Plan Review Stops For Permit 22060913 |
Review Stop |
AD |
ADDRESSING |
Rev No |
5 |
Status |
F |
Date |
2023-07-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-07-14 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-07-14 |
Time |
08:02 |
Sent To |
|
|
Notes |
2023-07-14 08:03:00 | WAITING ON ZONING TO APPROVE THEIR REVIEW, ONCE ZONING | | APPROVES THEIR REVIEW CONTACT ADDRESSING | | [email protected] OR CALL 561-805-6659 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
4 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-02 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-02 |
Time |
13:15 |
Sent To |
|
|
Notes |
2023-05-02 13:16:34 | WAITING ON ZONING TO APPROVE THEIR REVIEW, ONCE ZONING | | APPROVES THEIR REVIEW CONTACT ADDRESSING | | [email protected] OR CALL 561-805-6659 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
F |
Date |
2023-01-24 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-01-24 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-01-24 |
Time |
16:28 |
Sent To |
|
|
Notes |
2023-01-24 16:28:45 | SCOPE OF WORK IS FOR AN ADDITIONAL UNIT, PLEASE CONTACT | | [email protected] OR CALL 561-805-6659 FOR THE | | BUILDING TO BE ISSUED AN ADDRESSES, ONCE ZONING | | APPROVED THE ADDITIONAL UNIT. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-09-29 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-09-29 |
Time |
08:46 |
Sent To |
|
|
Notes |
2022-09-29 08:47:44 | SCOPE OF WORK IS FOR AN ADDITIONAL UNIT, PLEASE CONTACT | | [email protected] OR CALL 561-805-6659 FOR THE | | BUILDING TO BE ISSUED AN ADDRESSES, ONCE ZONING | | APPROVED THE ADDITIONAL UNIT. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-06-30 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-06-30 |
Time |
12:51 |
Sent To |
|
|
Notes |
2022-06-30 12:55:00 | SCOPE OF WORK IS FOR AN ADDITIONAL UNIT, PLEASE CONTACT | | [email protected] OR CALL 561-805-6659 FOR THE | | BUILDING TO BE ISSUED AN ADDRESSES, ONCE ZONING | | APPROVED THE ADDITIONAL UNIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-07-24 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-07-24 |
Time |
08:52 |
Sent To |
|
|
Notes |
2023-07-24 10:30:20 | NEW SINGLE FAMILY RESIDENCE(R3) FIFTH BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | 922 AVON RD | | | | | | PROVISO NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR | | PRODUCT APPROVALS DEFERRED SUBMITTAL). | | | | ***IMPORTANT | | ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED | | AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | BEFORE PERMIT ISSUANCE. | | | | | | PREVIOUS COMMENT: | | 2- ENERGY CALCULATIONS SUBMITTED: | | D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | PREVIOUS COMMENTS: | | 16- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | RESPONSE: | | NOT ADDRESSED AT ALL. IS IT GOING TO BE A DEFERRED | | SUBMITTAL? | | | | B)SLIDING GLASS DOORS. | | | | RESPONSE: | | PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN | | WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD | | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | C)SINGLE HUNG WINDOWS. | | | | RESPONSE: | | PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN | | WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD | | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | D)ENTRY DOOR. | | | | RESPONSE: | | REPEAT COMMENT. NO SUBMITTED AND PRODUCT APPROVAL NEEDS | | TO BE REVIEWED AND APPROVED IN WRITING (NOT SIGNING AND | | SEALING) BY DESIGNER OF RECORD AS REQUIRED BY SEC. | | 107.3.4.1 CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2023-05-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-05-11 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-05-11 |
Time |
13:51 |
Sent To |
|
|
Notes |
2023-05-11 17:53:28 | NEW SINGLE FAMILY RESIDENCE(R3) FOURTH BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | 922 AVON RD | | | | ORIGINAL COMMENT: | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | CONFLICTS/DELAYS. | | | | PREVIOUS COMMENT: | | RESPONSE: [ COMMENTS NOT ADDRESSED.] | | ENERGY CALCULATIONS SUBMITTED: | | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM | | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS | | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO | | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED. | | | | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED. | | | | C)CEILING INFORMATION ON ITEM #11 DOESN'T MATCH PLANS. | | PLANS SHOW VENTED ATTIC AND ROOF INSULATION. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED. | | | | D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED. | | | | E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY | | CONSERVATION. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED. | | | | NEW COMMENT BASED ON REVISED PLANS: | | F)REVISE SPACES INFORMATION ON PAGE 2. NEW PLANS DON'T | | SHOW A KITCHEN ANYMORE. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | 7- GUEST HOUSE ROOF FRAME DETAIL PLAN. | | ORIGINAL COMMENT: | | D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO | | COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. | | SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: | | NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO | | BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS | | REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 | | FBC-RESIDENTIAL. | | | | PREVIOUS COMMENT: | | RESPONSE: [ NOT RESOLVED.] | | ROOF SHEATHING SPECIFICATIONS SHOWN ON THE COMPONENT | | AND CLADDING PRESSURE ZONES ON SHEET S.3. DON'T COMPLY | | WITH TABLE R803.2.3.1 FBC-RESIDENTIAL. REVISE AS | | REQUIRED. | | NOTE: COORDINATE WITH ITEM 4(B) ABOVE. | | | | NEW RESPONSE ON 05/11/23: | | NEW DESIGNER OF RECORD. REVISE THE ROOF NAILING PATTERN | | SPECIFIED ON SHEET S-3 UNDER "MAX. COMPONENTS AND | | CLADDING DESIGN WIND PRESSURES". SPECIFICATIONS ARE | | INCOMPLETE. IT ONLY SPECIFIES THE SPACING AT THE EDGE. | | NEED TO PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS | | FOR ALL ROOF ZONES. TABLE R803.2.3.1 FBC-RESIDENTIAL. | | NOTE: PLYWOOD ROOF SHEATHING NAILING IS REQUIRED ALL | | THE TIME. IT IS NOT CLEAR WHY ARCHITECT WROTE NOTE "IF | | REQUIRED". CLARIFY AS REQUIRED. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | ORIGINAL COMMENTS: | | 16- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | ORIGINAL COMMENT: | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | PREVIOUS COMMENT: | | RESPONSE: [ NOT RESOLVED. THE C & C PRESSURES SPECIFIED | | ON SHEET S.1 FOR THE DOORS AND WINDOWS ARE QUITE HIGH | | FOR A BUILDING LESS THAN 15 FT IN HEIGHT. ] | | REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT | | SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED | | SUBMITTAL. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT | | SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED | | SUBMITTAL. | | NOTE: PRODUCT APPROVAL NEEDS TO BE REVIEWED AND | | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY | | DESIGNER OF RECORD AS REQUIRED BY SEC. 107.3.4.1 CITY | | AMENDMENTS. | | | | PREVIOUS COMMENT: | | B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | NEW RESPONSE ON 05/11/23: | | PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN | | WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD | | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PREVIOUS COMMENT: | | C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | NEW RESPONSE ON 05/11/23: | | PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN | | WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD | | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PREVIOUS COMMENT: | | D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED | | BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING. | | | | NEW RESPONSE ON 05/11/23: | | REPEAT COMMENT. NO SUBMITTED AND PRODUCT APPROVAL NEEDS | | TO BE REVIEWED AND APPROVED IN WRITING (NOT SIGNING AND | | SEALING) BY DESIGNER OF RECORD AS REQUIRED BY SEC. | | 107.3.4.1 CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | NEW COMMENTS BASED ON REVISED DRAWINGS BY NEW DESIGNER | | OF RECORD: | | 18- FLOOR PLAN LAYOUT WAS CHANGED BUT NEW ELECTRICAL, | | PLUMBING AND MECHANICAL PLANS WERE NOT SUBMITTED. NEED | | TO PROVIDE REVISED PLANS FOR ALL TRADES. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 19- REVISE THE ROOF DESIGN PRESSURES SPECIFIED ON SHEET | | S-3 UNDER "MAX. COMPONENTS AND CLADDING DESIGN WIND | | PRESSURES". SPECIFICATIONS ARE TOO LOW FOR BUILDING | | EXPOSURE "C". | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | 20- REVISE VENTING SPECIFICATIONS ON THE TYPICAL WALL | | SECTION ON SHEET S-2. | | 7"X24" VENTS AT 4'-0" O.C. DON'T ALLOW CROSS | | VENTILATION. THE ROOF IS FRAMED WITH 2X10'S AT 16" | | O.C.. REVISE AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-02-17 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-02-17 |
Time |
07:50 |
Sent To |
|
|
Notes |
2023-02-17 10:57:56 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | 922 AVON RD | | 3RD REVIEW (BY: ROBERT MCDOUGAL) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | 922 AVON RD | | | | ORIGINAL COMMENT: | | 1- OK | | | | ORIGINAL COMMENT: | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | CONFLICTS/DELAYS. | | | | RESPONSE: [ COMMENTS NOT ADDRESSED.] | | ENERGY CALCULATIONS SUBMITTED: | | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM | | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS | | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO | | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | C) OK | | | | D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY | | CONSERVATION. | | | | 3- OK. | | | | 4- WIND LOAD SCHEDULE. | | A)OK. | | | | ORIGINAL COMMENT: | | B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE | | DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS | | SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF | | CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED | | ROOF TYPE. | | | | RESPONSE: [ NOT RESOLVED. THE ROOF WINDLOAD SCHEDULE | | AND DIAGRAM ON S.3 IS ILLEGIBLE.] | | ROOFS DIAGRAMS SHOWN ON NEW SHEET S.3 DON'T MATCH | | CURRENT CODE REVISED FIGURE R301.2(7) FBC-RESIDENTIAL. | | REVISE AS REQUIRED. SHOW ALL NEW ZONES. | | | | 5- GUEST HOUSE DIMENSIONS FLOOR PLAN: | | ORIGINAL COMMENT: [ NOT RESOLVED.] | | A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH | | OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. | | REVISE AS REQUIRED. | | | | RESPONSE: | | COORDINATE WITH ITEM 5(B) BELOW. | | | | ORIGINAL COMMENT: | | B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE | | INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS. | | | | RESPONSE: [ NOT RESOLVED.] | | DOORS/WINDOWS SHOWN ON THE DOOR/WINDOW SCHEDULES ARE | | NOT KEYED ON THE FLOOR PLAN. CLEARLY KEY THEM ON BOTH | | TO AVOID CONFLICTS/CONFUSION. IT LOOKS LIKE THE ENTRY | | DOOR IS SPECIFIED AS 32" X84" ALU DOOR. THIS DOOR | | DOESN'T COMPLY WITH THE REQUIRED EGRESS DOOR. ALSO, | | NEED TO REVISE THE DOOR OPENING DIMENSION SHOWN ON THE | | GUEST HOUSE DIMENSION FLOOR PLAN. | | NOTE: COORDINATE INFORMATION ON GUEST HOUSE DIMENSION | | FLOOR PLAN, DOOR AND WINDOW SCHEDULES (CHECK SIZES) AND | | NEW PLAN VIEW ON SHEET S.1 TO AVOID MORE | | CONFLICTS/DELAYS. | | | | ORIGINAL COMMENT: | | C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A | | DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED | | BY SEC. R320.1.1 FBC-RESIDENTIAL. | | | | RESPONSE: [ NOT RESOLVED.] | | 30" DOOR DOESN'T COMPLY. REVISE AS REQUIRED. NEED DOOR | | THAT PROVIDES 29" MIN. CLEAR OPENING. REVISE AS | | REQUIRED. TYPICALLY 32" DOORS ARE THE ONES COMPLYING. | | | | 6- OK | | | | 7- GUEST HOUSE ROOF FRAME DETAIL PLAN. | | | | ORIGINAL COMMENT: | | D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO | | COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. | | SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: | | NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO | | BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS | | REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 | | FBC-RESIDENTIAL. | | | | RESPONSE: [ NOT RESOLVED.] | | SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING | | PRESSURE ZONES ON SHEET S.3. DON'T COMPLY WITH TABLE | | R803.2.3.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. | | NTE: COORDINATE WITH ITEM 4(B) ABOVE. | | | | 8-12 OK. | | | | 13- OK. | | | | 14- OK | | | | 15- OK. | | | | 16- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | ORIGINAL COMMENT: | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | RESPONSE: [ NOT RESOLVED. THE C & C PRESSURES SPECIFIED | | ON SHEET S.1 FOR THE DOORS AND WINDOWS ARE QUITE HIGH | | FOR A BULDING LESS THAN 15 FT IN HEIGHT. ] | | REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT | | SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED | | SUBMITTAL. | | | | B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED | | BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING. | | | | ORIGINAL COMMENT: | | 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | RESPONSE: [ NOT RESOLVED.] | | REPEAT COMMENT. | | | | NEW COMMENTS BASED ON REVISED DRAWINGS: | | 18- OK | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-10-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-21 |
Time |
17:38 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-20 |
Time |
18:17 |
Sent To |
|
|
Notes |
2022-10-21 17:38:49 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | 922 AVON RD | | | | ORIGINAL COMMENT: | | 1- LOT DRAINAGE | | PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE | | DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT | | WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. | | 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | ADJACENT PROPERTIES. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | ORIGINAL COMMENT: | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | CONFLICTS/DELAYS. | | | | RESPONSE: | | ENERGY CALCULATIONS SUBMITTED: | | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM | | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS | | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO | | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | C)CEILING INFORMATION ON ITEM #11 DOESN'T MATCH PLANS. | | PLANS SHOW VENTED ATTIC AND ROOF INSULATION. | | NOTE: COORDINATE WITH ENGINEER OF RECORD BECAUSE PLANS | | WILL NEED TO BE REVISED. THEY ARE NO CORRECT ON TYPE OF | | VENTILATION AND CEILING INSULATION. SEE COMMENTS BELOW. | | | | D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | CONSERVATION. | | | | E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY | | CONSERVATION. | | | | 3- OK. | | | | 4- WIND LOAD SCHEDULE. | | A)OK. | | | | ORIGINAL COMMENT: | | B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE | | DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS | | SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF | | CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED | | ROOF TYPE. | | | | RESPONSE: | | ROOFS DIAGRAMS SHOWN ON NEW SHEET S.3 DON'T MATCH | | CURRENT CODE REVISED FIGURE R301.2(7) FBC-RESIDENTIAL. | | REVISE AS REQUIRED. SHOW ALL NEW ZONES. | | | | 5- GUEST HOUSE DIMENSIONS FLOOR PLAN: | | ORIGINAL COMMENT: | | A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH | | OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. | | REVISE AS REQUIRED. | | | | RESPONSE: | | COORDINATE WITH ITEM 5(B) BELOW. | | | | ORIGINAL COMMENT: | | B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE | | INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS. | | | | RESPONSE: | | DOORS/WINDOWS SHOWN ON THE DOOR/WINDOW SCHEDULES ARE | | NOT KEYED ON THE FLOOR PLAN. CLEARLY KEY THEM ON BOTH | | TO AVOID CONFLICTS/CONFUSION. IT LOOKS LIKE THE ENTRY | | DOOR IS SPECIFIED AS 32" X84" ALU DOOR. THIS DOOR | | DOESN'T COMPLY WITH THE REQUIRED EGRESS DOOR. ALSO, | | NEED TO REVISE THE DOOR OPENING DIMENSION SHOWN ON THE | | GUEST HOUSE DIMENSION FLOOR PLAN. | | NOTE: COORDINATE INFORMATION ON GUEST HOUSE DIMENSION | | FLOOR PLAN, DOOR AND WINDOW SCHEDULES (CHECK SIZES) AND | | NEW PLAN VIEW ON SHEET S.1 TO AVOID MORE | | CONFLICTS/DELAYS. | | | | ORIGINAL COMMENT: | | C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A | | DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED | | BY SEC. R320.1.1 FBC-RESIDENTIAL. | | | | RESPONSE: | | 30" DOOR DOESN???T COMPLY. REVISE AS REQUIRED. NEED | | DOOR THAT PROVIDES 29" MIN. CLEAR OPENING. REVISE AS | | REQUIRED. TYPICALLY 32" DOORS ARE THE ONES COMPLYING. | | | | ORIGINAL COMMENT: | | 6- PLOT PLAN 1/S1 ON SHEET 1/5: SPECIFY NEW HOUSE | | CONSTRUCTION SETBACKS TO PROPERTY LINES AND EXISTING | | MAIN HOUSE. SEC. 107.2.1 CITY AMENDMENTS. | | | | RESPONSE: | | HOUSE GUEST HOUSE ADDITION LAYOUT SUBMITTED IS TOO | | SCHEMATIC. PROVIDE COMPLETE SITE PLAN BASED ON SURVEY | | SHOWING ACTUAL DIMENSIONS. SEC. 107.3.5.3 CITY | | AMENDMENTS. | | | | 7- GUEST HOUSE ROOF FRAME DETAIL PLAN. | | | | ORIGINAL COMMENT: | | D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO | | COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. | | SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: | | NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO | | BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS | | REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 | | FBC-RESIDENTIAL. | | | | RESPONSE: | | SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING | | PRESSURE ZONES ON SHEET S.3. DON'T COMPLY WITH TABLE | | R803.2.3.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. | | NTE: COORDINATE WITH ITEM 4(B) ABOVE. | | | | 8-12 OK. | | | | ORIGINAL COMMENT: | | 13-R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF JOIST. | | REVISE AS REQUIRED. COORDINATE WITH SPECIFIED CROSS | | VENTILATION. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | RESPONSE: | | REVISED DRAWINGS DON'T PROVIDE ANY INFORMATION FOR | | CEILING INSULATION. | | REVISE TYPICAL WALL SECTION TO INCLUDE: | | A)CEILING INSULATION TYPE AND R-VALUE. | | B)WALL INSULATION TYPE AND R-VALUE. | | | | ORIGINAL COMMENT: | | 14- ENGINEER OF RECORD TO SPECIFY ROOF CROSS | | VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. | | NOTE: R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF | | JOISTS. ALSO, IT DOESN'T ALLOW ROOF CROSS VENTILATION. | | SEC. R806.3 FBC-RESIDENTIAL. | | ENGINEER MAY DESIGN AN UNVENTED ATTIC. SEE SEC. R806.5 | | FBC-RESIDENTIAL AND PROVIDE COMPLETE SPECS SHOWING HOW | | DOING IT. | | | | RESPONSE: | | SPECIFY ROOF CROSS VENTILATION TO COMPLY WITH SEC. R806 | | FBC-RESIDENTIAL. SPECIFY VENT SIZE AND LOCATION. SEE | | INSULATION CLEARANCE FOR CROSS VENTILATION. CHECK ROOF | | JOIST SIZE. IF SPECIFYING UNVENTED ATTIC PROVIDE | | COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL. IF USING | | FOAM INSULATION, THEN PROVIDE ICC EVALUATION REPORT | | REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD. | | | | 15- OK. | | | | 16- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | ORIGINAL COMMENT: | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT | | SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED | | SUBMITTAL. | | | | B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES | | CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 | | DRAWING. | | | | D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED | | BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING. | | | | ORIGINAL COMMENT: | | 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | RESPONSE: | | REPEAT COMMENT. | | | | NEW COMMENTS BASED ON REVISED DRAWINGS: | | 18- THIS IS NOT ALTERATION LEVEL 2, THIS IS NEW | | CONSTRUCTION. REVISE INFORMATION ON SHEET 2/7 AND SHEET | | S.1. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-08-01 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-08-01 |
