Plan Review Details - Permit 22060290
Plan Review Stops For Permit 22060290
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By cpuell Date 2022-06-07 Time 11:35 Rev Time 0.00
Received By cpuell Date 2022-06-07 Time 11:35 Sent To  
Notes
2022-06-07 11:36:08ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-01 Cont ID  
Sent By jgomez Date 2023-06-01 Time 17:51 Rev Time 0.00
Received By jgomez Date 2023-06-01 Time 15:27 Sent To  
Notes
2023-06-01 17:51:20NEW SINGLE FAMILY RESIDENCE(R3) FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290
 1001 WINDSOR AVE
  
 PROVISO NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE
 CLEAR/LEGIBLE PLANS ARE UPLOADED TO PROJECTDOX. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR
 PRODUCT APPROVALS DEFERRED SUBMITTAL).
  
 ***IMPORTANT
 ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED
 AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
  
 7- NEW ENERGY CALCULATIONS SUBMITTED:
 A)FORM 401-10 WAS SUBMITTED. NEED TO SUBMIT CURRENT
 405-2020 FORM.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION.
 REVISE AS REQUIRED.
  
 C)CONCRETE BLOCK INSULATION R-VALUE DOESN???T MATCH
 R-VALUE SPECIFIED ON TYPICAL WALL SECTION. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)REVISE SPACE INFORMATION ON PAGE 2. NUMBER OF
 OCCUPANTS CAN NOT BE 3.5. NEED TO ROUND UP THE NUMBER.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE DOOR ORIENTIN ON PAGE 3. ENTRY DOO IS ON THE
 EAST SIDE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE WINDOWS INFORMATION TO MATCH PLANS. REVISE
 WINDOWS ORIENTATION, WINDOWS FRAME TYPE (ALUMINUM, NOT
 VINYL), WINDOWS AREA AND WINDOWS OVERHANG DEPTH AND
 SEPARATION TO MATCH PLANS. ALSO, THERE IS NOT GLASS
 BLOCK ON PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
  
 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO
 UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 PLANS ARE STILL NOT LEGIBLE.
  
 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8.
 THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE
 ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS
 A-A, B-B AND C-C.
 ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE
 IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS
 ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC.
 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS.
 SEC. R401.3 FC-RESIDENTIAL.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 UNABLE TO READ THE PLANS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 17:36 Rev Time 0.00
Received By jgomez Date 2023-03-03 Time 14:53 Sent To  
Notes
2023-03-03 17:37:27NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290
 1001 WINDSOR AVE
  
 7- ENERGY CALCULATIONS SUBMITTED:
 PREVIOUS COMMENT:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: IF ALL OF THE VALUES LISTED UNDER CLIMATE ZONE 1
 ARE NOT INSTALLED, THEN THIS PRESCRIPTIVE FORM CANNOT
 BE USED. SEE SCOPE INFORMATION ON TOP OF GENERAL
 INSTRUCTIONS OF FORM 402-2020 SUBMITTED.
  
 PREVIOUS COMMENT:
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 R-VALUE SPECIFIED IS INCORRECT. DUCTS R-VALUE IN
 UNCONDITIONED ATTICS IS R-8 NOT R-6.
 ALSO, SPECIFY LOCATION OF AIR HANDLER.
  
 PREVIOUS COMMENT:
 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO
 UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 PLANS NEED TO BE CLEAR TO BE REVIEWED AND STAMPED.
 THOSE WILL BE THE OFFICIAL APPROVED PLANS. IF THE
 ORIGINALS RE NOT CLEAR, THEN THE PLANS WILL NOT BE
 LEGIBLE WHEN PRINTING FOR THE JOB SITE EITHER.
 MECHANICAL REVIEWER HAS COMMENTS REGARDING THIS ISSUE
 ALSO.
 WE NEED LEGIBLE COPIES FOR RECORDS MANAGEMENT. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8.
 THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE
 ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS
 A-A, B-B AND C-C.
 ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE
 IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS
 ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC.
 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS.
 SEC. R401.3 FC-RESIDENTIAL.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 DRAINAGE PLAN IS NOT LEGIBLE. UNABLE TO REVIEW.
 ALSO, ENGINEER DOESN'T SHOW HOW RAISING THE GRADE AT
 THE PERIMETER OF THE LOT. RETAINING WALL REQUIRED?
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 14:21 Rev Time 0.00
Received By lbond Date 2023-02-23 Time 14:20 Sent To  
Notes
2023-01-25 14:23:42NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290 1001 WINDSOR AVE
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 ORIGINAL COMMENT:
 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE
 DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE
 HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR
 HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS
 CLEAR OPENINGS.
  
