Plan Review Details - Permit 22061010
Plan Review Stops For Permit 22061010
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 07:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-04 Cont ID  
Sent By jwitmer Date 2022-08-04 Time 09:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-08-04 09:20:17COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 09:40 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-01-26 Cont ID  
Sent By jwitmer Date 2023-01-26 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2023-01-26 Time 10:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-03 Cont ID  
Sent By jwitmer Date 2023-01-03 Time 11:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-03 11:46:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061010
 ADD: 701 S OLIVE AVE. # 109
 CONT: SCALTEC USA, CORP
 TEL: 954-553-0354
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN.03RD/2023
 ACTION: DENIED
  
 1) THE COVERSHEET BUILDING DATA:
 1A) COMPLIED.
  
 1B)3RD REQUEST. THE COVERSHEET STILL STATES A MULTI USE
 RESIDENCE. PLEASE SHOW WHERE THE RESIDENCE BEDROOM,
 BATH AND KITCHEN ARE LOCATED AND WHERE NOT MORE THAN 50
 % OF THE AREA IS THE WORK AREA, PROVIDE EACH AREA IN
 SQUARE FEET FOR LIVE LOFT AND WORK AREA. IF THIS DOES
 NOT MEET THIS REQUIREMENT, THEN A ONE HOUR FIRE
 PARTITION WALL PER SECTION 420.2 OF THE 2020
 FBC-BUILDING CODE WILL BE REQUIRED. OTHERWISE AS SHOWN
 THIS IS A BUSINESS OCCUPANCY PER 304.1, FBC-BUILDING
 CODE.
  
 1ST ROUND COMMENTS. OCCUPANCY TYPE IS LISTED AS A
 RESIDENTIAL LIVE/ WORK LOFT AND REFERENCES FBC-310.4.
 PLEASE ALSO REFER TO THE CODE REQUIREMENTS FOR
 LIVE/WORK LOFTS FOUND IN SECTION 419 OF THE 2020
 FBC-BUILDING CODE. REVIEW 419.1.1(2) WHERE THE
 NONRESIDENTIAL AREA IS PERMITTED TO B NOT MORE THAN 50
 PERCENT OF THE AREA OF LIVE WORK UNIT. THE PROPOSED
 FLOOR PLAN NOR MEZZANINE FLOOR PLAN SHOW WHERE THE
 LIVING QUARTERS ARE.
  
 1C) 3RD REVIEW. PLEASE REVIEW THE 2020 FBC-BUILDING
 CODE SECTION 419.9. WHERE THE NONRESIDENTIAL AREA OF
 THE LIVE/WORK UNIT IS REQUIRED TO BE ACCESSIBLE BY THE
 FLORIDA BUILDING CODE, ACCESSIBILITY, THE PLUMBING
 FIXTURES SPECIFIED BY CHAPTER 29 SHALL BE ACCESSIBLE.
 PLEASE SHOW A BLOW-UP FLOOR PLAN OF THE 1ST FLOOR
 RESTROOM WITH DIMENSIONS, AND COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTIONS:
  
 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED,
 SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH (FINISHES MAY ENCROACH) ON THE FINISH
 DIMENSION!!!
  
 603.3 MIRRORS. 2020 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 GRAB BARS/ RESTROOMS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE SIDE
 WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED
 12 INCHES MAXIMUM FROM THE REAR WALL AND EXTENDING 54
 INCHES MINIMUM FROM THE REAR WALL.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL
 NOT BE LOCATED BEHIND THE GRAB BARS.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE
 604.3.1 CLEARANCE AT WATER CLOSETS. THE 2020
 FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE 604.3.1
 CLEARANCE AT WATER CLOSETS AND OVERLAP IN SECTION
 604.3.2.
  
 TOILET ROOM DOORS. 2020 FBC-ACCESSIBILITY CODE FIGURE
 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE REVIEW SECTION
 603.2.3. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OR CLEARANCES REQUIRED FOR ANY FIXTURE. DOORS
 SHALL BE PERMITTED TO SWING INTO THE REQUIRED TURNING
 SPACE. PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE
 FOR INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING. WHAT IS MISSING IS THE REQUIRED
 30X48 INCH CLEAR FLOOR SPACE BEYOND THE ARC OF THE
 DOOR. USUALLY AT A 45% ANGLE TO THE DOOR ENTRANCE.
 1ST ROUND OF COMMENTS. PROPOSED FLOOR PLAN & MEZZANINE
 PLAN, 419.1.1(3) THE NON-RESIDENTIAL AREA FUNCTION
 SHALL BE LIMITED TO THE 1ST FLOOR ONLY OF THE LIVE WORK
 UNIT.
  