Time |
17:17 |
Sent To |
|
|
Notes |
2022-08-01 17:20:13 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22060913 | | | | 1- LOT DRAINAGE | | PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE | | DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT | | WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. | | 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | ADJACENT PROPERTIES. | | | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | CONFLICTS/DELAYS. | | | | 3- FOUNDATION PLAN: | | A)PROVIDE COMPLETE FOUNDATION PLAN. SEC. R401.2 | | FBC-RESIDENTIAL. | | | | B) SPECIFY MIN. DEPTH AS REQUIRED BY SEC. R403.1.4 | | FBC-RESIDENTIAL. | | NOTE: COORDINATE WITH THE WALL SECTION. SHOW DEPTH ON | | THE WALL SECTION IN RELATION TO THE FINISH GRADE. | | | | 4- WIND LOAD SCHEDULE ON SHEET 1/5: | | A)DESIGN PRESSURES ARE TOO LOW. THE EFFECTIVE WIND AREA | | IS TOO LARGE. SEE FOOTNOTES ON TABLE R301.2(2) | | FBC-RESIDENTIAL AND REVISE AS REQUIRED. ALSO, THERE IS | | A NOTE AT THE BOTTOM RIGHT OF THE TABLE ON SHEET 1/5 | | STATING "AREA OF COMPONENTS= 50SQF". REVISE THIS NOTE | | AS WELL. | | | | B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE | | DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS | | SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF | | CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED | | ROOF TYPE. | | | | 5- GUEST HOUSE DIMENSIONS PLAN ON SHEET 2/5: | | A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH | | OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. | | REVISE AS REQUIRED. | | | | B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE | | INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS. | | | | C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A | | DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED | | BY SEC. R320.1.1 FBC-RESIDENTIAL. | | | | D) PROVIDE COMPLETE DIMENSIONS FOR LOCATION OF DOORS, | | WINDOWS, HALLWAY WIDTH BETWEEN BATHROOM AND BEDROOM, | | CLOSET DEPTH, KITCHEN COUNTER-TOPS, ETC. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 6- PLOT PLAN 1/S1 ON SHEET 1/5: SPECIFY NEW HOUSE | | CONSTRUCTION SETBACKS TO PROPERTY LINES AND EXISTING | | MAIN HOUSE. SEC. 107.2.1 CITY AMENDMENTS. | | | | 7- GUEST HOUSE ROOF FRAME DETAIL PLAN ON SHEET 2/5: | | A) 2"X4" ROOF JOISTS ARE NOT ADEQUATE TO CARRY THE LIVE | | AND DEAD LOADS SPECIFIED ON SHEET 3/5. REVISE AS | | REQUIRED OR ENGINEER TO PROVIDE COMPLETE ENGINEERING | | ANALYSIS SHOWING COMPLIANCE. SEC. R301.1 | | FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | B)SPECIFY STRUCTURAL CONNECTOR AT EACH END OF ROOF | | JOISTS. SEC. R301.2.1 FBC-RESIDENTIAL. | | NOTE: COORDINATE WITH CONNECTORS SPECIFIED ON SHEET 3/5 | | ON THE CONNECTOR SCHEDULE. WHO IS THE MANUFACTURER OF | | THE SPECIFIED CONNECTORS. PROVIDE PRODUCT APPROVAL. | | FAC. 61G20.3.001. | | | | C) ROOF OUTRIGGERS. PROVIDE COMPLETE FRAMING DETAILS | | AND SPECIFICATIONS, SPECIFY STRUCTURAL FRAMING MEMBER | | SIZE, SPACING AND CONNECTORS AT EACH END. SEC. R301.2.1 | | FBC-RESIDENTIAL. | | | | D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO | | COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. | | SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: | | NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO | | BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS | | REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 | | FBC-RESIDENTIAL. | | | | 8- CONSTRUCTION OF THE NEW BUILDING IS NOT CLEAR. PLANS | | SUBMITTED HAVE INFORMATION FOR WOOD FRAMED CONSTRUCTION | | AND CONCRETE BLOCK CONSTRUCTION. PROVIDE ONLY THE | | INFORMATION RELEVANT TO THIS PROJECT TO AVOID | | CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS. | | | | 9- DETAIL 4/S1 ON SHEET 2/5 DOESN'T MATCH FLOOR PLAN | | AND INFORMATION ON DETAIL 6/S1 ON SAME SHEET. REVISE AS | | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | 10- PROVIDE COMPLETE OPENING FRAMING DETAIL FOR NEW | | DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS AND | | CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL. | | | | 11- DETAIL 6/S1 ON SHEET 2/5: | | A)ENGINEER TO CLARIFY WHY IS "NEW NON BEARING WALL | | DETAILS (TYP)" IF THIS IS AN EXTERIOR WALL. TYPICALLY | | EXTERIOR WALLS ARE BEARING WALLS. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | B)CORNER DETAIL IS NOT CLEAR AND DOESN'T SEEM TO BE | | CORRECT. CLEARLY SHOW THE CORNER FRAMING MEMBERS AND | | HOW THE CORNER IS REINFORCED. SEC. R301.2.1 | | FBC-RESIDENTIAL. | | NOTE: SEE AWC-WCD1-CONVENTIONAL WOOD FRAME DETAILS FOR | | REFERENCE AND REVISE CORNER DETAIL AS REQUIRED. | | | | C)BOTTOM PLATE ANCHORING. SPECIFY HOW MUCH EMBEDMENT IS | | REQUIRED FOR THE 5/8" ANCHOR BOLT. SEC. R301.2.1 | | FBC-RESIDENTIAL. | | | | D)SPECIFY ON ALL WALL SECTIONS THE MIN. 6" CLEARANCE | | FOR TERMITE INSPECTION BETWEEN THE EXTERIOR WALL | | COVERING AND FINAL EARTH GRADE AS REQUIRED BY SEC. | | R318.7 FBC-RESIDENTIAL. | | | | 12- SHEET 3/5: | | A) DETAILS 8/S2 AND 4/S2 KEYED ON THE NEW GUEST HOUSE | | PLAN DETAIL 1/S2 DON'T CORRESPOND TO THIS PROJECT. | | REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | B)SPECIFICATIONS ON DETAIL 5/S2 ARE NOT CLEAR. SEC. | | 107.2.1 CITY AMENDMENTS. | | | | C) DETAIL 3/S2: PROVIDE COMPLETE SPECIFICATIONS FOR THE | | BOND BEAM. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 13- DETAIL 7/S2 ON SHEET 3/5: | | A) ASPHALT SHINGLES CAN NOT BE INSTALLED ON A FLAT | | ROOF. REVISE AS REQUIRED. | | SEC. R905.2.2 FBC-RESIDENTIAL. | | | | B)WALL SECTION IS NOT CLEAR. WHY PROVIDING | | SPECIFICATIONS FOR WALL STUD AND CONCRETE BLOCK. ALSO, | | PROVIDE COMPLETE INFORMATION FOR EXTERIOR AND INTERIOR | | CONSTRUCTION. SEC. 107.2.1 CITY AMENDMENTS. | | | | C)R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF JOIST. | | REVISE AS REQUIRED. COORDINATE WITH SPECIFIED CROSS | | VENTILATION. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 14- ENGINEER OF RECORD TO SPECIFY ROOF CROSS | | VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. | | NOTE: R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF | | JOISTS. ALSO, IT DOESN'T ALLOW ROOF CROSS VENTILATION. | | SEC. R806.3 FBC-RESIDENTIAL. | | ENGINEER MAY DESIGN AN UNVENTED ATTIC. SEE SEC. R806.5 | | FBC-RESIDENTIAL AND PROVIDE COMPLETE SPECS SHOWING HOW | | DOING IT. | | | | 15- ENGINEER OF RECORD TO SPECIFY HOW PROVIDING HEAT AS | | REQUIRED BY SEC. R303.10 FBC-RESIDENTIAL. | | | | 16- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE | | TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL). | | | | B)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | C) ALUMINUM VENTED SOFFIT AS SPECIFIED ON PLANS. | | | | 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | 18- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | AMENDMENTS. | | VALUATION UPDATED TO $60,348. THE PERMIT FEE BALANCE IS | | $913.04. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-11 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-11 |
Time |
08:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2023-05-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-05-12 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-05-12 |
Time |
09:52 |
Sent To |
|
|
Notes |
2023-05-12 09:59:09 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | BUILDING PLANS AND ELECTRICAL PLANS DO NOT MATCH. | | LAYOUT OF ROOMS IS NOT THE SAME. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-20 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-07-19 |
Time |
16:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2023-07-31 |
Time |
|
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-07-31 |
Time |
11:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-05-22 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-05-22 |
Time |
12:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-02-17 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-01-19 |
Time |
16:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-10-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-21 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-09-27 |
Time |
08:52 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-08-01 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-06-29 |
Time |
06:19 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
F |
Date |
2023-05-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-05-11 |
Time |
18:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-05-11 |
Time |
18:01 |
Sent To |
|
|
Notes |
2023-05-11 18:03:31 | IMPACT FEES QUESTIONNAIRE IS UPLAODED TO PROJECTDOX. | | SEND EMAIL TO LIBRARIAN WHEN APPROVED. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2022-10-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-21 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-21 |
Time |
17:40 |
Sent To |
|
|
Notes |
2022-10-21 17:40:23 | IMPACT FEES | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | IMPACT FEE ASSESSMENT. | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-08-01 |
Time |
17:32 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-08-01 |
Time |
12:57 |
Sent To |
|
|
Notes |
2022-08-01 17:32:50 | IMPACT FEES | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | IMPACT FEE ASSESSMENT. | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-07-18 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2023-07-18 |
Time |
13:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2023-05-12 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-05-12 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-05-12 |
Time |
09:08 |
Sent To |
|
|
Notes |
2023-05-12 09:10:22 | 4TH PLUMBING REVIEW | | | | | | | | 1. 2017 WPB AMENDS 107.3.5.1.3 - THE NEW SET OF PLANS | | BY THE NEW DESIGNER NEEDS A NEW SET OFMECHANICAL PAGES | | DESIGNED BY THE NEW DESIGNER. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2023-01-20 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-01-20 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-20 |
Time |
10:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2022-09-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-09-30 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-09-30 |
Time |
12:54 |
Sent To |
|
|
Notes |
2022-09-30 12:57:30 | 2ND ATTEMPT: | | PROVIDE A MECHANICAL DRAWING SHOWING THE MINISPLITS | | LOCATIONS AND THE TIE DOWN OF THE CONDENSING UNIT ALONG | | WITH THE BATH EXHAUST FAN AND TERMINATION LOCATION FOR | | THE EXHAUST. | | PROVIDE THE CFM'S OF THE HOOD EXHAUST FAN MOTOR AND THE | | TERMINATION LOCATION.FBC 107.3.5 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2022-07-06 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-07-06 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-07-06 |
Time |
13:29 |
Sent To |
|
|
Notes |
2022-07-06 13:33:20 | PROVIDE A MECHANICAL SCOPE OF WORK FOR THIS PROJECT | | INCLUDING THE INFORMATION BELOW: FBC 107.2.1 | | PROVIDE ENERGY CALCULATIONS. | | PROVIDE MECHANICAL EQUIMENT SIZING CALCULATIONS. | | SHOW BATH EXHAUST FAN AND TERMINATION LOCATION FOR THE | | EXHAUST. | | PROVIDE THE CFM'S OF THE HOOD EXHAUST FAN MOTOR AND THE | | TERMINATION LOCATION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2023-07-11 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-07-11 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-07-11 |
Time |
07:33 |
Sent To |
|
|
Notes |
2023-07-11 07:35:37 | 5TH PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - THE REQUIRED RISER | | HAS BEEN REMOVED FROM THE PLANS. THE FLOOR PLAN SHOWN | | DOES NOT INDICATE A CODE COMPLIANT DRAIN, WASTE AND | | VENT SYSTEM. PLEASE AMEND THE FLOOR PLAN AND SHOW A | | CODE COMPLIANT DRAIN, WASTE AND VENT SYSTEM IN | | ISOMETRIC FORM FOR REVIEW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2023-05-12 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-05-12 |
Time |
07:27 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-05-12 |
Time |
07:27 |
Sent To |
|
|
Notes |
2023-05-12 07:28:30 | 4TH PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMENDS 107.3.5.1.3 - THE NEW SET OF PLANS | | BY THE NEW DESIGNER NEEDS A NEW SET OF PLUMBING PAGES | | DESIGNED BY THE NEW DESIGNER. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2023-01-20 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-01-20 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-01-20 |
Time |
08:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-09-29 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-09-29 |
Time |
12:46 |
Sent To |
|
|
Notes |
2022-09-29 12:47:02 | 2ND PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. ----NOT SUMBITTED ----- 2017 WPB AMEND - 107.3.5.3 | | (12.) -- PLEASE SUBMIT A PLUMBING RISER. PLEASE INCLUDE | | THE SIGNATURE OF THE PERSON WHO DESIGNED THE ISOMETRIC | | AS A REQUIREMENT OF 107.2.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-07-01 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-07-01 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-07-01 |
Time |
12:00 |
Sent To |
|
|
Notes |
2022-07-01 12:22:53 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMEND - 107.3.5.3 (12.) -- PLEASE SUBMIT A | | PLUMBING RISER. PLEASE INCLUDE THE SIGNATURE OF THE | | PERSON WHO DESIGNED THE ISOMETRIC AS A REQUIREMENT OF | | 107.2.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
5 |
Status |
F |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-07-24 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-07-24 |
Time |
10:30 |
Sent To |
|
|
Notes |
2023-07-24 10:31:19 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
F |
Date |
2023-05-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-05-11 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-05-11 |
Time |
18:05 |
Sent To |
|
|
Notes |
2023-05-11 18:06:17 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-02-17 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-02-17 |
Time |
12:21 |
Sent To |
|
|
Notes |
2023-02-17 12:21:17 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | PLAN | | REVIEW COMMENTS | | | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2022-10-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-21 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-21 |
Time |
17:38 |
Sent To |
|
|
Notes |
2022-10-21 17:39:27 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-08-01 |
Time |
17:33 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-08-01 |
Time |
17:32 |
Sent To |
|
|
Notes |
2022-08-01 17:35:04 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-07-24 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-07-24 |
Time |
10:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2023-05-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-05-11 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-05-11 |
Time |
18:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-02-17 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-02-17 |
Time |
09:56 |
Sent To |
|
|
Notes |
2023-01-20 10:46:44 | MECHANICAL DIGITAL SIGNATURE APPROVED ME |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-10-21 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-21 |
Time |
17:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-07-01 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-07-01 |
Time |
11:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2023-07-31 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-07-31 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-07-31 |
Time |
11:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-05-22 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-05-22 |
Time |
12:42 |
Sent To |
|
|
Notes |
2023-05-22 12:42:40 | 5/22/2023 | | FAILED | | | | A STOVE CANNOT BE INSTALLED BECAUSE AN ADDITIONAL UNIT | | WOULD NOT BE ALLOWED ON THIS PROPERTY. YOU DONT MEET | | THE LOT WIDTH OF 60FT. | | | | YOU ARE ALLOWED TO HAVE AN ACCESORY STRUCTURE BUT IT | | CAN NOT BE RENTED OUT AND NO STOVE COULD BE INSTALLED. | | | | HEIGHT ELEVATION OF THE STRUCTURE | | | | | | | | ARTICLE III. SECTION 94-74 | | MINIMUM LOT DIMENSIONS FOR SINGLE-FAMILY USE WITH | | ACCESSORY APARTMENT. | | A. | | LOT AREA: 6,000 FEET; | | B. | | LOT WIDTH: 60 FEET; | | C. | | LOT WIDTH OF PARCELS DESCRIBED IN SUBSECTION | | 94-71(D)(2): 75 FEET; | | D. | | LOT DEPTH OF PARCELS DESCRIBED IN SUBSECTION | | 94-71(D)(2): 100 FEET MEASURED FROM THE EAST PROPERTY | | LINE TO THE WEST PROPERTY LINE AT THE SHORTEST DISTANCE | | BETWEEN THE PROPERTY LINES. THE EAST PROPERTY LINES OF | | LOTS DESCRIBED IN SUBSECTIONS 94-71(D)(2)(B) AND (D) | | THAT ARE PARALLEL TO AND ABUT EITHER FLAGLER DRIVE OR | | FLAGLER COURT SHALL BE CONSIDERED THE FRONT PROPERTY | | LINES. | | | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2023-01-24 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-01-24 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-01-24 |
Time |
11:23 |
Sent To |
|
|
Notes |
2023-01-24 11:32:56 | 1/24/2023 | | FAILED | | | | A STOVE CANNOT BE INSTALLED BECAUSE AN ADDITIONAL UNIT | | WOULD NOT BE ALLOWED ON THIS PROPERTY. YOU DONT MEET | | THE LOT WIDTH OF 60FT. | | | | YOU ARE ALLOWED TO HAVE AN ACCESORY STRUCTURE BUT IT | | CAN NOT BE RENTED OUT AND NO STOVE COULD BE INSTALLED. | | | | HEIGHT ELEVATION OF THE STRUCTURE | | | | | | | | ARTICLE III. SECTION 94-74 | | MINIMUM LOT DIMENSIONS FOR SINGLE-FAMILY USE WITH | | ACCESSORY APARTMENT. | | A. | | LOT AREA: 6,000 FEET; | | B. | | LOT WIDTH: 60 FEET; | | C. | | LOT WIDTH OF PARCELS DESCRIBED IN SUBSECTION | | 94-71(D)(2): 75 FEET; | | D. | | LOT DEPTH OF PARCELS DESCRIBED IN SUBSECTION | | 94-71(D)(2): 100 FEET MEASURED FROM THE EAST PROPERTY | | LINE TO THE WEST PROPERTY LINE AT THE SHORTEST DISTANCE | | BETWEEN THE PROPERTY LINES. THE EAST PROPERTY LINES OF | | LOTS DESCRIBED IN SUBSECTIONS 94-71(D)(2)(B) AND (D) | | THAT ARE PARALLEL TO AND ABUT EITHER FLAGLER DRIVE OR | | FLAGLER COURT SHALL BE CONSIDERED THE FRONT PROPERTY | | LINES. | | | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2022-09-30 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-09-30 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-09-30 |
Time |
13:56 |
Sent To |
|
|
Notes |
2022-09-30 13:57:58 | 07/05/22 FAILED - NEED TO PROVIDE A SURVEY OF THE | | PROPERTY. | | | | ADDITIONALLY,PROVIDE PROOF THAT THE FOLLOWING STANDARDS | | ARE MET | | | | ADDITIONAL STANDARDS. | | ALL ACCESSORY APARTMENTS MUST COMPLY WITH THE | | DEVELOPMENT STANDARDS FOR RESIDENTIAL ACCESSORY | | STRUCTURES. | | LOT WIDTH: 60 FEET | | | | PARKING: ONE PARKING SPACE SHALL BE PROVIDED FOR THE | | APARTMENT AND TWO FOR THE PRINCIPAL STRUCTURE ON SITE. | | | | | | PLEASE SHOW ALL PARKING, BUILDING ELEVATIONS, AND | | SETBACKS ON A SURVEY/SITE PLAN OF THE PROPERTY | | | | ALEXANDER FOWLKES | | [email protected] | | 5618221431 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-07-05 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-07-05 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-07-05 |
Time |
16:35 |
Sent To |
|
|
Notes |
2022-07-05 16:45:10 | 07/05/22 FAILED - NEED TO SHOW THE PROPOSED IMPROVEMENT | | ON A SURVEY. ADDITIONALLY, ACCESSORY APARTMENTS MUST | | MEET THE FOLLOWING STANDARDS | | | | ADDITIONAL STANDARDS. | | ALL ACCESSORY APARTMENTS MUST COMPLY WITH THE | | DEVELOPMENT STANDARDS FOR RESIDENTIAL ACCESSORY | | STRUCTURES. | | LOT WIDTH: 60 FEET | | MAXIMUM UNIT SIZE: 800 SQUARE FEET. | | SETBACKS: SEE SUBSECTION 94-305(B)(2) | | PARKING: ONE PARKING SPACE SHALL BE PROVIDED FOR THE | | APARTMENT AND TWO FOR THE PRINCIPAL STRUCTURE ON SITE. | | MAXIMUM HEIGHT: ACCESSORY APARTMENTS SHALL NOT EXCEED | | 25 FEET IN HEIGHT. | | | | PLEASE SHOW ALL PARKING, BUILDING ELEVATIONS, AND | | SETBACKS | | | | ALEXANDER FOWLKES | | [email protected] | | 5618221431 |
|
|