Plan Review Details - Permit 22060408
Plan Review Stops For Permit 22060408
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By cwalker Date 2022-06-08 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-06-08 13:12:55FIRE COMMENT:
 MODIFICATIONS TO EXISTING PIPING SYSTEMS SHALL REQUIRE
 TESTING AT SYSTEM WORKING PRESSURE. NFPA 13, 25.2.1.4
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-09 Cont ID  
Sent By shill Date 2022-06-09 Time 08:48 Rev Time 0.00
Received By shill Date 2022-06-08 Time 05:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By shill Date 2022-06-09 Time 08:48 Rev Time 0.00
Received By shill Date 2022-06-09 Time 08:48 Sent To  
Notes
***NONE***