 1D) 3RD REQUEST. FOR THIS TO BE A LIVE/ WORK UNIT WHERE
 IS THE KITCHEN AND WHERE ARE THE SLEEPING QUARTERS
 NETHER IS SHOWN ON THE PLANS, THE PROPOSED USE APPEARS
 TO BE A CHANGE OF USE, TO A BUSINESS OCCUPANCY. THERE
 IS A BUSINESS LICENSE TO YIGTALP LLC FOR A HAIRDRESSER,
 PLEASE UPDATE PLANS FOR A HAIR SALON.
  
 2) 2ND REQUEST. 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2A) 2ND REQUEST. 1210.2.2 WALLS & PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 2B) 2ND REQUEST. 2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
  
  
 3) ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 07:53 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-29 07:53:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061010
 ADD: 701 S OLIVE AVE. # 109
 CONT: SCALTEC USA, CORP
 TEL: 954-553-0354
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV.29TH/2022
 ACTION: DENIED
  
 1) THE COVERSHEET BUILDING DATA:
 1A) COMPLIED.
  
 1B)2ND REQUEST. THE COVERSHEET STILL STATES A MULTI USE
 RESIDENCE. PLEASE SHOW WHERE THE RESIDENCE BEDROOM,
 BATH AND KITCHEN ARE LOCATED AND WHERE NOT MORE THAN 50
 % OF THE AREA IS THE WORK AREA, PROVIDE EACH AREA IN
 SQUARE FEET FOR LIVE LOFT AND WORK AREA. IF THIS DOES
 NOT MEET THIS REQUIREMENT, THEN A ONE HOUR FIRE
 PARTITION WALL PER SECTION 420.2 OF THE 2020
 FBC-BUILDING CODE WILL BE REQUIRED. OTHERWISE AS SHOWN
 THIS IS A BUSINESS OCCUPANCY PER 304.1, FBC-BUILDING
 CODE.
  
 1ST ROUND COMMENTS. OCCUPANCY TYPE IS LISTED AS A
 RESIDENTIAL LIVE/ WORK LOFT AND REFERENCES FBC-310.4.
 PLEASE ALSO REFER TO THE CODE REQUIREMENTS FOR
 LIVE/WORK LOFTS FOUND IN SECTION 419 OF THE 2020
 FBC-BUILDING CODE. REVIEW 419.1.1(2) WHERE THE
 NONRESIDENTIAL AREA IS PERMITTED TO B NOT MORE THAN 50
 PERCENT OF THE AREA OF LIVE WORK UNIT. THE PROPOSED
 FLOOR PLAN NOR MEZZANINE FLOOR PLAN SHOW WHERE THE
 LIVING QUARTERS ARE.
  
 1C) 2ND REVIEW. PLEASE REVIEW THE 2020 FBC-BUILDING
 CODE SECTION 419.9. WHERE THE NONRESIDENTIAL AREA OF
 THE LIVE/WORK UNIT IS REQUIRED TO BE ACCESSIBLE BY THE
 FLORIDA BUILDING CODE, ACCESSIBILITY, THE PLUMBING
 FIXTURES SPECIFIED BY CHAPTER 29 SHALL BE ACCESSIBLE.
 PLEASE SHOW A BLOW UP FLOOR PLAN OF THE 1ST FLOOR
 RESTROOM WITH DIMENSIONS, AND COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTIONS:
  
 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED,
 SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH (FINISHES MAY ENCROACH) ON THE FINISH
 DIMENSION!!!
  
 603.3 MIRRORS. 2020 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 GRAB BARS/ RESTROOMS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE SIDE
 WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED
 12 INCHES MAXIMUM FROM THE REAR WALL AND EXTENDING 54
 INCHES MINIMUM FROM THE REAR WALL.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL
 NOT BE LOCATED BEHIND THE GRAB BARS.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE
 604.3.1 CLEARANCE AT WATER CLOSETS. THE 2020
 FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE 604.3.1
 CLEARANCE AT WATER CLOSETS AND OVERLAP IN SECTION
 604.3.2.
  
 TOILET ROOM DOORS. 2020 FBC-ACCESSIBILITY CODE FIGURE
 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE REVIEW SECTION
 603.2.3. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OR CLEARANCES REQUIRED FOR ANY FIXTURE. DOORS
 SHALL BE PERMITTED TO SWING INTO THE REQUIRED TURNING
 SPACE. PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE
 FOR INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING. WHAT IS MISSING IS THE REQUIRED
 30X48 INCH CLEAR FLOOR SPACE BEYOND THE ARC OF THE
 DOOR. USUALLY AT A 45% ANGLE TO THE DOOR ENTRANCE.
 1ST ROUND OF COMMENTS. PROPOSED FLOOR PLAN & MEZZANINE
 PLAN, 419.1.1(3) THE NON-RESIDENTIAL AREA FUNCTION
 SHALL BE LIMITED TO THE 1ST FLOOR ONLY OF THE LIVE WORK
 UNIT.
  
 1D) 2ND REQUEST. FOR THIS TO BE A LIVE/ WORK UNIT WHERE
 IS THE KITCHEN AND WHERE ARE THE SLEEPING QUARTERS
 NETHER IS SHOWN ON THE PLANS, THE PROPOSED USE APPEARS
 TO BE A CHANGE OF USE, TO A BUSINESS OCCUPANCY. THERE
 IS A BUSINESS LICENSE TO YIGTALP LLC FOR A HAIRDRESSER,
 PLEASE UPDATE PLANS FOR A HAIR SALON.
  
 2) NEW COMMENT. 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
  
  
 3) ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-04 Cont ID  
Sent By jwitmer Date 2022-08-04 Time 09:23 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-08-04 09:23:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061010
 ADD: 701 S OLIVE AVE. # 109
 CONT: SCALTEC USA, CORP
 TEL: 954-553-0354
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 04TH/2022
 ACTION: DENIED
  
 1) THE COVERSHEET BUILDING DATA:
 1A) CONSTRUCTION TYPE LIST THIS AS A TYPE II-A
 CONSTRUCTION. MY GEO NAV SHOWS THIS AS A 20-STORY
 BUILDING OR CONSTRUCTION TYPE I-A-UNLIMITED HEIGHT SEE
 THE 2020 FBC-B TABLE502.4.4. PLEASE CORRECT.
  
 1B) OCCUPANCY TYPE IS LISTED AS A RESIDENTIAL LIVE/
 WORK LOFT AND REFERENCES FBC-310.4. PLEASE ALSO REFER
 TO THE CODE REQUIREMENTS FOR LIVE/WORK LOFTS FOUND IN
 SECTION 419 OF THE 2020 FBC-BUILDING CODE. REVIEW
 419.1.1(2) WHERE THE NONRESIDENTIAL AREA IS PERMITTED
 TO B NOT MORE THAN 50 PERCENT OF THE AREA OF LIVE WORK
 UNIT. THE PROPOSED FLOOR PLAN NOR MEZZANINE FLOOR PLAN
 SHOW WHERE THE LIVING QUARTERS ARE.
  
 1C) PROPOSED FLOOR PLAN & MEZZANINE PLAN, 419.1.1(3)
 THE NON-RESIDENTIAL AREA FUNCTION SHALL BE LIMITED TO
 THE 1ST FLOOR ONLY OF THE LIVE WORK UNIT.
  
 1D) FOR THIS TO BE A LIVE/ WORK UNIT WHERE IS THE
 KITCHEN AND WHERE ARE THE SLEEPING QUARTERS NETHER IS
 SHOWN ON THE PLANS, THE PROPOSED USE APPEARS TO BE A
 CHANGE OF USE, TO A BUSINESS OCCUPANCY. THERE IS A
 BUSINESS LICENSE TO YIGTALP LLC FOR A HAIRDRESSER,
 PLEASE UPDATE PLANS FOR A HAIR SALON.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-04-14 Cont ID  
Sent By jleahy Date 2023-04-14 Time 15:42 Rev Time 0.00
Received By jleahy Date 2023-04-14 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-10 Cont ID  
Sent By jleahy Date 2023-03-10 Time 16:03 Rev Time 0.00
Received By jleahy Date 2023-03-10 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-12-21 Cont ID  
Sent By jleahy Date 2022-12-21 Time 12:12 Rev Time 0.00
Received By jleahy Date 2022-12-21 Time 11:54 Sent To  
Notes
2022-12-21 12:13:17NO ELECTRICAL WORK REVIEWED OR APPROVED JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jleahy Date 2022-08-05 Time 06:48 Rev Time 0.00
Received By jleahy Date 2022-08-05 Time 06:39 Sent To  
Notes
2022-08-05 06:50:42FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN, IF NO ELECTRICAL WORK TO BE
 DONE PLEASE NOT IT ON THE PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-12-30 Cont ID  
Sent By pleduc Date 2022-12-30 Time   Rev Time 0.00
Received By pleduc Date 2022-12-30 Time 11:42 Sent To  
Notes
2022-12-30 11:44:08FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By pleduc Date 2022-11-28 Time   Rev Time 0.00
Received By pleduc Date 2022-11-28 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-27 Cont ID  
Sent By pleduc Date 2022-06-27 Time   Rev Time 0.00
Received By pleduc Date 2022-06-27 Time 12:10 Sent To  
Notes
2022-06-27 13:58:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION WITHIN THE SCOPE OF WORK TO
 REMOVE INTERIOR PARTITION WALL ON FIRST FLOOR.
  
 HOWEVER,SHEET A 3 INDICATES AN INDICATION OF SCOPE OF
 WORK ONLY WITH AN ARROW AND CIRCLE AROUND 2 SINKS.
  
 PLEASE REVIEW AND CORRECT AS TO WHICH STATEMENT, (OR
 BOTH) IS ARE CORRECT AND MAKE THE APPLICABLE CHANGES.
  
  
  
 2) THERE IS AN INDICATION OF A NEW WALL ON THE
 MEZZANINE WITH AN OPENING, HOWEVER THERE ARE NO
 DIMENSIONS INDICATING THE HEIGHT AND WIDTH OF THE
 OPENING THAT MEETS THE MINIMUM MEANS OF EGRESS
 REQUIREMENTS.
  
 PLEASE PROVIDE THE DIMENSIONS.
  
  
  
 3) SHEET A 4 - THERE IS AN INDICATION OF A NEW WALL,
 HOWEVER, THERE IS NO INDICATION OF THE MODIFICATION OF
 THE FIRE SPRINKLER HEAD LOCATION/PROTECTION.
  
  
 THE REMOVAL AND CONSTRUCTION OF NEW SPACES/AREAS
 REQUIRE A REVIEW BY A FIRE SPRINKLER CONTRACTOR FOR
 MODIFICATIONS.
  
 A FIRE SPRINKLER CONTRACTOR IS REQUIRED TO REVIEW THE
 PROPOSED WORK TO ENSURE CODE COMPLIANT COVERAGE IS
 MAINTAINED.
  
 SHOULD NO WORK BE REQUIRED, A LETTER FROM THAT
 CONTRACTOR WILL BE REQUIRED TO BE SUBMITTED ON FINAL
 FIRE INSPECTIONS TO THE FIRE INSPECTOR.
  