 RESPONSE:
 WINDOW SIZE WAS NOT REVISED. NEED TO REVISE. TYPICALLY,
 37" X 63" WINDOWS AS SPECIFIED FOR BEDROOM #2 ARE THE
 ONES COMPLYING WITH THE EGRESS REQUIREMENTS. REVISE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING
 SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4
 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
 REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND
 NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL
 SECTION ON SHEET 4.
  
 RESPONSE:
 ROOF SHEATHING SPECIFICATIONS ON TYPICAL WALL SECTION
 ON SHEET 4 WAS NOT REVISED TO SHOW COMPLIANCE. NEED TO
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION
 CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT
 SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON
 SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 R806 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- OK.
 5- OK.
 6- OK.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 R-VALUE SPECIFIED IS INCORRECT. DUCTS DIAMETER IS
 GREATER THAN 3 IN.
 ALSO, SPECIFY LOCATION OF AIR HANDLER.
  
 C)OK.
 D)OK.
 E)OK.
  
 NEW COMMENT BASED ON INFORMATION SUBMITTED:
 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO
 UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8.
 THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE
 ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS
 A-A, B-B AND C-C.
 ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE
 IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS
 ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC.
 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS.
 SEC. R401.3 FC-RESIDENTIAL.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By jgomez Date 2022-08-01 Time 10:16 Rev Time 0.00
Received By jgomez Date 2022-07-29 Time 18:22 Sent To  
Notes
2022-08-01 10:18:17NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290 1001 WINDSOR AVE
  
 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE
 DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE
 HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR
 HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS
 CLEAR OPENINGS.
  
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING
 SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4
 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
 REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND
 NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL
 SECTION ON SHEET 4.
  
 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION
 CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT
 SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON
 SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 R806 FBC-RESIDENTIAL.
  
 4- NORTH ARROW ORIENTATION SHOWN ON ALL PLANS SUBMITTED
 IS INCORRECT. SEE SURVEY AND REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)VENTED ALUMINUM SOFFIT SPECIFIED ON THE TYPICAL WALL
 SECTION.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 C)DUCT TESTING IS REQUIRED. REVISE INFORMATION ON PAGE
 2. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 D)THERE IS NOT PTAC INSTALLED IN THIS HOUSE. REVISE
 INFORMATION SHOWN ON PAGE 2. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 E)WATER HEATER INFORMATION ON PAGE 2 DOESN'T MATCH
 PLANS. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-09 Cont ID  
Sent By fgiaquin Date 2023-03-09 Time 18:59 Rev Time 0.00
Received By fgiaquin Date 2023-03-07 Time 22:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-12 Cont ID  
Sent By fgiaquin Date 2023-01-12 Time 21:09 Rev Time 0.00
Received By fgiaquin Date 2023-01-12 Time 21:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-24 Cont ID  
Sent By fgiaquin Date 2022-06-24 Time 23:25 Rev Time 0.00
Received By fgiaquin Date 2022-06-24 Time 19:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-01 Cont ID  
Sent By jgomez Date 2023-06-01 Time 17:54 Rev Time 0.00
Received By jgomez Date 2023-05-02 Time 18:56 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-09 Cont ID  
Sent By fgiaquin Date 2023-03-09 Time 18:59 Rev Time 0.00
Received By fgiaquin Date 2023-02-22 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 14:42 Rev Time 0.00
Received By jgomez Date 2023-01-05 Time 08:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-01 Cont ID  
Sent By jgomez Date 2022-08-01 Time 10:49 Rev Time 0.00
Received By jgomez Date 2022-06-07 Time 10:14 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 14:24 Rev Time 0.00
Received By jgomez Date 2023-01-25 Time 14:24 Sent To  
Notes
2023-01-25 14:24:35NOTE: IMPACT FEES QUESTIONNAIRE IS ALREADY UPLOADED TO
 PROJECTDOX. THE PERMIT LIBRARIAN WILL EMAIL THE COUNTY
 WHEN THE PERMIT IS CLOSE TO BE APPROVED. JG.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-29 Cont ID  
Sent By jgomez Date 2022-07-29 Time 18:24 Rev Time 0.00
Received By jgomez Date 2022-07-29 Time 18:23 Sent To  
Notes
2022-07-29 18:27:23NOTE: IMPACT FEES QUESTIONNAIRE IS ALREADY UPLOADED TO
 PROJECTDOX. THE PERMIT LIBRARIAN WILL EMAIL THE COUNTY
 WHEN THE PERMIT IS CLOSE TO BE APPROVED. JG.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 07:37 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 07:37 Sent To  
Notes
2023-05-09 07:40:05THE MECHANICAL DRAWING IS A COPY OF THE ORIGINAL. IT
 CANNOT BE READ. PROVIDE A CLEAR DRAWING THAT CAN BE
 READ. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 10:37 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 10:37 Sent To  
Notes
2023-02-27 10:38:08PLEASE UNDERSTAND THAT I CANNOT SEE THE INFORMATION ON
 THIS MECHANICAL DRAWING.
  
 THE DRAWING SUBMITTED IS NOT READABLE. PROVIDE THE
 ORIGINAL SIGNED AND SEALED MECHANICAL DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-06 Cont ID  
Sent By medwards Date 2023-01-06 Time 16:31 Rev Time 0.00
Received By medwards Date 2023-01-06 Time 16:31 Sent To  
Notes
2023-01-06 16:34:17THE DRAWING SUBMITTED IS NOT READABLE. PROVIDE THE
 ORIGINAL SIGNED AND SEALED MECHANICAL DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-06-17 Cont ID  
Sent By medwards Date 2022-06-17 Time 05:40 Rev Time 0.00
Received By medwards Date 2022-06-17 Time 05:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-05-03 Cont ID  
Sent By rwbrown Date 2023-05-03 Time 13:47 Rev Time 0.00
Received By rwbrown Date 2023-05-03 Time 13:47 Sent To  
Notes
2023-05-03 13:48:121ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - FOR SOME REASON THE
 PLUMBING DIAGRAMS PREVIOUSLY APPROVED ARE CROSSED OUT.
 PLEASE RECTIFY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By rwbrown Date 2023-01-06 Time 08:39 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By rwbrown Date 2022-06-08 Time 14:36 Rev Time 0.00
Received By rwbrown Date 2022-06-08 Time 14:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 14:29 Rev Time 0.00
Received By jgomez Date 2023-01-25 Time 14:24 Sent To  
Notes
2023-01-25 14:32:221-SHINGLES GFA NOA 21-1209.01
 2-ROOF UNDERLAYMENT POLYGLASS POLYSTICK NOA 21-1217.02

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By jgomez Date 2022-08-01 Time 10:42 Rev Time 0.00
Received By jgomez Date 2022-08-01 Time 10:41 Sent To  
Notes
2022-08-01 10:43:281-SHINGLES NOA 21-1209.01
 2-ROOF UNDERLAYMENT NOA 21-0602.14

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-05-02 Cont ID  
Sent By ccole Date 2023-05-02 Time 12:13 Rev Time 0.00
Received By ccole Date 2023-05-02 Time 12:13 Sent To  
Notes
2023-05-02 12:19:24SIGNATURE REVIEW FBC- 2020
 PERMIT- 22060290
 5/2/23
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PLAN SHEETS GN, 1, 4, & 8 APPEAR TO BE
 PRINTED COPIES OF DIGITALLY SIGNED AND SEALED PLANS.
 PLANS PREPARED BY FL. LICENSED ENGINEERS THAT ARE
 TRANSMITTED ELECTRONICALLY SHALL BEAR VERIFIABLE
 DIGITAL SEALS AND SIGNATURES OF THE ENGINEERS- FL.
 STATUTE 471.025, AND SECTION 61G15-23.005 FAC. PLANS
 SUBMITTED IN PAPER FORM TO THE FRONT COUNTER OF THE WPB
 BUILDING DEPT. SHALL BEAR EITHER RAISED OR INK SEALS
 AND THE WET SIGNATURES OF THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 17:38 Rev Time 0.00
Received By jgomez Date 2023-03-03 Time 17:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 14:41 Rev Time 0.00
Received By jgomez Date 2023-01-25 Time 14:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By jgomez Date 2022-08-01 Time 10:47 Rev Time 0.00
Received By jgomez Date 2022-08-01 Time 10:43 Sent To  
Notes
2022-08-01 10:48:29SIGNATURE REVIEW
  
 1- ALL DRAWINGS NEED THE ORIGINAL SEAL AND SIGNATURE OF
 THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC
 RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S
 VERIFIABLE DIGITAL SIGNATURE
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-05-16 Cont ID  
Sent By vbroglia Date 2023-05-16 Time 14:12 Rev Time 0.00
Received By vbroglia Date 2023-05-16 Time 14:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-06 Cont ID  
Sent By vbroglia Date 2023-03-06 Time 15:05 Rev Time 0.00
Received By vbroglia Date 2023-03-06 Time 15:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-18 Cont ID  
Sent By vbroglia Date 2023-01-18 Time 12:40 Rev Time 0.00
Received By vbroglia Date 2023-01-18 Time 12:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By vbroglia Date 2022-06-14 Time   Rev Time 0.00
Received By vbroglia Date 2022-06-14 Time 09:08 Sent To  
Notes
***NONE***