2022-07-28 11:04:20 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL11559-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL11559.3-R7 COVERS MULTIPLE FASTENER SPACING |
| TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT |
| FASTENER PATTERN & SPACING FROM TABLE ?A? PAGE #5 OF |
| THE EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM |
| DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE |
| CATEGORY D AREAS. |
| 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT TO |
| BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING |
| 4. 61G15-23.001. F.A.C. (B). ENGINEERING SPECIFICATIONS |
| AND CALCULATIONS. AN INDEX SHEET SHALL BE USED AND |
| SHALL BE SIGNED, DATED AND SEALED BY EACH PROFESSIONAL |
| ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF |
| THE ENGINEERING SPECIFICATIONS OR CALCULATIONS. THE |
| INDEX SHEET MUST BE SIGNED, DATED AND SEALED BY THOSE |
| PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF THE |
| PRODUCTION AND PREPARATION OF EACH SECTION OF THE |
| ENGINEERING SPECIFICATIONS OR CALCULATIONS, WITH |
| SUFFICIENT INFORMATION ON THE INDEX SHEET SO THAT THE |
| USER WILL BE AWARE OF EACH PORTION OF THE |
| SPECIFICATIONS OR CALCULATIONS FOR WHICH EACH |
| PROFESSIONAL ENGINEER IS RESPONSIBLE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |