Plan Review Details - Permit 22060556
Plan Review Stops For Permit 22060556
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-21 Cont ID  
Sent By cthroop Date 2022-12-21 Time 16:06 Rev Time 0.00
Received By cthroop Date 2022-12-21 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 07:06 Rev Time 0.00
Received By cthroop Date 2022-08-30 Time 06:24 Sent To  
Notes
2022-08-30 07:08:26PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1.
  
 2.
  
 SHUTTERS
 3. PROVIDE A SCHEDULE OF OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES.
 1609.1.2 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN
 BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS
 OF ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS)
 OR TAS 201, 202 AND 203, AAMA 506, ASTM E1996 AND ASTM
 E1886 REFERENCED HEREIN, OR AN APPROVED
 IMPACT-RESISTANT STANDARD AS FOLLOWS:
  
 WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE
 FACTORS THAT APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 NOTICE: I HAVE UPLOADED A COPY OF THE CITY'S SHUTTER
 SCHEDULE TO PROJECT DOX FOR YOUR REVIEW AND OR USE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-06 Cont ID  
Sent By cthroop Date 2022-08-06 Time 08:51 Rev Time 0.00
Received By cthroop Date 2022-08-06 Time 08:51 Sent To  
Notes
2022-08-06 09:01:48PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA
 FOR THE PROPOSED EXTERIOR DOOR (#12) TO BE INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOA?S DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. IDENTIFY THE LOCATION OF THE TWO SHUTTERS ON THE
 FLOOR PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 SHUTTERS
 3. PROVIDE A SCHEDULE OF OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES.
 1609.1.2 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN
 BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS
 OF ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS)
 OR TAS 201, 202 AND 203, AAMA 506, ASTM E1996 AND ASTM
 E1886 REFERENCED HEREIN, OR AN APPROVED
 IMPACT-RESISTANT STANDARD AS FOLLOWS:
  
 WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE
 FACTORS THAT APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 NOTICE: I HAVE UPLOADED A COPY OF THE CITY'S SHUTTER
 SCHEDULE TO PROJECT DOX FOR YOUR REVIEW AND OR USE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-21 Cont ID  
Sent By cthroop Date 2022-12-21 Time 16:07 Rev Time 0.00
Received By cthroop Date 2022-11-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-30 Cont ID  
Sent By cthroop Date 2022-08-30 Time 07:06 Rev Time 0.00
Received By cthroop Date 2022-08-16 Time 07:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-06 Cont ID  
Sent By cthroop Date 2022-08-06 Time 09:01 Rev Time 0.00
Received By cthroop Date 2022-06-10 Time 20:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-08-06 Cont ID  
Sent By cthroop Date 2022-08-06 Time 08:51 Rev Time 0.00
Received By cthroop Date 2022-08-06 Time 08:51 Sent To  
Notes
***NONE***