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2023-04-20 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-18 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-04-14 Cont ID  
Sent By jleahy Date 2023-04-14 Time 15:42 Rev Time 0.00
Received By jleahy Date 2023-04-04 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-10 Cont ID  
Sent By jleahy Date 2023-03-10 Time 16:03 Rev Time 0.00
Received By jleahy Date 2023-02-14 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 10:45 Rev Time 0.00
Received By medwards Date 2023-01-24 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-12 Cont ID  
Sent By medwards Date 2023-01-12 Time 16:28 Rev Time 0.00
Received By medwards Date 2022-12-29 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-21 Cont ID  
Sent By jleahy Date 2022-12-21 Time 12:15 Rev Time 0.00
Received By jleahy Date 2022-11-23 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-08 Cont ID  
Sent By medwards Date 2022-08-08 Time 09:09 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 14:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2023-04-13 Cont ID  
Sent By lmarchan Date 2023-04-13 Time 15:57 Rev Time 0.00
Received By lmarchan Date 2023-03-10 Time 16:12 Sent To  
Notes
2023-04-11 16:19:39RECEIPT MU 2023-012412-0000 - $5,235.53 PAID AO
2023-03-10 16:12:19EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-01-26 Cont ID  
Sent By jwitmer Date 2023-01-26 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2023-01-26 Time 10:50 Sent To  
Notes
2023-01-26 10:49:04IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-04 Cont ID  
Sent By jwitmer Date 2022-08-04 Time 09:21 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-08-04 09:21:08IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2023-04-04 Cont ID  
Sent By medwards Date 2023-04-04 Time 11:24 Rev Time 0.00
Received By medwards Date 2023-04-04 Time 11:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 15:12 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 15:12 Sent To  
Notes
2023-02-27 15:12:48PROVIDE DRAWINGS WITH THE DIGITAL SIGNATURE OF THE
 DESIGNER OR PROVIDE THE ORIGIANL WET SEAL STAMPED AND
 SIGNED DRAWINGS. THE DRAWINGS SUBMITTED APPEAR TO BE
 COPIES OF THE SET SEAL AND SIGNATURE OF THE DESIGNER.FS
 471/481

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 10:41 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 10:41 Sent To  
Notes
2023-01-31 10:42:064TH REVIEW FMC
 PERMIT: 22061010
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS
 NOW INDICATED BARBER SHOP. THE PREVIOUS SUBMITTAL DID
 SHOW MANICURE STATIONS. FMC TABLE 403.3.1.1
  
 2) THE REVIEWER NOTES SUBMITTED THIS CYCLE HAS A
 MECHANICAL REVIEW DATE OF 08/08/2022, THIS IS NOT THE
 MOST RECENT REVIEW COMMENTS. THE MOST RECENT MECHANICAL
 REVIEW COMMENTS ARE DATED 1/12/2023 AND THERE ARE 6
 COMMENTS THAT WOULD NEED TO BE ADDRESSED. PLEASE SEE
 BELOW:
 3RD REVIEW FMC
 PERMIT: 22061010
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I CANNOT DO A COMPLETE REVIEW UNTIL A COMPLETE
 DESIGN FOR THIS TENANT IS DESIGNED AND SUBMITTED.
  
 2) THE PERMIT APPLICATION SHOULD REFLECT WHAT IS BEING
 BROUGHT INTO THIS TENANT SPACE. CORRECT THE
 APPLICATION.
  
 3) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW
 TENANT. THE UPSTAIRS WAS FOR THE LIVE AND THE MAIN
 FLOOR WAS FOR THE BUSINESS. IT APPEARS THAT NOW THE
 ENTIRE TENANT SPACE IS TO BE A BEAUTY SALON WITH
 MANICURE STATIONS. THIS REQUIRES MORE EXHAUST THAN THE
 ORIGINAL DESIGN OF THIS SPACE HAS NOW. FBC 107.3.5
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THIS CHANGE
 OF USE. PROVIDE A COMPLETE EXHAUST DESIGN FOR THE
 MANICURE STATIONS. IS THERE TO BE PEDICURE STATIONS AS
 WELL? IF SO SHOW THE DESIGN FOR THIS AS WELL.
 502.20 MANICURE AND PEDICURE STATIONS. MANICURE AND
 PEDICURE STATIONS SHALL BE PROVIDED WITH AN EXHAUST
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1, NOTE H.
 MANICURE TABLES AND PEDICURE STATIONS NOT PROVIDED WITH
 FACTORY-INSTALLED EXHAUST INLETS SHALL BE PROVIDED WITH
 EXHAUST INLETS LOCATED NOT MORE THAN 12 INCHES (305 MM)
 HORIZONTALLY AND VERTICALLY FROM THE POINT OF CHEMICAL
 APPLICATION.
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE ENTIRE
 TENANT SPACE FOR EACH USE OF SPACE. USE THE OCCUPANCY
 CLASSIFICATION FROM TABLE 403.3.1.1 FOR THE OCCUPANCY
 USE OF EACH SPACE.
  
