Plan Review Details - Permit 22061529
Plan Review Stops For Permit 22061529
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 06:59 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 06:59 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2022-08-29 Time 09:09 Sent To  
Notes
2022-08-29 09:46:52THE ASBESTOS LETTER THAT WAS SUBMITTED DOES NOT HAVE
 THE ADDRESS OF THE PROJECT AND HAS THE WRONG PERMIT
 NUMBER. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-23 Cont ID  
Sent By shill Date 2022-09-23 Time 10:29 Rev Time 0.00
Received By shill Date 2022-09-23 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 08:04 Sent To  
Notes
2022-09-22 08:05:48PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLAME SPREAD AND SMOKE DEVELOPED TEST REPORT FOR
 WHISPERMAT CS WAS SUBMITTED. PLEASE SUBMIT THE
 WHISPERMAT CS TEST REPORTS FOR THE FOLLOWING ITEMS.
  
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2022-08-29 Time 09:09 Sent To  
Notes
2022-08-29 13:53:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET CVR THE EXPOSURE CATEGORY IN SPECIFIED AS
 C. THIS BUILDING IS LOCATED IN EXPOSURE CATEGORY D. FBC
 1609.4.3
  
 2) ON SHEET CVR, THE OCCUPANCY TYPE UNDER THE BUILDING
 CODE IS R-2. THE MF32 IS A ZONING DESIGNATION. FBC
 310.4
  
 3) A DATA SHEET FOR DUROCK WAS SUBMITTED. THE SCOPE OF
 WORK ON THE PLANS DOES NOT SPECIFY WHERE THE DUROCK
 WILL BE INSTALLED. PLEASE CLARIFY. FBC 107.2.1
  
 4) THE FLAME SPREAD AND SMOKE DEVELOPED TEST REPORT FOR
 WHISPERMAT CS WAS SUBMITTED. PLEASE SUBMIT THE
 WHISPERMAT CS TEST REPORTS FOR THE FOLLOWING ITEMS.
  
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-08 Cont ID  
Sent By fgiaquin Date 2022-09-08 Time 19:28 Rev Time 0.00
Received By fgiaquin Date 2022-09-08 Time 18:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-09 Cont ID  
Sent By fgiaquin Date 2022-08-09 Time 22:36 Rev Time 0.00
Received By fgiaquin Date 2022-08-09 Time 18:32 Sent To  
Notes
2022-08-09 22:42:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 2. RECEPTACLES REQUIRED ON BOTH FRONT AND REAR OF
 DWELLING OUTSIDE NEC 210.52E
  
 3. RECEPTACLE REQUIRED ON BALCONY. 210.52E
  
 4. NO EGRESS LIGHTING SHOWN. NEC 210.70
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-08 Cont ID  
Sent By   Date 2022-09-08 Time   Rev Time 0.00
Received By bdolan Date 2022-09-08 Time 11:45 Sent To  
Notes
2022-09-08 11:45:33FIRE DEPARTMENT HAS NO OBJECTION TO THE PROJECT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-02 Cont ID  
Sent By   Date 2022-08-02 Time   Rev Time 0.00
Received By bdolan Date 2022-08-02 Time 12:32 Sent To  
Notes
2022-08-02 12:33:02FIRE DEPARTMENT HAS NO OBJECTION TO THE PROJECT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2022-09-06 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 13:54 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 07:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By rmcdouga Date 2022-08-29 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2022-08-29 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2022-09-07 Cont ID  
Sent By medwards Date 2022-09-07 Time 13:40 Rev Time 0.00
Received By medwards Date 2022-09-07 Time 13:40 Sent To  
Notes
2022-09-07 13:40:31NO MECHANICAL WORK SHOWN FOR THIS PROJECT. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-29 Cont ID  
Sent By medwards Date 2022-07-29 Time 09:30 Rev Time 0.00
Received By medwards Date 2022-07-29 Time 09:30 Sent To  
Notes
2022-07-29 09:34:11THEE IS NO COMMENTS ABOUT THE MECHANICAL WORK FOR THIS
 COMPLETE REMODEL, BUT ON THE MEP SHEET UNDER THE
 ELECTRICAL FIXTURES SCHEDULE IT IS EXPLAINED THAT THE N
 IS FOR NEW. IN THE A/C CLOSET THE ELECTRICAL IS NEW.
 EXPLAIN THE REASON FOR THE NEW WIRING IF THERE IS TO BE
 NO MECHANICAL WORK FOR THIS PROJECT. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By rwbrown Date 2022-09-07 Time 06:11 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-07-29 Cont ID  
Sent By rwbrown Date 2022-07-29 Time 10:17 Rev Time 0.00
Received By rwbrown Date 2022-07-29 Time 10:12 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By rgathrig Date 2022-07-18 Time 13:56 Rev Time 0.00
Received By rgathrig Date 2022-07-18 Time 13:56 Sent To  
Notes
2022-07-18 13:57:32PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
  
 TEW AND TAYLOR
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 08:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-16 Cont ID  
Sent By jleahy Date 2022-08-16 Time 15:56 Rev Time  
Received By jleahy Date   Time   Sent To  
Notes
2022-08-16 15:57:51PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A PHOTOCOPIED OR PRINTED
 SIGNATURE IS NOT ACCEPTABLE. PER FAC 61G15-23.003, (1)
 THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEES SIGNATURE ON EACH PAGE REQUIRED TO BE SEALED.
 A SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEES SIGNATURE SHALL NOT BE USED.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-04 Cont ID  
Sent By afowlkes Date 2022-08-04 Time 15:37 Rev Time 0.00
Received By afowlkes Date 2022-08-04 Time 15:37 Sent To  
Notes
***NONE***