Plan Review Details - Permit 22060565
Plan Review Stops For Permit 22060565
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-06-15 Cont ID  
Sent By ccole Date 2022-06-15 Time 10:42 Rev Time 0.00
Received By ccole Date 2022-06-15 Time 06:58 Sent To  
Notes
2022-06-15 10:43:281ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22060733
 6/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I WAS UNABLE TO LOCATE ANY PREVIOUS GAS PIPING
 PERMIT RECORDS FOR 731 HIGH ST., AND UNABLE TO VERIFY
 THE EXISTING 1-1/4 GALVANIZED UNDERGROUND GAS PIPING
 WAS LEGALLY PERMITTED AND INSPECTED- SECS. 105.1 &
 107.2.1 WPB. IT APPEARS THAT THE GAS PIPING TO THE POOL
 HEATER AND ANY OTHER "EXISTING" GAS PIPING AT THE
 RESIDENCE MUST BE REVIEWED AND APPROVED AS NEW
 INSTALLATIONS. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 &
 G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS-
 THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) PROVIDE A BASIC SITE PLAN THAT SHOWS THE LOCATION OF
 THE POOL HEATER WITH CLEARANCE DISTANCE MEASUREMENTS TO
 THE BUILDING, WINDOW AND DOOR OPENINGS, AND OTHER AIR
 INTAKES INTO THE BUILDING- SECS. G2427.8, AND G2441.1
 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER- SEC. G2441.1 FBC RES.
  
 4) PLEASE NOTE THE RESUBMITTED RISER SHALL INCLUDE THE
 ADDRESS OF THE PROPERTY, AND THE PRINTED NAME AND
 SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO PREPARED
 THE DRAWING- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-06-15 Time   Rev Time 0.00
Received By cdecoeur Date 2022-06-14 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-06-15 Cont ID  
Sent By ccole Date 2022-06-15 Time 10:29 Rev Time 0.00
Received By ccole Date 2022-06-15 Time 06:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-15 Cont ID  
Sent By ccole Date 2022-06-15 Time 10:29 Rev Time 0.00
Received By ccole Date 2022-06-15 Time 06:58 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved