Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By medwards Date 2022-09-22 Time 13:34 Rev Time 0.00
Received By medwards Date 2022-09-22 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 06:56 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 06:56 Sent To  
Notes
2022-07-08 07:04:08SHEET 1 OF 2 IN THE SUBMITTED DRAWINGS HAS A NOTE THAT
 STATES- INDOOR CONDENSING UNIT LOCATION REQUIRES 1,OOO
 CFM PER HP PER UNIT MECHANICAL VENTILATION HEAT
 EXTRACTION. THE MECHANICAL ENGINEER FOR THIS PROJECT
 MUST REVISED THE ORIGINAL MECHANICAL DESIGN TO REFLECT
 THIS REQUIREMENT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  