Plan Review Stops For Permit 22060498 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-06 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-06 |
Time |
17:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-01 |
Time |
12:43 |
Sent To |
|
|
Notes |
2022-09-01 12:44:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 107, SEE PREVIOUS COMMENTS. THE SURVEY STILL | | SHOWS AN EXISTING FENCE. THERE IS A NEW PERMIT | | APPLICATION IN PLAN REVIEW. PLEASE SUBMIT A SURVEY/SITE | | PLAN THAT DOES NOT REFER TO AN EXISTING FENCE TO SERVE | | AS THE POOL BARRIER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-15 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-15 |
Time |
17:53 |
Sent To |
|
|
Notes |
2022-08-15 17:55:51 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | FROM PREVIOUS LIST, NOT ADDRESSED: | | | | 2. PROVIDE A PERMIT NUMBER FOR THE "EXISTING FENCE". | | OUR SYSTEM GOES BACK TO 1999 AND I WAS UNABLE TO FIND A | | FENCE PERMIT. IF YOU WISH TO SUBMIT A RECORDS RESEARCH | | REQUEST: | | | | HTTPS://WESTPALMBEACHFL.GOVQA.US/WEBAPP/_RS/(S(ZDXLAPYW | | FWXQY4YPMZC43LNR))/SUPPORTHOME.ASPX | | | | IF THERE IS NO PERMIT FOR THE "EXISTING FENCE" (MUST BE | | ON THE SUBJECT PROPERTY), YOU MAY REVISE THE PLAN TO | | INDICATE THAT A POOL BARRIER PERMIT WILL BE SUBMITTED. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-02 |
Time |
18:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-02 |
Time |
18:04 |
Sent To |
|
|
Notes |
2022-08-02 18:06:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | FROM PREVIOUS LIST, NOT ADDRESSED: | | | | 1. FBC R 4501.17.1.9(3), FBC R CHAPTER 46, SEE THE | | POOLGUARD SPECS. IT STATES IT COMPLIES (ON PAGE 2) WITH | | ASTM F2208-2008, THIS SHOULD BE ASTMF2208-2014. | | | | 2. NEW COMMENT - SURVEY SHOWS AN "EXISTING FENCE". THE | | PLAN IS DIFFICULT TO READ. PROVIDE A SURVEY WITHOUT ALL | | OF THE MARKINGS. PROVIDE A PERMIT NUMBER FOR THE FENCE. | | OUR SYSTEM GOES BACK TO 1999 AND I WAS UNABLE TO FIND A | | FENCE PERMIT. IF YOU WISH TO SUBMIT A RECORDS RESEARCH | | REQUEST: | | | | HTTPS://WESTPALMBEACHFL.GOVQA.US/WEBAPP/_RS/(S(ZDXLAPYW | | FWXQY4YPMZC43LNR))/SUPPORTHOME.ASPX | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-20 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-20 |
Time |
11:56 |
Sent To |
|
|
Notes |
2022-07-20 12:38:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC R 4501.17.1.9(3), FBC R CHAPTER 46, SEE THE | | POOLGUARD SPECS. IT STATES IT COMPLIES (ON PAGE 2) WITH | | ASTM F2208-2008, THIS SHOULD BE ASTMF2208-2014. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-06-27 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-06-27 |
Time |
11:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-09-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-13 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-09-02 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-24 |
Time |
17:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-15 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-11 |
Time |
09:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-02 |
Time |
18:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-29 |
Time |
15:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-20 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-06-09 |
Time |
04:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2022-06-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-15 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-15 |
Time |
17:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-01 |
Time |
12:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-15 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-15 |
Time |
17:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-06-27 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-06-27 |
Time |
11:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2022-09-08 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-09-08 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-09-08 |
Time |
16:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-08-26 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-08-26 |
Time |
14:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-08-15 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-08-15 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-08-15 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2022-08-02 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-08-02 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-08-02 |
Time |
15:35 |
Sent To |
|
|
Notes |
2022-08-02 15:41:01 | 08/02/22 | | | | I CAN'T TELL HOW FAR BACK THE POOL EQUIPMENT IS SETBACK | | ON THE SURVEY, PLEASE PROVIDE A CLEARER MARKUP ON THE | | SURVEY. | | | | PREVIOUS COMMENTS NOT ADDRESSED: | | PER CITY CODE, MECHANICAL EQUIPMENT CANNOT PROTRUDE | | MORE THAN 4 FT INTO ANY SETBACK .THE PROPOSED POOL | | EQUIPMENT ENCROACHES TOO FAR INTO THE REAR SETBACK OF | | 12.5 FEET. IT MUST BE SETBACK AT LEAST 8.5 FEET FROM | | THE REAR PROPERTY LINE. | | | | THE PERMIT APPLICATION ALSO MENTIONS A DECK BUT THIS IS | | NOT SHOWN ON THE POOL PLAN. THIS IS FINE BUT IT MEANS | | THAT A DECK WILL NOT BE PERMITTED UNDER THIS PERMIT. | | | | | | ALEXANDER FOWLKES | | [email protected] | | 5618221431 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
Sent By |
afowlkes |
Date |
2022-06-14 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
afowlkes |
Date |
2022-06-14 |
Time |
11:30 |
Sent To |
|
|
Notes |
2022-06-14 11:33:33 | 06/14/22 FAILED - PER CITY CODE, MECHANICAL EQUIPMENT | | CANNOT PROTRUDE MORE THAN 4 FT INTO ANY SETBACK .THE | | PROPOSED POOL EQUIPMENT ENCROACHES TOO FAR INTO THE | | REAR SETBACK OF 12.5 FEET. IT MUST BE SETBACK AT LEAST | | 8.5 FEET FROM THE REAR PROPERTY LINE. | | | | ADITIONALLY, PLEASE SHOW THE LOCATION OF THE PROPOSED | | FENCE ENCLOSURE ON THE POOL PLAN. | | | | THE PERMIT APPLICATION ALSO MENTIONS A DECK BUT THIS IS | | NOT SHOWN ON THE POOL PLAN. THIS IS FINE BUT IT MEANS | | THAT A DECK WILL NOT BE PERMITTED UNDER THIS PERMIT. | | | | ALEXANDER FOWLKES | | [email protected] | | 5618221431 |
|
|