 5) THE UPSTAIRS BATHROOM APPEARS TO NOW BE FOR THE
 PUBLIC. SHOW THAT THE BATHROOM EXHAUST FAN WILL MEET
 THE EXHAUST REQUIREMENTS FROM TABLE 403.3.1.1
  
 6) THE NEW O/A GRILL APPEARS TO BE COMING FROM THE A/C
 CLOSET. HOW IS THIS OUTDOOR AIR BEING CONDITIONED?
 TYPICALLY, THE OUTDOOR AIR IS BROUGHT INTO THE RETURN
 AIR DUCT AT THE MECHANICAL SYSTEM FROM THE EXTERIOR OF
 THE BUILDING. SHOW THE DUCT SIZE ON THE DRAWING FOR THE
 OUTDOOR AIR. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-12 Cont ID  
Sent By medwards Date 2023-01-12 Time 16:27 Rev Time 0.00
Received By medwards Date 2023-01-12 Time 16:27 Sent To  
Notes
2023-01-12 16:27:223RD REVIEW FMC
 PERMIT: 22061010
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I CANNOT DO A COMPLETE REVIEW UNTIL A COMPLETE
 DESIGN FOR THIS TENANT IS DESIGNED AND SUBMITTED.
  
 2) THE PERMIT APPLICATION SHOULD REFLECT WHAT IS BEING
 BROUGHT INTO THIS TENANT SPACE. CORRECT THE
 APPLICATION.
  
 3) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW
 TENANT. THE UPSTAIRS WAS FOR THE LIVE AND THE MAIN
 FLOOR WAS FOR THE BUSINESS. IT APPEARS THAT NOW THE
 ENTIRE TENANT SPACE IS TO BE A BEAUTY SALON WITH
 MANICURE STATIONS. THIS REQUIRES MORE EXHAUST THAN THE
 ORIGINAL DESIGN OF THIS SPACE HAS NOW. FBC 107.3.5
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THIS CHANGE
 OF USE. PROVIDE A COMPLETE EXHAUST DESIGN FOR THE
 MANICURE STATIONS. IS THERE TO BE PEDICURE STATIONS AS
 WELL? IF SO SHOW THE DESIGN FOR THIS AS WELL.
 502.20 MANICURE AND PEDICURE STATIONS. MANICURE AND
 PEDICURE STATIONS SHALL BE PROVIDED WITH AN EXHAUST
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1, NOTE H.
 MANICURE TABLES AND PEDICURE STATIONS NOT PROVIDED WITH
 FACTORY-INSTALLED EXHAUST INLETS SHALL BE PROVIDED WITH
 EXHAUST INLETS LOCATED NOT MORE THAN 12 INCHES (305 MM)
 HORIZONTALLY AND VERTICALLY FROM THE POINT OF CHEMICAL
 APPLICATION.
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE ENTIRE
 TENANT SPACE FOR EACH USE OF SPACE. USE THE OCCUPANCY
 CLASSIFICATION FROM TABLE 403.3.1.1 FOR THE OCCUPANCY
 USE OF EACH SPACE.
  
 5) THE UPSTAIRS BATHROOM APPEARS TO NOW BE FOR THE
 PUBLIC. SHOW THAT THE BATHROOM EXHAUST FAN WILL MEET
 THE EXHAUST REQUIREMENTS FROM TABLE 403.3.1.1
  
 6) THE NEW O/A GRILL APPEARS TO BE COMING FROM THE A/C
 CLOSET. HOW IS THIS OUTDOOR AIR BEING CONDITIONED?
 TYPICALLY THE OUTDOOR AIR IS BROUGHT INTO THE RETURN
 AIR DUCT AT THE MECHANICAL SYSTEM FROM THE EXTERIOR OF
 THE BUILDING. SHOW THE DUCT SIZE ON THE DRAWING FOR THE
 OUTDOOR AIR. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 10:38 Rev Time 0.00
Received By medwards Date 2022-12-14 Time 10:38 Sent To  
Notes
2022-12-14 11:00:52PLEASE ADDRESS FIRST CYCLE COMMENTS LISTED BELOW:
  
  
 2) WHAT IS THE PREVIOUS USE OF SPACE IN THE WORK AREA?
  
 3) IS THE NEW WORK AREA TO BE A BEAUTY SALON? IF SO
 PROVIDE THE OUTDOOR AIR AND EXHAUST CALCULATIONS FOR
 THIS BEAUTY SALON. FMC 403.3.1.1
  
 PLEASE ADD EXPLAINATORY NOTES TO THE SUBMITTED M-1
 SHEET. IT IS UNCLEAR TO THIS REVIEWER AS TO HOW THE O/A
 IS BEING INTRODUCED TO THIS UNIT. IT APPEARS THAT IT IS
 NOT BEING INTRODUCED INTO THE MECHANICAL SYSTEM. PLEASE
 SHOW THAT THIS O/A DUCT IS TO BE CONNECTED TO THE
 MECHANICAL SYSTEM RETURN. FMC 403.3.1.1
  
 PROVIDE A DETAIL FOR THE NEW 360 CFM EXHAUST FAN TYING
 INTO THE EXHISTING EXHAUST VENT SHAFT. EXPLAIN WHY 360
 CFM'S OF EXHAUST IS REQUIRED. FBC 107.3.5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-08 Cont ID  
Sent By medwards Date 2022-08-08 Time 08:57 Rev Time 0.00
Received By medwards Date 2022-08-08 Time 08:57 Sent To  
Notes
2022-08-08 09:08:431) A-1- EXISTING FLOOR PLAN DOES NOT MATCH A-2-
 EXISTING MEZZANINE PLAN. PLEASE PROVIDE ACCURATE PLANS.
 FBC 107.2.1
  
 2) WHAT IS THE PREVIOUS USE OF SPACE IN THE WORK AREA?
  
 3) IS THE NEW WORK AREA TO BE A BEAUTY SALON? IF SO
 PROVIDE THE OUTDOOR AIR AND EXHAUST CALCULATIONS FOR
 THIS BEAUTY SALON. FMC 403.3.1.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2023-04-20 Cont ID  
Sent By ccole Date 2023-04-20 Time 15:36 Rev Time 0.00
Received By ccole Date 2023-04-20 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2023-04-11 Cont ID  
Sent By ccole Date 2023-04-11 Time 15:30 Rev Time 0.00
Received By ccole Date 2023-04-11 Time 15:17 Sent To  
Notes
2023-04-11 15:34:594TH REVIEW FBC-2020 PLUMBING
 PERMIT-22061010
 4/11/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED P-1 PLAN IS MISSING THE SANITARY
 RISER, THE FIXTURE SCHEDULE, AND THE PLUMBING NOTES.
 ALL OF THESE ITEMS ARE REQUIRED FOR PLUMBING PLAN
 APPROVAL, AND ALL WERE ON THE PREVIOUS PLAN- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
 CHRISTOPHER L. COLE
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-01-27 Cont ID  
Sent By ccole Date 2023-01-27 Time 11:01 Rev Time 0.00
Received By ccole Date 2023-01-27 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-09 Cont ID  
Sent By ccole Date 2023-01-09 Time 11:31 Rev Time 0.00
Received By ccole Date 2023-01-09 Time 10:50 Sent To  
Notes
2023-01-09 12:00:193RD REVIEW FBC-2020 PLUMBING
 PERMIT-22061010
 1/9/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) C-1 COVER SHEET: THE REVISED PLAN IS INDICATING BOTH
 B AND R-2 FOR THE SPACE. PLEASE CLARIFY IF THE UNIT OR
 PORTION OF THE UNIT IS UNDERGOING A CHANGE OF OCCUPANCY
 AS DEFINED IN SEC. 202 FBC EX. BASED ON THE BUILDING
 REVIEWER???S COMMENTS REQUIRING THE FIRST FLOOR
 BATHROOM TO HAVE ACCESSIBLE FIXTURES, THE PLUMBING
 REVIEW IS TEMPORARILY STOPPED PENDING RESUBMITTAL OF
 CORRECTED PLANS.
 PLEASE NOTE THAT AN ENLARGED BATHROOM FLOOR PLAN AND
 DETAILS PER THE BUILDING REVIEWER???S COMMENTS WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
 CHRISTOPHER L. COLE
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-12-08 Cont ID  
Sent By ccole Date 2022-12-08 Time 09:47 Rev Time 0.00
Received By ccole Date 2022-12-07 Time 16:30 Sent To  
Notes
2022-12-08 09:46:572ND REVIEW FBC-2020 PLUMBING
 PERMIT-22061010
 12/8/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: THE RESUBMITTED PLAN IS SHOWING MOEN
 SHOWER VALVES TO BE INSTALLED AS MIXING VALVES FOR THE
 SHAMPOO SINKS WHICH ARE NOT IN COMPLIANCE WITH SEC.
 607.1.1 FBC P AND 412.10 HEAD SHAMPOO SINK FAUCETS.
 HEAD SHAMPOO SINK FAUCETS SHALL BE SUPPLIED WITH HOT
 WATER THAT IS LIMITED TO A MAXIMUM TEMPERATURE OF
 120??F BY A WATER-TEMPERATURE-LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. EACH FAUCET SHALL
 HAVE INTEGRAL CHECK VALVES TO PREVENT CROSSOVER FLOW
 BETWEEN THE HOT AND COLD WATER SUPPLY CONNECTIONS.
  
 2) BASED ON THE BUILDING REVIEWER'S COMMENTS REQUIRING
 ACCESSIBLE BATHROOM FIXTURES IT APPEARS CHANGES WILL BE
 MADE TO DRAWINGS WHICH WILL REQUIRE FURTHER PLUMBING
 REVIEW- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By ccole Date 2022-06-28 Time 13:59 Rev Time 0.00
Received By ccole Date 2022-06-28 Time 12:16 Sent To  
Notes
2022-06-28 14:00:161ST REVIEW FBC-2020 PLUMBING
 PERMIT-22061160
 6/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: PROVIDE A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE AT THE SINKS- SEC. 607.1.1 FBC P.
 PLEASE NOTE THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING MEANS.
  
 2) P-1: PROVIDE A FIXTURE SCHEDULE ON THE PLAN THAT
 INCLUDES THE SINKS AND THE FAUCETS- SECS. 422.1 & 412.1
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-04-20 Cont ID  
Sent By ccole Date 2023-04-20 Time 15:36 Rev Time 0.00
Received By ccole Date 2023-04-20 Time 15:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-04-14 Cont ID  
Sent By jleahy Date 2023-04-14 Time 15:42 Rev Time 0.00
Received By jleahy Date 2023-04-14 Time 15:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 15:13 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 15:13 Sent To  
Notes
2023-02-27 15:13:32SEE PREVIOUS REVIEW COMMENT BELOW:
  
 PROVIDE DRAWINGS WITH THE DIGITAL SIGNATURE OF THE
 DESIGNER OR PROVIDE THE ORIGIANL WET SEAL STAMPED AND
 SIGNED DRAWINGS. THE DRAWINGS SUBMITTED APPEAR TO BE
 COPIES OF THE SET SEAL AND SIGNATURE OF THE DESIGNER.FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 10:43 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 10:43 Sent To  
Notes
2023-01-31 10:45:15PROVIDE DRAWINGS WITH THE DIGITAL SIGNATURE OF THE
 DESIGNER OR PROVIDE THE ORIGIANL WET SEAL STAMPED AND
 SIGNED DRAWINGS. THE DRAWINGS SUBMITTED APPEAR TO BE
 COPIES OF THE SET SEAL AND SIGNATURE OF THE DESIGNER.FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-30 Cont ID  
Sent By mpeterso Date 2022-12-30 Time 08:57 Rev Time 0.00
Received By mpeterso Date 2022-12-30 Time 08:57 Sent To  
Notes
2022-12-30 08:59:1312/30/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By jleahy Date 2022-12-21 Time 12:15 Rev Time 0.00
Received By jleahy Date 2022-12-21 Time 12:15 Sent To  
Notes
2022-12-21 12:15:38SEE REVIEW FROM 8/3/22 JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By rwbrown Date 2022-08-03 Time 06:25 Rev Time 0.00
Received By jleahy Date 2022-12-21 Time 12:14 Sent To  
Notes
2022-08-03 06:25:48ALL PAGES ARE NOT ELECTRONICALLY SIGNED/SEALED
  
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  