT LETTER HAS THE WRONG ADDRESS.
 NEED LETTER WITH CORRECT ADDRESS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2023-01-10 Cont ID  
Sent By jgomez Date 2023-01-10 Time 17:31 Rev Time 0.00
Received By jgomez Date 2023-01-10 Time 17:31 Sent To  
Notes
2023-01-10 17:32:0501/10/23 MET WITH FLOYD SCARLETT TO GO OVER
 ACKNOWLEDGMENT LETTER CONTENT. JG.
  
  
 NOTE: CHANGE OF CONTRACTOR. NEED ASBESTOS LETTER FROM
 NEW CONTRACTOR.
  
 CONTRACTOR'S ASBESTOS ACKNOWLEDGMENT
 1-CONTRACTOR TO PROVIDE A SIGNED ACKNOWLEDGMENT LETTER,
 ON CONTRACTOR'S LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 13:57 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 13:26 Sent To  
Notes
2023-01-09 13:59:27NOTE: CHANGE OF CONTRACTOR. NEED ASBESTOS LETTER FROM
 NEW CONTRACTOR.
  
 CONTRACTOR'S ASBESTOS ACKNOWLEDGMENT
 1-CONTRACTOR TO PROVIDE A SIGNED ACKNOWLEDGMENT LETTER,
 ON CONTRACTOR'S LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:40 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:40 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 18:44 Rev Time 0.00
Received By shill Date 2022-07-25 Time 18:44 Sent To  
Notes
2022-07-25 18:44:44PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 18:27 Rev Time 0.00
Received By jgomez Date 2023-06-29 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 14:21 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 14:16 Sent To  
Notes
2023-01-19 14:20:00RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061582
 2761 VILLAGE BLVD # 403
  
 NOTE:
 LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 1- FLOYD SCARLET EMAILED ME PLANS. PLANS WERE NOT
 PREPARED BY LICENSED ARCHITECT. MR. SCARLETT WAS TOLD
 ON 01/10/23 THAT PLANS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY SEC. 481.229 F.S
  
  
 01/10/23 MET WITH FLOYD SCARLETT TO GO OVER SCOPE.
 BASED ON ALL THE PROPOSED SCOPE OF WORK AND VALUE, IT
 WAS EXPLAINED TO MR. SCARLETT THAT THE PLANS NEED TO BE
 DONE BY ARCHITECT AND COMPLETE DETAILS AND
 SPECIFICATIONS WILL NEED TO BE PROVIDED. JG.
 SEC. 481.229 F.S.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-01-10 Cont ID  
Sent By jgomez Date 2023-01-10 Time 17:27 Rev Time 0.00
Received By jgomez Date 2023-01-10 Time 17:27 Sent To  
Notes
2023-01-10 17:31:2801/10/23 MET WITH FLOYD SCARLETT TO GO OVER SCOPE.
 BASED ON ALL THE PROPOSED SCOPE OF WORK AND VALUE, IT
 WAS EXPLAINED TO MR. SCARLETT THAT THE PLANS NEED TO BE
 DONE BY ARCHITECT AND COMPLETE DETAILS AND
 SPECIFICATIONS WILL NEED TO BE PROVIDED. JG.
  
  
 RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061582
 2761 VILLAGE BLVD # 403
  
 NOTE:
 LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- NEED TO SPECIFY BATHROOM TILE BACKBOARD. SEC. 2509
 FBC-BUILDING.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 13:46 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 13:30 Sent To  
Notes
2023-01-09 13:47:05RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061582
 2761 VILLAGE BLVD # 403
  
 NOTE:
 LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- NEED TO SPECIFY BATHROOM TILE BACKBOARD. SEC. 2509
 FBC-BUILDING.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:49 Rev Time 0.00
Received By shill Date 2022-12-06 Time 10:49 Sent To  
Notes
2022-12-06 10:49:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TEST REPORTS WERE NOT SUBMITTED. NOT CLEAR HOW ITEM #3
 WAS ADDRESSED.
  
 1. OK
  
 2. FS471, ENGINEER DOES NOT HAVE A DIGITAL OR
 ELECTRONIC SIGNATURE - HE CAN SUBMIT ONE SIGNED AND
 SEALED PAPER ORIGINAL AFTER ALL REVIEWS HAVE PASSED.
  
 3. FBC B 1207 (ALSO SEE PREVIOUS LIST FOR MORE COMPLETE
 CODE REFERENCES AND GUIDANCE). BASED ON THE FILES
 UPLOADED, NUCORE FLOORING IS PROPOSED OVER SHAW
 GROUNDWORKS UNDERLAYMENT.
  
 FLAME SPREAD FOR GROUNDWORKS - IS OK.
  
 THE STC/IIC FOR GROUNDWORKS WAS DONE WITH SMARTCORE PRO
 FLOORING. SINCE LVT HAS A STC/IIC VALUE, IT IS NOT
 CLEAR IF THE FLOORING PROPOSED COMPLIES WITH THE
 MINIMUM REQUIREMENTS OF STC/IIC. EITHER PROVIDE AN
 ENGINEERED ANALYSIS OF NUCORE VS. SMARTCORE, OR PROVIDE
 TEST REPORTS FOR STC/IIC FOR THIS ASSEMBLY, OR PROPOSE
 A DIFFERENT PRODUCT.
  
 YOU MAY EMAIL THE PROPOSED RESOLUTION PRIOR TO
 RESUBMITTING IF YOU WOULD LIKE. ALTHOUGH THIS REVIEW IS
 BEING DONE WITHIN A DAY OF RESUBMITTAL, THIS IS NOT
 TYPICAL. OUR TARGET IS 10-14 DAYS.
  
  
  
 FOR REFERENCE ONLY, THE FOLLOWING FILES WERE SUBMITTED
 FOR FLOORING:
  
 SHAW GROUNDWORKS UNDERLAYMENT FLAME SPREAD (FILE NAME
 INTERTEK FLAME SPREAD TEST REPORT)
 NUCORE FLOORING SPEC SHEET
 SMARTCORE PRO STC/IIC (FILE NAME SHAW INDUSTRIES VINYL
 PLANK TEST REPORT)
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:50 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:50 Sent To  
Notes
2022-08-06 10:57:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 2. FS471, ENGINEER DOES NOT HAVE A DIGITAL OR
 ELECTRONIC SIGNATURE - HE CAN SUBMIT ONE SIGNED AND
 SEALED PAPER ORIGINAL AFTER ALL REVIEWS HAVE PASSED.
  
 3. FBC B 1207 (ALSO SEE PREVIOUS LIST FOR MORE COMPLETE
 CODE REFERENCES AND GUIDANCE). BASED ON THE FILES
 UPLOADED, NUCORE FLOORING IS PROPOSED OVER SHAW
 GROUNDWORKS UNDERLAYMENT.
  
 FLAME SPREAD FOR GROUNDWORKS - IS OK.
  
 THE STC/IIC FOR GROUNDWORKS WAS DONE WITH SMARTCORE PRO
 FLOORING. SINCE LVT HAS A STC/IIC VALUE, IT IS NOT
 CLEAR IF THE FLOORING PROPOSED COMPLIES WITH THE
 MINIMUM REQUIREMENTS OF STC/IIC. EITHER PROVIDE AN
 ENGINEERED ANALYSIS OF NUCORE VS. SMARTCORE, OR PROVIDE
 TEST REPORTS FOR STC/IIC FOR THIS ASSEMBLY, OR PROPOSE
 A DIFFERENT PRODUCT.
  
 YOU MAY EMAIL THE PROPOSED RESOLUTION PRIOR TO
 RESUBMITTING IF YOU WOULD LIKE. ALTHOUGH THIS REVIEW IS
 BEING DONE WITHIN A DAY OF RESUBMITTAL, THIS IS NOT
 TYPICAL. OUR TARGET IS 10-14 DAYS.
  
  
  
 FOR REFERENCE ONLY, THE FOLLOWING FILES WERE SUBMITTED
 FOR FLOORING:
  
 SHAW GROUNDWORKS UNDERLAYMENT FLAME SPREAD (FILE NAME
 INTERTEK FLAME SPREAD TEST REPORT)
 NUCORE FLOORING SPEC SHEET
 SMARTCORE PRO STC/IIC (FILE NAME SHAW INDUSTRIES VINYL
 PLANK TEST REPORT)
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 18:45 Rev Time 0.00
Received By shill Date 2022-07-25 Time 18:45 Sent To  
Notes
2022-07-25 18:47:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 2509, REVISE PLAN TO SPECIFY TILE BACKERBOARD.
  
 2. FS471, PLAN WAS PREPARED BY DAVID MONK, PE. UPLOAD A
 DIGITALLY SIGNED DOCUMENT. IF THE ENGINEER DOES NOT
 HAVE A DIGITAL SIGNATURE, EMAIL ME TO DISCUSS. NOTE
 THAT THE SEAL USED HAS NOT BEEN ACCEPTED BY FBPE FOR
 OVER TEN YEARS.
  
 3. NEW FLOORING IS PROPOSED. REVISE THE PLAN TO CLARIFY
 FLOORING TYPE - FOR INSTANCE TILE, LVT, WOOD, ETC. IF
 THE FLOORING ALONE DOES NOT HAVE TEST REPORTS TO SHOW
 COMPLIANCE WITH STC AND IIC REQUIREMENTS, UNDERLAYMENT
 IS REQUIRED. IF UNDERLAYMENT IS NOT REQUIRED, PROVIDE
 STC AND IIC TEST REPORTS FOR THE PROPOSED FLOORING. SEE
 BELOW FOR ADDITIONAL INFO.
  
 PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2023-06-02 Cont ID  
Sent By jleahy Date 2023-06-02 Time 12:53 Rev Time 0.00
Received By jleahy Date 2023-06-02 Time 12:48 Sent To  
Notes
2023-06-02 12:53:50ALL ELECTRIC IS SHOWN AS EXISTING JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:05 Rev Time 0.00
Received By jleahy Date 2022-08-23 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-07-21 Cont ID  
Sent By jleahy Date 2022-07-21 Time 13:53 Rev Time 0.00
Received By jleahy Date 2022-07-21 Time 13:50 Sent To  
Notes
2022-07-21 13:54:18NO ELECTRICAL WORK SHOWN OR APPROVED JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-05-25 Cont ID  
Sent By pleduc Date 2023-05-25 Time   Rev Time 0.00
Received By pleduc Date 2023-05-25 Time 15:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-01-10 Cont ID  
Sent By cwalker Date 2023-01-10 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-12-01 Cont ID  
Sent By cwalker Date 2022-12-01 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-08 Cont ID  
Sent By cwalker Date 2022-08-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By cwalker Date 2022-06-30 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-06-30 11:12:48FIRE REVIEW COMMENTS:
 PROVIDE DETAILS ON THE TYPE OF FLOORING TO BE INSTALLED
 TO INCLUDE THE MANUFACTURES INFORMATION FOR THE
 MATERIALS FIRE PERFORMANCE TO INCLUDE THE CRITICAL
 RADIANT FLUX. NFPA 101, 10.2.7
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-07-05 Cont ID  
Sent By aoliver Date 2023-07-05 Time 08:03 Rev Time 0.00
Received By aoliver Date 2023-07-03 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 18:32 Rev Time 0.00
Received By jgomez Date 2023-05-24 Time 12:25 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 14:36 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 14:16 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-10 Cont ID  
Sent By jgomez Date 2023-01-10 Time 17:34 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 14:22 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:50 Rev Time 0.00
Received By shill Date 2022-11-29 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:05 Rev Time 0.00
Received By jleahy Date 2022-08-06 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 18:49 Rev Time 0.00
Received By shill Date 2022-06-30 Time 05:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2023-05-25 Cont ID  
Sent By rwbrown Date 2023-05-25 Time 07:10 Rev Time 0.00
Received By rwbrown Date 2023-05-25 Time 07:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-01-10 Cont ID  
Sent By rwbrown Date 2023-01-10 Time 07:09 Rev Time 0.00
Received By rwbrown Date 2023-05-25 Time 07:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-05 Cont ID  
Sent By rwbrown Date 2022-12-05 Time 05:57 Rev Time 0.00
Received By rwbrown Date 2023-05-25 Time 07:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By rwbrown Date 2022-08-09 Time 07:10 Rev Time 0.00
Received By rwbrown Date 2022-08-09 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By rwbrown Date 2022-07-05 Time 11:52 Rev Time 0.00
Received By rwbrown Date 2022-07-05 Time 11:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 18:28 Rev Time 0.00
Received By jgomez Date 2023-06-29 Time 18:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 14:36 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 14:36 Sent To  
Notes
2023-01-19 14:37:3301/10/23 MET WITH FLOYD SCARLETT TO GO OVER SCOPE.
 BASED ON ALL THE PROPOSED SCOPE OF WORK AND VALUE, IT
 WAS EXPLAINED TO MR. SCARLETT THAT THE PLANS NEED TO BE
 DONE BY ARCHITECT AND COMPLETE DETAILS AND
 SPECIFICATIONS WILL NEED TO BE PROVIDED. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-01-10 Cont ID  
Sent By jgomez Date 2023-01-10 Time 17:33 Rev Time 0.00
Received By jgomez Date 2023-01-10 Time 17:33 Sent To  
Notes
2023-01-10 17:33:5701/10/23 MET WITH FLOYD SCARLETT TO GO OVER SCOPE.
 BASED ON ALL THE PROPOSED SCOPE OF WORK AND VALUE, IT
 WAS EXPLAINED TO MR. SCARLETT THAT THE PLANS NEED TO BE
 DONE BY ARCHITECT AND COMPLETE DETAILS AND
 SPECIFICATIONS WILL NEED TO BE PROVIDED. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 14:00 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 14:00 Sent To  
Notes
2023-01-09 14:00:47NO ARCHITECT OR ENGINEER. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 10:50 Rev Time 0.00
Received By shill Date 2022-12-06 Time 10:50 Sent To  
Notes
2022-12-06 10:50:21SEE BUILDING

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:39 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:39 Sent To  
Notes
2022-08-06 10:39:33SEE BUILDING
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 18:47 Rev Time 0.00
Received By shill Date 2022-07-25 Time 18:47 Sent To  
Notes
2022-07-25 18:48:09SEE BUILDING
 UPLOAD A DIGITALLY SIGNED DOCUMENT
  