2022-08-31 10:23:43 | RESIDENTIAL(R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22061225 |
| 4098 WINNIPEG WAY |
| |
| 1- SIZE OF ANCHOR SPECIFIED (ITW TAPCON 1/4X2-1/4) FOR |
| CONCRETE INSTALLATION DOESN'T PROVIDE 1.75 INCH |
| EMBEDMENT INTO THE CONCRETE AS REQUIRED BY ANCHOR |
| SCHEDULE TABLE ON SHEET 12 OF 18 OF SHUTTERS DRAWINGS |
| SUBMITTED. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 2- BASED ON THE SHUTTERS SPAN. THE ANCHOR SPACING |
| SPECIFIED AT THE BOTTOM FOR OPENINGS #1, #2, #4 AND #9 |
| IS INCORRECT. SEE THE SHUTTERS SPACING ON THE ANCHOR |
| SPACING TABLE ON SHEET 13 OF 18 OF SHUTTERS DRAWINGS |
| SUBMITTED. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- TYPE OF ANCHOR SPECIFIED UNDER THE BUILDING HEIGHT |
| IS INCOMPLETE. ITW IS JUST THE BRAND NAME. NEED TO |
| PROVIDE COMPLETE SPECIFICATIONS OF ANCHORS TO BE |
| INSTALLED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- INFORMATION ENTERED IN COLUMN #4 FOR OPENING #3 IS |
| INCORRECT. THERE IS NOT ANCHOR TYPE B2. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: THIS COLUMN IS TO SPECIFY THE SHUTTER MOUNTING |
| CONDITION. FOR EXAMPLE WALL MOUNT SECTION C AS SHOWN ON |
| SHEET 04 OF 18, BUILT OUT MOUNTING, ETC. ANCHOR TYPE A, |
| A1, ETC. SHOULD BE ENTERED IN THE SPECIFIC ANCHOR TYPE |
| COLUMN. |
| |
| 5- INSTALLATION SCHEDULE IS MISSING THE INFORMATION IN |
| THE SUBSTRATE COLUMN (CONCRETE OR CONCRETE BLOCK, |
| ETC.). |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 6- ACCORDING SHUTTERS ARE INSTALLED VERTICALLY NOT |
| HORIZONTALLY. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |