Plan Review Details - Permit 22060480
Plan Review Stops For Permit 22060480
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By pleduc Date 2022-06-13 Time   Rev Time 0.00
Received By pleduc Date 2022-06-13 Time 11:43 Sent To  
Notes
2022-06-13 11:44:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE MASTER PERMIT # 22030450 FOR THE NORTH BUILDING
 HAS BEEN REJECTED DUE IN PART OF THE REQUIREMENTS OF
 F.A.C. 69G15-32.
  
 THE REQUIRED FIRE SPRINKLER DOCUMENTS WHERE NO
 SUBMITTED WITH THE MASTER.
  
 PLEASE REVIEW THOSE REQUIRMENTS AND RESUBMIT AFTER THE
 MASTER PERMIT HAS BEEN REVIEWED AND APPROVED.
  
  
 1A) IS LSM THE EOR FOR THIS FS SYSTEM INSTALL?
  
 PER F.A.C. 69G15-32 THE EOR SHALL PROVIDE PROPER
 DOCUMENTATION OF DEFFERAL SHALL BE PROVIDED
  
 61G15-32.001 GENERAL RESPONSIBILITY.
  
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL BE PREPARED
 IN ACCORDANCE WITH APPLICABLE TECHNOLOGY AND THE
 REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. THE
 DOCUMENTS SHALL IDENTIFY THE ENGINEER OF RECORD FOR THE
 PROJECT. BOTH THE ENGINEER OF RECORD FOR THE FIRE
 PROTECTION SYSTEM AND THE DELEGATED ENGINEER, IF
 UTILIZED, SHALL COMPLY WITH THE REQUIREMENTS OF THE
 GENERAL RESPONSIBILITY RULES, CHAPTER 61G15-30, F.A.C.,
 AND WITH THE REQUIREMENTS OF THE MORE SPECIFIC RULES
 CONTAINED HEREIN. THE ENGINEER OF RECORD FOR THE FIRE
 PROTECTION SYSTEM(S) SHALL PROVIDE DESIGN REQUIREMENTS
 IN WRITING TO THE DELEGATED ENGINEER IF ONE IS USED AND
 SHALL REVIEW THE DESIGN DOCUMENTS OF THE DELEGATED
 ENGINEER FOR CONFORMANCE WITH HIS WRITTEN INSTRUCTIONS
 IN ACCORDANCE WITH RULE 61G15-30.005, F.A.C. ANY FIRE
 PROTECTION DELEGATED ENGINEERING DOCUMENTS MUST BE
 INCLUDED IN THE FINAL SET OF DOCUMENTS FILED FOR
 PERMIT.
  
 PLEASE REVIEW AND COMPLY WITH THE REQUIREMENTS AS
 APPLICABLE.
  
 RESUBMIT AS APPLICABLE WITH ANY OFFICIAL DOCUMENTS
 ATTACHED.
  
  
 2) ANY FIRE LINE UNDERGROUND, INCLUDING THE DDCV &
 FDC'S, ASSOCIATED WITH THIS FS SYSTEM SHALL BE
 INSTALLED UNDER SEPARATE PERMIT & SHOP DRAWINGS IN
 COMPLIANCE WITH NFPA 24 AND MANUFACTURE'S
 SPECIFICATIONS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-14 Cont ID  
Sent By aoliver Date 2022-06-14 Time 08:01 Rev Time 0.00
Received By aoliver Date 2022-06-10 Time 09:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By pvalenti Date 2022-06-13 Time 05:53 Rev Time 0.00
Received By pvalenti Date 2022-06-13 Time 05:53 Sent To  
Notes
2022-06-13 05:56:55SIGNATURE REVIEW DENIED:
  
 THE SUBMITTED PLAN SHEETS AND CALCULATIONS INDICATE
 THAT THEY HAVE BEEN DIGITALLY SIGNED/SEALED BY
 PROFESSIONAL ENGINEER JUAN E. REYES. HOWEVER, THESE
 DOCUMENTS APPEAR TO BE SCANS OF ORIGINALS AND CAN NOT
 BE APPROVED FOR 3RD PARTY VERIFICATION.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  