Plan Review Stops For Permit 22060245 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-09-01 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-09-01 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-20 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-07-20 |
Time |
09:54 |
Sent To |
|
|
Notes |
2022-07-20 09:56:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC R 4501.6, SHEET 4 OF 4, GENERAL NOTE 4, NOTE | | REFERS TO 2013 VERSION. SEE FBC R CHAPTER 46, THIS IS | | NOT CORRECT FOR ANSI/APSP/ICC 3, 4 AND 5. EITHER REMOVE | | SPECIFIC VERSION REFERENCE OR UPDATE NOTE TO INCLUDE | | CORRECT VERSIONS. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-09-08 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-09-08 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-09-02 |
Time |
17:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-06-27 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-06-27 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-09-08 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-09-08 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-08-26 |
Time |
16:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-07-20 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-06-07 |
Time |
06:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-08-29 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-08-29 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-06-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-15 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-15 |
Time |
11:38 |
Sent To |
|
|
Notes |
2022-06-15 12:11:59 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22060245 | | 6/15/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P-4: PROVIDE THE POOL PUMP CURVE ON THE PLAN | | SHEET- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 | | & R4501.7.3 FBC RES.2 | | | | 2) P-3 & P-4: IF AN AUTOFILL IS TO BE INSTALLED, PLEASE | | SHOW THE LOCATIONS OF THE DEVICE AND THE REQUIRED | | BACKFLOW PREVENTER TO PROTECT THE POTABLE WATER SYSTEM- | | SEC. R4501.9 & P2902.3 FBC RES. PLEASE INDICATE THE | | TYPE OF BACKFLOW PREVENTER TO BE INSTALLED- TABLE | | P2902.3 FBC RES. | | | | 3) PLEASE NOTE A RPZ BACKFLOW PREVENTER IS REQUIRED AT | | THE WATER METER TO PROTECT THE POTABLE WATER SERVICE- | | SEC. C & D WPB UTILITIES CROSS-CONNECTION MANUAL. THE | | DEVICE SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. | | 105.1 WPB. | | | | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE HAYWARD | | ANTI-ENTRAPMENT CHANNEL DRAIN ASSEMBLY INCLUDING | | SUCTION OUTLET COVER AND FRAME- SEC. R4501.6.2 & | | R4501.6.6 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-08-29 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-08-29 |
Time |
16:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-06-27 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-06-27 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-08-23 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-08-23 |
Time |
08:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-06-13 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-06-13 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-06-13 |
Time |
09:55 |
Sent To |
|
|
Notes |
2022-06-13 10:03:21 | 6/13/2022 | | FAIL | | POOL SETBACK FOR HOMES LOCATED IN THE RENAISSANCE (RPD) | | SIDE SETBACK: 5FT | | REAR SETBACK: 5FT | | | | DECK/PATIO SETBACK FOR HOMES LOCATED IN THE RENAISSANCE | | (RPD) | | SIDE SETBACK: 2FT | | REAR SETBACK; 0FT | | | | ALEXIS SANGELEER | | ASSOCIATE PLANNER | | [email protected] |
|
|