Plan Review Details - Permit 22060245
Plan Review Stops For Permit 22060245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 17:26 Rev Time 0.00
Received By shill Date 2022-09-01 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-20 Cont ID  
Sent By shill Date 2022-07-20 Time 09:54 Rev Time 0.00
Received By shill Date 2022-07-20 Time 09:54 Sent To  
Notes
2022-07-20 09:56:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC R 4501.6, SHEET 4 OF 4, GENERAL NOTE 4, NOTE
 REFERS TO 2013 VERSION. SEE FBC R CHAPTER 46, THIS IS
 NOT CORRECT FOR ANSI/APSP/ICC 3, 4 AND 5. EITHER REMOVE
 SPECIFIC VERSION REFERENCE OR UPDATE NOTE TO INCLUDE
 CORRECT VERSIONS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-08 Cont ID  
Sent By ppetty Date 2022-09-08 Time 09:17 Rev Time 0.00
Received By ppetty Date 2022-09-02 Time 17:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-27 Cont ID  
Sent By ppetty Date 2022-06-27 Time 10:28 Rev Time 0.00
Received By ppetty Date 2022-06-27 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-08 Cont ID  
Sent By ppetty Date 2022-09-08 Time 09:17 Rev Time 0.00
Received By ppetty Date 2022-08-26 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-20 Cont ID  
Sent By shill Date 2022-07-20 Time 09:56 Rev Time 0.00
Received By shill Date 2022-06-07 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-29 Cont ID  
Sent By ccole Date 2022-08-29 Time 16:58 Rev Time 0.00
Received By ccole Date 2022-08-29 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-15 Cont ID  
Sent By ccole Date 2022-06-15 Time 12:11 Rev Time 0.00
Received By ccole Date 2022-06-15 Time 11:38 Sent To  
Notes
2022-06-15 12:11:591ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060245
 6/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-4: PROVIDE THE POOL PUMP CURVE ON THE PLAN
 SHEET- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2
 & R4501.7.3 FBC RES.2
  
 2) P-3 & P-4: IF AN AUTOFILL IS TO BE INSTALLED, PLEASE
 SHOW THE LOCATIONS OF THE DEVICE AND THE REQUIRED
 BACKFLOW PREVENTER TO PROTECT THE POTABLE WATER SYSTEM-
 SEC. R4501.9 & P2902.3 FBC RES. PLEASE INDICATE THE
 TYPE OF BACKFLOW PREVENTER TO BE INSTALLED- TABLE
 P2902.3 FBC RES.
  
 3) PLEASE NOTE A RPZ BACKFLOW PREVENTER IS REQUIRED AT
 THE WATER METER TO PROTECT THE POTABLE WATER SERVICE-
 SEC. C & D WPB UTILITIES CROSS-CONNECTION MANUAL. THE
 DEVICE SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC.
 105.1 WPB.
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE HAYWARD
 ANTI-ENTRAPMENT CHANNEL DRAIN ASSEMBLY INCLUDING
 SUCTION OUTLET COVER AND FRAME- SEC. R4501.6.2 &
 R4501.6.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-29 Cont ID  
Sent By ccole Date 2022-08-29 Time 16:58 Rev Time 0.00
Received By ccole Date 2022-08-29 Time 16:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-27 Cont ID  
Sent By ppetty Date 2022-06-27 Time 10:23 Rev Time 0.00
Received By ppetty Date 2022-06-27 Time 10:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By asangele Date 2022-08-23 Time 08:17 Rev Time 0.00
Received By asangele Date 2022-08-23 Time 08:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By asangele Date 2022-06-13 Time 09:55 Rev Time 0.00
Received By asangele Date 2022-06-13 Time 09:55 Sent To  
Notes
2022-06-13 10:03:216/13/2022
 FAIL
 POOL SETBACK FOR HOMES LOCATED IN THE RENAISSANCE (RPD)
 SIDE SETBACK: 5FT
 REAR SETBACK: 5FT
  
 DECK/PATIO SETBACK FOR HOMES LOCATED IN THE RENAISSANCE
 (RPD)
 SIDE SETBACK: 2FT
 REAR SETBACK; 0FT
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]