Plan Review Details - Permit 22060560
Plan Review Stops For Permit 22060560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-24 Cont ID  
Sent By rmcphers Date 2022-08-24 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2022-08-24 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 14:02 Sent To  
Notes
2022-08-03 14:05:52GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE DISTANCE FROM THE GENERATOR EXHAUST
 TO ANY BUILDING OPENINGS - FBC R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 15:12 Rev Time 0.00
Received By jleahy Date 2022-08-03 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-24 Cont ID  
Sent By rmcphers Date 2022-08-24 Time 08:37 Rev Time 0.00
Received By rmcphers Date 2022-08-16 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 15:12 Rev Time 0.00
Received By jleahy Date 2022-07-20 Time 06:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 14:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-22 Cont ID  
Sent By asangele Date 2022-08-22 Time 14:48 Rev Time 0.00
Received By asangele Date 2022-08-22 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By asangele Date 2022-07-26 Time 14:55 Rev Time 0.00
Received By asangele Date 2022-07-26 Time 14:55 Sent To  
Notes
***NONE***